Fisher FIELDVUE DLC3100 Digital Level Controller
Purchase options
Request a quote
- Availability
- Call for availability Originalx
Independent supplier
Sproh is an independent supplier and is not an authorized distributor or official representative of Fisher or Emerson.
Overview
Digital level transmitter for liquid level, interface and density using Fisher 249 and equivalent displacer sensors. 4-20 mA with HART, NAMUR NE43 alarms, RTD temperature compensation and 0.25 percent linearity.
Key specifications
- Measurement principle
- Liquid level, interface level or density (density not available on the SIS version)
- Accuracy
- Independent linearity ±0.25 percent of output span (controller), ±0.5 percent with most 249 sensors; repeatability ±0.1 percent
- Output signal
- 4-20 mA DC with HART 1200 baud FSK, direct or reverse action
- Power supply
- 12 to 30 V DC, 25 mA, reverse polarity protected
- Transmitter compatibility
- Fisher 249 caged and cageless displacer sensors; Masoneilan, Foxboro-Eckardt and Yamatake with adaptors
- Response time
- Saturation 3.8 / 20.5 mA; high alarm above 21.0 mA or low alarm below 3.6 mA per NAMUR NE43
Replacing the pneumatic controller
The 249 displacer sensor and the 2500 pneumatic controller have been a pair for decades. The DLC3100 keeps the sensor and replaces the pneumatic half with a digital transmitter: the torque tube rotation is measured electronically and converted to 4-20 mA with HART, which is what lets a legacy displacer installation report to a DCS without changing the vessel connection.
What it measures
Liquid level, interface level or density. Density is the interesting one: it needs the displacer's buoyancy change to be interpreted against temperature, so the DLC3100 accepts a 2- or 3-wire 100 ohm platinum RTD input — or a user-entered target temperature — and compensates. The SIS version does not offer density.
Accuracy
Independent linearity is ±0.25 percent of output span for the controller and ±0.5 percent with most 249 sensors, with repeatability of ±0.1 percent of full scale. The distinction matters: the electronics are better than the mechanical sensor, so the sensor is what sets the installed accuracy.
Signals and safety
4-20 mA DC, direct or reverse action, HART 1200 baud FSK superimposed. Saturation is 3.8 / 20.5 mA with high alarm above 21.0 mA or low alarm below 3.6 mA per NAMUR NE43 — the convention a DCS needs to distinguish a real measurement from a failed transmitter. Supply is 12 to 30 V DC at 25 mA, reverse polarity protected.
Specifications
| Attribute | Value |
|---|---|
| Measurement principle | Liquid level, interface level or density (density not available on the SIS version) |
| Accuracy | Independent linearity ±0.25 percent of output span (controller), ±0.5 percent with most 249 sensors; repeatability ±0.1 percent |
| Output signal | 4-20 mA DC with HART 1200 baud FSK, direct or reverse action |
| Power supply | 12 to 30 V DC, 25 mA, reverse polarity protected |
| Transmitter compatibility | Fisher 249 caged and cageless displacer sensors; Masoneilan, Foxboro-Eckardt and Yamatake with adaptors |
| Response time | Saturation 3.8 / 20.5 mA; high alarm above 21.0 mA or low alarm below 3.6 mA per NAMUR NE43 |