Fisher Type 63EG Relief Valve and Backpressure Regulator
Purchase options
Request a quote
- Availability
- Call for availability Originalx
Independent supplier
Sproh is an independent supplier and is not an authorized distributor or official representative of Fisher or Emerson.
Overview
Pilot-operated relief valve and backpressure regulator for gas, liquid and steam lines: NPS 1 to 12 x 6 bodies, 6358 series pilots, up to 400 psig inlet, top-entry trim access and an optional Whisper Trim III cage for high-noise relief.
Key specifications
- Line size range
- NPS 1, 2, 3, 4, 6, 8 x 6 and 12 x 6 (DN 25 to DN 300 x 150)
- Process temperature
- NBR -29 to 82 C; FKM 0 to 149 C; EPR -29 to 135 C; FFKM -18 to 218 C
- Pressure rating
- 400 psig / 27.6 bar maximum relief (inlet) pressure, or body rating if lower
- Process connection
- NPT, BWE, SWE, CL150 RF, CL300 RF, CL600 RF, PN 16/25/40
- Certifications
- NACE MR0175 / ISO 15156 and oxygen-service material options available
- Variants
- Types 63EG and 1098-63EGR; 6358, 6358B, 6358EB and 6358EBH pilots
The Fisher Type 63EG is a pilot-operated relief valve and backpressure regulator for gas, liquid and steam service. A 6358 series pilot senses upstream pressure and loads or vents a large top-entry main valve, so a small sensing element controls a wide range of flows without exposing the diaphragm to the full line size.
How the pilot and main valve work together
Below set pressure the pilot spring keeps the pilot plug shut and inlet pressure builds on top of the main plug, holding it closed against the main spring. When upstream pressure crosses the set point the pilot diaphragm lifts, exhausts the loading pressure above the main plug, and the pressure unbalance opens the valve. A hollow pilot stem registers pressure quickly at start-up, which stops the main valve from lifting before the pilot has taken control, and a fixed restriction in the relief pilots lets the plug reseat quickly once pressure falls. The pilot only bleeds while it repositions the valve, which matters where venting has to stay minimal or be piped away.
Body sizes and capacities
Seven body sizes cover small separator duty up to large transmission lines. Port diameters and weights below are the manufacturer's published values with the pilot included.
| Body size | Port diameter | Travel | Weight with pilot |
|---|---|---|---|
| NPS 1 / DN 25 | 33 mm (1.31 in) | 19 mm | 16 kg |
| NPS 2 / DN 50 | 60 mm (2.38 in) | 29 mm | 25 kg |
| NPS 3 / DN 80 | 86 mm (3.38 in) | 38 mm | 43 kg |
| NPS 4 / DN 100 | 111 mm (4.38 in) | 51 mm | 66 kg |
| NPS 6 / DN 150 | 183 mm (7.19 in) | 51 mm | 150 kg |
| NPS 8 x 6 / DN 200 x 150 | 183 mm (7.19 in) | 51 mm | 304 kg |
| NPS 12 x 6 / DN 300 x 150 | 183 mm (7.19 in) | 51 mm | 521 kg |
Trim, noise and materials
Linear trim is the standard characteristic; quick-opening trim is available where fast capacity rise is wanted. For relief points close to sonic velocity the Whisper Trim III cage cuts gas noise by up to 10 dB without changing the body. Bodies come in WCC steel, cast iron or CF8M stainless steel, and the pilots are CF8M stainless or aluminium. Elastomer choice sets the temperature window: nitrile to 82 °C, FKM to 149 °C, EPR to 135 °C and perfluoroelastomer to 218 °C, with water service limited to 82 °C across all of them.
Maintenance in service
The main valve is top-entry: the cage, plug and seat ring come out from above without breaking the pipeline, and if an actuator is fitted its stem stays connected. A travel indicator on the main valve shows plug position while the valve is in service, and the pilot can be cleaned or re-set without removing the body. Pilot supply filters are worth fitting where pipeline debris is likely, because a blocked pilot restriction is the most common cause of slow reseating.
Where the 63EG is specified
- Gas transmission and distribution stations needing upstream pressure hold or relief.
- Oilfield separators and scrubbers, including throttling backpressure duty.
- Pump recirculation and discharge protection on liquid lines.
- Fuel gas and utility headers where venting must be piped to a safe location.
Note that the 63EG is a pressure control device, not an ASME-certified safety relief valve; where code requires a certified safety valve, the 63EG works alongside it rather than replacing it.
Ordering information to send with an enquiry
State the fluid, set pressure, relieving or throttling flow, maximum inlet pressure including build-up, body size and end connection, body material, trim type, pilot type and elastomer, and whether NACE or oxygen-service materials are required.
Specifications
| Attribute | Value |
|---|---|
| Line size range | NPS 1, 2, 3, 4, 6, 8 x 6 and 12 x 6 (DN 25 to DN 300 x 150) |
| Process temperature | NBR -29 to 82 C; FKM 0 to 149 C; EPR -29 to 135 C; FFKM -18 to 218 C |
| Pressure rating | 400 psig / 27.6 bar maximum relief (inlet) pressure, or body rating if lower |
| Process connection | NPT, BWE, SWE, CL150 RF, CL300 RF, CL600 RF, PN 16/25/40 |
| Certifications | NACE MR0175 / ISO 15156 and oxygen-service material options available |
| Variants | Types 63EG and 1098-63EGR; 6358, 6358B, 6358EB and 6358EBH pilots |
| Application | Natural gas transmission and distribution, oilfield separators, pump recirculation, fuel gas supply |
| Valve configuration | Pilot-operated relief valve and backpressure regulator; linear, quick-open or Whisper Trim III cage |
| Material of construction | Body: WCC steel, cast iron or CF8M stainless steel. Pilot: CF8M stainless steel or aluminium |
Documents
Accessories and related items
Accessories and related items for this product are not available to order on Sproh yet. If the manufacturer lists them, an engineer can source them for you.
Ask an engineer