Fisher 1190 Pilot-Operated Gas Blanketing Regulator
Purchase options
Request a quote
- Availability
- Call for availability Originalx
Independent supplier
Sproh is an independent supplier and is not an authorized distributor or official representative of Fisher or Emerson.
Overview
Pilot-operated blanketing regulator built as an assembly: EGR main valve, Type 1098 actuator, T205P sensing pilot and MR95H supply regulator. Holds blanket pressures from 0.25 in. w.c. on large tanks and vessels.
Key specifications
- Line size range
- NPS 1, 2, 3, 4, 6, 8 x 6 and 12 x 6 (DN 25 to DN 300 x 150)
- Process temperature
- NBR and FEP -29 to 82 C; FKM 4 to 149 C; EPDM -29 to 135 C
- Pressure rating
- Main valve 400 psig / 27.6 bar; maximum operating inlet 200 psig cast iron, 300 psig steel or stainless
- Measurement range
- Pilot outlet settings from 0.25 in. w.c. to 7 psig (0.6 mbar to 0.48 bar) over seven springs
- Application
- Tank and vessel blanketing on large storage tanks with very low blanket pressure
- Material of construction
- Type EGR main valve with Type 1098 actuator; Type T205P pilot; Type MR95H supply regulator
An assembly, not a single valve
The 1190 designation covers a built-up blanketing regulator: a Type EGR main valve with a Type 1098 actuator, a Type T205P sensing pilot and a Type MR95H supply regulator. What you specify is therefore the main valve body and trim, the main valve spring (which sets how much differential is available), the pilot spring that sets blanket pressure, and the supply regulator.
Why blanketing needs its own regulator
Tank blanketing holds a slight positive pressure of inert gas over a stored liquid so air cannot enter and so the vapour space does not collapse during pump-out. The pressures are tiny — down to 0.25 in. w.c. — which is why a standard pressure reducing regulator cannot do the job: it needs a sensing pilot that reads inches of water and a supply regulator that keeps its own inlet steady.
Ranges and sizes
Main valve bodies run from NPS 1 to 12 x 6 with cast iron, WCC steel or CF8M stainless, and NPT, SWE, BWE, CL125 FF, CL250 RF, CL150/300/600 RF or PN connections. Maximum main valve inlet is 400 psig, but maximum operating inlet is 200 psig on cast iron and 300 psig on steel or stainless. Seven pilot springs cover outlet settings from 0.25 in. w.c. up to 7 psig.
Installation points that decide whether it works
Registration is by external control line — the sense point must be in the vapour space, away from the gas inlet, or the regulator will chase its own supply. The pilot needs a clean, dry supply; the MR95H exists to guarantee that. Temperature limits are set by elastomer: NBR and FEP -29 to 82 °C, FKM 4 to 149 °C, EPDM -29 to 135 °C.
Specifications
| Attribute | Value |
|---|---|
| Line size range | NPS 1, 2, 3, 4, 6, 8 x 6 and 12 x 6 (DN 25 to DN 300 x 150) |
| Process temperature | NBR and FEP -29 to 82 C; FKM 4 to 149 C; EPDM -29 to 135 C |
| Pressure rating | Main valve 400 psig / 27.6 bar; maximum operating inlet 200 psig cast iron, 300 psig steel or stainless |
| Measurement range | Pilot outlet settings from 0.25 in. w.c. to 7 psig (0.6 mbar to 0.48 bar) over seven springs |
| Application | Tank and vessel blanketing on large storage tanks with very low blanket pressure |
| Material of construction | Type EGR main valve with Type 1098 actuator; Type T205P pilot; Type MR95H supply regulator |