Overview
Reverse-acting spring-opposed diaphragm actuator for angle and globe valves. Integral mounting pad for FIELDVUE or bracket-mounted positioners, multiple spring rates, travel stops and manual operators.
Key specifications
- Variants
- Reverse-acting, spring-opposed diaphragm actuator with linear travel; multiple spring rates and travel stops
- Mounting
- Integral mounting pad with integral air passage; externally tubed option available; manual operator option
- Transmitter compatibility
- Angle and globe valves, with FIELDVUE controllers or bracket-mounted positioners
- Operating temperature (°C)
- Cryogenic, low temperature, standard and high temperature constructions
Reverse acting, and why that matters
On a reverse-acting actuator, increasing air pressure retracts the stem and the spring drives it out. That is the opposite of the 657, and it decides the valve's failure position: with the spring pushing the plug onto the seat, loss of air closes a globe valve. Choosing between direct and reverse acting is therefore a process safety decision, not a mounting preference.
Where it is used
On angle and globe valves, for on/off and throttling duty. The 667 shares the 657's yoke design, so the same integral mounting pad with the integral air passage takes a FIELDVUE digital valve controller directly, and bracket-mounted positioners remain an option.
Sizing options
Multiple spring rates let one actuator frame cover a range of bench-set and thrust requirements; travel stops set the mechanical stroke limits, and manual operators allow the valve to be stroked with no air available. Temperature constructions run from cryogenic through low, standard and high temperature, with the diaphragm and O-ring materials matched to each.
Applying it
Confirm the required failure action first, then the thrust at the available supply pressure, then the spring rate that gives the bench set. The actuator is only as good as that sequence — a correctly sized actuator with the wrong spring rate will still be unstable in throttling service.
Specifications
| Attribute | Value |
|---|---|
| Variants | Reverse-acting, spring-opposed diaphragm actuator with linear travel; multiple spring rates and travel stops |
| Mounting | Integral mounting pad with integral air passage; externally tubed option available; manual operator option |
| Transmitter compatibility | Angle and globe valves, with FIELDVUE controllers or bracket-mounted positioners |
| Operating temperature (°C) | Cryogenic, low temperature, standard and high temperature constructions |