Fisher FIELDVUE DVC6200 SIS Digital Valve Controller
Purchase options
Request a quote
- Availability
- Call for availability Originalx
Independent supplier
Sproh is an independent supplier and is not an authorized distributor or official representative of Fisher or Emerson.
Overview
Digital valve controller for safety instrumented systems, SIL 3 per IEC 61508 edition 2 with DETT or ETT proof testing. HART 5/7, partial and full stroke testing, low-bleed or high-Cv relay options.
Key specifications
- Output signal
- 4-20 mA DC point-to-point with HART 5 or HART 7; 9.5 V DC minimum for analog, 10 V DC for HART; multi-drop 11-30 V DC at 10 mA
- Power supply
- Pneumatic output to full supply pressure, maximum span 9.5 bar (140 psig); low bleed relay needs 0.3 bar above actuator requirement
- Certifications
- IEC 61508 edition 2, SIL 3 for DETT or ETT configurations; position monitor SIL 2
- Pressure range
- Low bleed relay 29.5 normal m3/h at 5.5 bar; High Cv relays HCv1 1.2, HCv2 3.2, HCv3 6.2 Cv
- Variants
- Double acting, single direct or single reverse configurations; partial stroke and full stroke testing
- Transmitter compatibility
- Safety instrumented system shutdown and emergency isolation valves
Why a shutdown valve needs its own instrument
A safety valve spends its life sitting still. Its dangerous failure mode is that it will not move when demanded — a stuck stem, a dry actuator, a plugged relay. The DVC6200 SIS exists to make that failure visible before the demand: it performs partial stroke testing on a live valve and full stroke testing on demand, and it is certified to SIL 3 for the function.
Certification, stated precisely
IEC 61508 edition 2, SIL 3 for DETT (Decommissioning End-to-End Test) or ETT (End-to-End Test) configurations. The position monitor function alone is SIL 2. That distinction matters in a safety requirement specification: the SIL applies to a defined configuration, not to the box in general.
Electrical
4-20 mA DC point-to-point with HART 5 or HART 7. Minimum terminal voltage is 9.5 V DC for analog control and 10 V DC for HART; multi-drop runs at 11 to 30 V DC at 10 mA. These are the numbers that decide whether a marginal loop power budget can carry the instrument.
Pneumatics
Output up to full supply pressure, maximum span 9.5 bar (140 psig), in double-acting, single direct and single reverse configurations. Two relay families: a low-bleed relay needing only 0.3 bar above the actuator requirement and delivering 29.5 normal m3/h at 5.5 bar supply — the choice for a plant that cannot afford continuous air loss — or High Cv relays (HCv1 1.2, HCv2 3.2, HCv3 6.2 Cv) for large actuators that need volume more than they need economy.
Specifications
| Attribute | Value |
|---|---|
| Output signal | 4-20 mA DC point-to-point with HART 5 or HART 7; 9.5 V DC minimum for analog, 10 V DC for HART; multi-drop 11-30 V DC at 10 mA |
| Power supply | Pneumatic output to full supply pressure, maximum span 9.5 bar (140 psig); low bleed relay needs 0.3 bar above actuator requirement |
| Certifications | IEC 61508 edition 2, SIL 3 for DETT or ETT configurations; position monitor SIL 2 |
| Pressure range | Low bleed relay 29.5 normal m3/h at 5.5 bar; High Cv relays HCv1 1.2, HCv2 3.2, HCv3 6.2 Cv |
| Variants | Double acting, single direct or single reverse configurations; partial stroke and full stroke testing |
| Transmitter compatibility | Safety instrumented system shutdown and emergency isolation valves |