Overview
Low-consumption pneumatic controller and transmitter for gauge, vacuum, compound or differential pressure. P, P+I and differential-gap versions, field-reversible action without extra parts, 0.08 normal m3/h steady-state air use.
Key specifications
- Measurement principle
- Gauge, vacuum, compound or differential pressure of a liquid or gas
- Accuracy
- Proportional band 2-100 percent of sensing range (3-15 psig) or 4-100 percent (6-30 psig)
- Output signal
- 0.2-1.0 bar (3-15 psig) or 0.4-2.0 bar (6-30 psig) for P and P+I; differential gap 0-1.4 or 0-2.4 bar
- Power supply
- Clean, dry, non-corrosive air or natural gas to ISA 7.0.01 / ISO 8573-1; 0.08-0.12 normal m3/h steady-state consumption
- Variants
- Proportional only, proportional plus reset, or differential gap versions; field-reversible direct or reverse action
The low-consumption point
Most pneumatic controllers bleed air continuously to maintain their nozzle pressure. The C1's steady-state consumption is 0.08 normal m3/h on the 3-15 psig range and 0.12 on 6-30 psig — roughly a tenth of a conventional controller. On a plant with dozens of pneumatic loops and a finite instrument air capacity, that difference is what decides whether the compressor has to run.
What it measures
Gauge, vacuum, compound or differential pressure of a liquid or gas, depending on the element ordered. Output is 0.2 to 1.0 bar or 0.4 to 2.0 bar on proportional and proportional-plus-reset versions; differential-gap versions switch 0 to 1.4 bar or 0 to 2.4 bar for on-off control without a positioner.
Adjustment and action
Proportional band is adjustable from 2 to 100 percent of the sensing range on the 3-15 psig output, or 4 to 100 percent on 6-30 psig. Action is field reversible between direct and reverse without additional parts, so one spare covers both duties.
Supply
Clean, dry, non-corrosive air or natural gas to ISA 7.0.01 or ISO 8573-1 — the specification matters here, because a low-consumption nozzle is also a small orifice that contamination will block. Filtering the supply is not optional on this instrument.
Specifications
| Attribute | Value |
|---|---|
| Measurement principle | Gauge, vacuum, compound or differential pressure of a liquid or gas |
| Accuracy | Proportional band 2-100 percent of sensing range (3-15 psig) or 4-100 percent (6-30 psig) |
| Output signal | 0.2-1.0 bar (3-15 psig) or 0.4-2.0 bar (6-30 psig) for P and P+I; differential gap 0-1.4 or 0-2.4 bar |
| Power supply | Clean, dry, non-corrosive air or natural gas to ISA 7.0.01 / ISO 8573-1; 0.08-0.12 normal m3/h steady-state consumption |