Pilot-operated pressure reducing regulator for natural gas distribution and industrial fuel gas. NPS 1 to 12 x 6 bodies, inlet up to 400 psig, accurate control down to a 1 psi differential, and an optional Whisper Trim cage for noise reduction.
Key specifications
- Line size range
- NPS 1, 2, 3, 4, 6, 8 x 6 and 12 x 6 (DN 25 to DN 300 x 150)
- Process temperature
- Nitrile -29 to 82 C; fluorocarbon -18 to 149 C; EPR -29 to 135 C
- Pressure rating
- 400 psig / 28 bar maximum inlet pressure, or body rating if lower
- Process connection
- NPT, CL125 FF, CL250 RF, CL150/300/600 RF, BWE, SWE, PN 16/25/40
- Variants
- Pilot-operated; optional Whisper Trim cage for up to 30 dBA noise reduction
- Application
- Natural gas distribution, industrial fuel gas to boilers, furnaces, ovens and mixers
Duty
The 1098-EGR holds a steady downstream pressure on natural gas distribution systems and on industrial fuel gas lines feeding boilers, furnaces, ovens and mixers. A pilot senses outlet pressure and loads the main valve diaphragm, so a small sensing element positions a much larger valve without exposing it to full line pressure.
Low differential capability
Where inlet and outlet pressures sit close together — the usual case on a distribution take-off — the regulator still controls accurately down to about 1 psi of differential. That is the property that decides whether a station can hold setpoint at high flow instead of drifting as demand rises.
Noise
High pressure drop means high gas velocity and noise. The optional Whisper Trim cage cuts sound levels by up to 30 dBA relative to standard trim, which is often what allows a regulator to be installed without a separate silencer or a heavier pipe schedule.
Sizes, connections and temperature
Body sizes run from NPS 1 to NPS 12 x 6, with NPT, CL125 FF, CL250 RF, CL150/300/600 RF, BWE, SWE and PN 16/25/40 connections. Maximum inlet pressure is 400 psig or the body rating, whichever is lower. Elastomer choice sets the temperature window: nitrile -29 to 82 °C, fluorocarbon -18 to 149 °C, EPR -29 to 135 °C.
Specifying
State inlet and outlet pressure, maximum and minimum flow, gas composition, allowable noise, body size and connection, and whether the station needs a monitor or slam-shut upstream. The trim and spring selection follows from those figures, not from the body size alone.
Specifications
| Attribute | Value |
|---|---|
| Line size range | NPS 1, 2, 3, 4, 6, 8 x 6 and 12 x 6 (DN 25 to DN 300 x 150) |
| Process temperature | Nitrile -29 to 82 C; fluorocarbon -18 to 149 C; EPR -29 to 135 C |
| Pressure rating | 400 psig / 28 bar maximum inlet pressure, or body rating if lower |
| Process connection | NPT, CL125 FF, CL250 RF, CL150/300/600 RF, BWE, SWE, PN 16/25/40 |
| Variants | Pilot-operated; optional Whisper Trim cage for up to 30 dBA noise reduction |
| Application | Natural gas distribution, industrial fuel gas to boilers, furnaces, ovens and mixers |