Overview
Pneumatic and electro-pneumatic positioner for diaphragm-actuated sliding-stem valves. The 3582 takes a 0.2-1.0 bar air signal; the 3582i adds a 582i converter for 4-20 mA input, with 1 percent linearity and 0.5 percent hysteresis.
Key specifications
- Accuracy
- Independent linearity 1 percent (3582) or 2 percent (3582i); hysteresis 0.5 / 0.6 percent of span
- Output signal
- 3582: 0.2-1.0 bar (3-15 psig), 0.4-2.0 bar (6-30 psig) or split range; 3582i: 4-20 mA DC
- Power supply
- Supply 0.3 bar above actuator requirement; maximum 3.4 bar (50 psig) or actuator rating
- Transmitter compatibility
- Diaphragm-actuated sliding-stem control valves
- Material of construction
- Pneumatic positioner with 582i converter on the 3582i; field-reversible direct or reverse action
What a positioner adds
A diaphragm actuator on its own moves to whatever pressure the controller happens to supply; friction in the packing and unbalance in the plug decide where it actually settles. The 3582 closes that loop: it compares the valve stem position with the input signal and adjusts the air to the actuator until the two agree, which removes most of the friction and unbalance error.
Pneumatic and electro-pneumatic
The 3582 takes a standard pneumatic signal — 0.2 to 1.0 bar (3-15 psig), 0.4 to 2.0 bar (6-30 psig) or a split range. The 3582i adds the 582i converter so the same instrument accepts 4-20 mA DC directly from a control system, without a separate I/P in the loop. Both are field-reversible between direct and reverse action.
Accuracy figures
Independent linearity is 1 percent of output span on the 3582 and 2 percent on the 3582i; hysteresis is 0.5 and 0.6 percent respectively. Open loop gain is 100 for the 3-15 psig range and 55 for 6-30 psig. Steady-state air consumption at 2.0 bar is 0.48 normal m3/h (0.57 for the 3582i), with a maximum supply demand of 6.7 normal m3/h — the figure that decides whether the instrument air compressor can carry a large valve population.
Supply and medium
Supply should sit about 0.3 bar above what the actuator needs, with a maximum of 3.4 bar or the actuator rating, whichever is lower. The 3582 can run on air or natural gas; the 3582i is not approved for natural gas because of its electrical section.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | Independent linearity 1 percent (3582) or 2 percent (3582i); hysteresis 0.5 / 0.6 percent of span |
| Output signal | 3582: 0.2-1.0 bar (3-15 psig), 0.4-2.0 bar (6-30 psig) or split range; 3582i: 4-20 mA DC |
| Power supply | Supply 0.3 bar above actuator requirement; maximum 3.4 bar (50 psig) or actuator rating |
| Transmitter compatibility | Diaphragm-actuated sliding-stem control valves |
| Material of construction | Pneumatic positioner with 582i converter on the 3582i; field-reversible direct or reverse action |
Documents
Accessories and related items
Accessories and related items for this product are not available to order on Sproh yet. If the manufacturer lists them, an engineer can source them for you.