Fisher FIELDVUE L2t Electronic Liquid Level Controller
Purchase options
Request a quote
- Availability
- Call for availability Originalx
Independent supplier
Sproh is an independent supplier and is not an authorized distributor or official representative of Fisher or Emerson.
Overview
Displacer level controller with 4-20 mA and HART 7 output, two isolated solid-state limit switches and a 102 to 305 mm span. Measures level or interface down to specific gravity 0.4.
Key specifications
- Measurement principle
- Liquid level or liquid-to-liquid interface by displacer
- Output signal
- 4-20 mA DC with HART 7; two isolated solid-state limit switches
- Power supply
- 24 to 30 V DC at 25 mA recommended; reverse polarity protected; 17.75 V DC minimum compliance for HART
- Pressure range
- Level span minimum 102 mm (4 in.), maximum 305 mm (12 in.) with standard displacer; minimum specific gravity 0.4
- Transmitter compatibility
- Fisher 249 displacer sensor family
- Response time
- Saturation 20.5 / 3.8 mA; alarms above 21.0 mA or below 3.6 mA per NAMUR NE43
What it is
A displacer level controller with an electronic output instead of a pneumatic one: the torque tube rotation is measured and converted to 4-20 mA with HART 7, and the same instrument carries two isolated solid-state limit switches for alarms or interlocks. It keeps the displacer sensor a plant already has — the 249 family — and replaces the pneumatic transmission behind it.
Span and density
Level span is 102 mm (4 in.) minimum and 305 mm (12 in.) maximum with the standard displacer, and the minimum specific gravity is 0.4. That SG figure is the one that decides feasibility: a light hydrocarbon interface at 0.45 SG needs a bigger displacer and a different torque tube, and a controller specified without checking it will read noise.
Signals
4-20 mA DC with HART 7. Saturation is 20.5 mA high and 3.8 mA low, with alarms above 21.0 mA or below 3.6 mA per NAMUR NE43 — the convention that lets a DCS tell a real over-range from a failed transmitter. Power is 24 to 30 V DC at 25 mA recommended, reverse polarity protected, with 17.75 V DC minimum compliance for HART communication.
Why electronic
A pneumatic level controller has to be read at the vessel and has no diagnostics. The L2t reports the level to the control system and the two limit switches can drive an interlock directly, which is what turns a legacy displacer installation into something a modern safety or control system can use without replacing the process connection.
Specifications
| Attribute | Value |
|---|---|
| Measurement principle | Liquid level or liquid-to-liquid interface by displacer |
| Output signal | 4-20 mA DC with HART 7; two isolated solid-state limit switches |
| Power supply | 24 to 30 V DC at 25 mA recommended; reverse polarity protected; 17.75 V DC minimum compliance for HART |
| Pressure range | Level span minimum 102 mm (4 in.), maximum 305 mm (12 in.) with standard displacer; minimum specific gravity 0.4 |
| Transmitter compatibility | Fisher 249 displacer sensor family |
| Response time | Saturation 20.5 / 3.8 mA; alarms above 21.0 mA or below 3.6 mA per NAMUR NE43 |