Fisher 1805 Series Relief Valves
Purchase options
Request a quote
- Availability
- Call for availability Originalx
Independent supplier
Sproh is an independent supplier and is not an authorized distributor or official representative of Fisher or Emerson.
Overview
Spring-loaded relief valves in a globe body with an O-ring seat, sizes 3/4 to 2 NPT. Set pressures from 5 to 125 psig, 150 psig maximum inlet including build-up, for low-pressure gas and liquid systems.
Key specifications
- Line size range
- 3/4, 1, 1-1/2 and 2 NPT globe body
- Process temperature
- -29 to 66 C (-20 to 150 F)
- Pressure rating
- 150 psig / 10.3 bar maximum inlet pressure including build-up
- Variants
- Types 1805-2, -3, -4, -5 and -7; NACE option on 3/4 and 1 NPT
- Application
- Low-pressure gas and liquid systems: small regulators, meters, pilot supplies, blanketing headers
- Material of construction
- Cast iron body; nitrile diaphragm and O-rings; aluminium guide; brass diaphragm plate; stainless washer and vent screen
What the 1805 is
A spring-loaded relief valve in a globe body with sizes from 3/4 to 2 NPT. It protects low-pressure gas or liquid systems by opening at a set pressure and reseating when pressure falls — the everyday duty on small regulators, meters, pilot supplies and blanketing headers.
Set ranges by size
The small bodies (3/4 and 1 NPT) come in 5-35, 10-60 and 20-125 psig spring ranges; the larger 1-1/2 and 2 NPT bodies in 5-20, 10-50 and 35-125 psig ranges. Maximum inlet pressure is 150 psig including build-up, and temperature limits are -29 to 66 °C.
Construction
Cast iron body, nitrile diaphragm and O-rings, aluminium valve guide and O-ring holder, brass diaphragm plate, stainless O-ring washer and vent screen. A ductile iron NACE option exists on the 3/4 and 1 NPT sizes. Flow coefficient C1 is 35 on the smaller bodies (Xt 0.73, FD 0.39) and Xt 0.94 on the larger ones.
Sizing and installation
Size the orifice on the relieving flow the system can generate, not on the normal flow. The vent must be piped or protected against rain, ice and insects, and where the relieved gas is flammable or toxic it must be taken to a safe location. Weight is about 2 kg for the small sizes and 6 kg for the 1-1/2 and 2 NPT bodies.
Specifications
| Attribute | Value |
|---|---|
| Line size range | 3/4, 1, 1-1/2 and 2 NPT globe body |
| Process temperature | -29 to 66 C (-20 to 150 F) |
| Pressure rating | 150 psig / 10.3 bar maximum inlet pressure including build-up |
| Variants | Types 1805-2, -3, -4, -5 and -7; NACE option on 3/4 and 1 NPT |
| Application | Low-pressure gas and liquid systems: small regulators, meters, pilot supplies, blanketing headers |
| Material of construction | Cast iron body; nitrile diaphragm and O-rings; aluminium guide; brass diaphragm plate; stainless washer and vent screen |
Documents
Accessories and related items
Accessories and related items for this product are not available to order on Sproh yet. If the manufacturer lists them, an engineer can source them for you.
Ask an engineer