Fisher 2500 Pneumatic Level Controller
Purchase options
Request a quote
- Availability
- Call for availability Originalx
Independent supplier
Sproh is an independent supplier and is not an authorized distributor or official representative of Fisher or Emerson.
Overview
Pneumatic level controller and transmitter series used with Fisher 249 displacer sensors. Handles liquid level, interface level and density, with proportional, on-off and transmitter outputs over 0.2 to 1.0 bar.
Key specifications
- Measurement principle
- Pneumatic displacer torque-tube measurement with Fisher 249 sensor; level, interface level and density
- Output signal
- Proportional and transmitter: 0.2 to 1.0 bar (3-15 psig) or 0.4 to 2.0 bar (6-30 psig); on-off: 0 or 1.4 bar / full supply
- Power supply
- 1.4 bar (20 psig) or 2.4 bar (35 psig) normal supply; 3 bar (45 psig) maximum
- Variants
- 2500, 2500R, 2500S, 2500T, 2502, 2502F and 2503 with 249 displacer sensors
- Application
- Level control and transmission on tanks and vessels, including interface and density service
- Operating temperature (°C)
- Ambient -40 to 71 C standard; -18 to 104 C high temperature
What it does
The 2500 turns the small rotation of a 249 displacer sensor's torque tube into a pneumatic signal. That signal either drives a control valve directly (proportional controllers), switches at a level (on-off versions), or is transmitted to a control room (transmitter versions). Level, liquid-to-liquid interface and density are all read the same way — the difference is the displacer and the calibration.
Versions
The series covers 2500 proportional controllers, 2500R and 2500S on-off types, 2500T transmitters, 2502 and 2502F proportional controllers with reset, and 2503 for density service. Output is 0.2 to 1.0 bar (3-15 psig) or 0.4 to 2.0 bar (6-30 psig) on proportional and transmitter units; on-off types switch between 0 and 1.4 bar or full supply.
Performance that matters on a level loop
Hysteresis is 0.6 percent of output change and repeatability 0.2 percent of displacer length — figures that decide whether a level loop can hold a tight band without cycling. Transmitter linearity is 1 percent of output change. The 2502's reset is adjustable from 0.005 to over 0.9 minutes per repeat, which is what keeps a slow vessel from hunting.
Air and environment
Normal supply is 1.4 or 2.4 bar (20 or 35 psig), maximum 3 bar (45 psig). Standard ambient range is -40 to 71 °C, with a high-temperature version to 104 °C. Specific gravity range is 0.20 to 1.10 on the 2500 and 0.25 to 1.10 on the 2503 — outside that, the displacer and torque tube have to be resized.
Specifications
| Attribute | Value |
|---|---|
| Measurement principle | Pneumatic displacer torque-tube measurement with Fisher 249 sensor; level, interface level and density |
| Output signal | Proportional and transmitter: 0.2 to 1.0 bar (3-15 psig) or 0.4 to 2.0 bar (6-30 psig); on-off: 0 or 1.4 bar / full supply |
| Power supply | 1.4 bar (20 psig) or 2.4 bar (35 psig) normal supply; 3 bar (45 psig) maximum |
| Variants | 2500, 2500R, 2500S, 2500T, 2502, 2502F and 2503 with 249 displacer sensors |
| Application | Level control and transmission on tanks and vessels, including interface and density service |
| Operating temperature (°C) | Ambient -40 to 71 C standard; -18 to 104 C high temperature |