Fisher i2P-100 Electro-Pneumatic Transducer
Purchase options
Request a quote
- Availability
- Call for availability Originalx
Independent supplier
Sproh is an independent supplier and is not an authorized distributor or official representative of Fisher or Emerson.
Overview
Compact 4-20 mA to pneumatic transducer with a piezo-actuator and a booster relay. Split ranges, 0.2-1.0 or 0.4-2.0 bar output, 1 percent reference accuracy and 8.04 m3/h output capacity.
Key specifications
- Accuracy
- Reference accuracy ±1.0 percent of full scale output span, hysteresis, linearity and deadband combined
- Output signal
- Input 4-20 mA DC standard; 4-12 mA or 12-20 mA split range
- Power supply
- Supply recommended 0.3 bar above upper output limit; maximum 3.4 bar (50 psig); air or non-corrosive natural gas
- Pressure range
- Output 0.2-1.0 bar (3-15 psig), 0.4-2.0 bar (6-30 psig) or 0.14-2.3 bar (2-33 psig)
- Material of construction
- Piezo-electric actuator with booster relay; no moving armature
- Response time
- Maximum output capacity 8.04 m3/h (300 scfh) at 1.4 bar supply
Piezo actuator instead of a torque motor
Most I/P transducers use a torque motor: a coil, an armature and a flapper that can be knocked out of alignment by vibration. The i2P-100 uses a piezo-electric actuator, which has no moving armature — so there is nothing to wear, nothing to re-zero after a vibration event, and no air bleed at steady state in the way a nozzle-flapper needs.
Signals
Input 4-20 mA DC standard, with 4-12 mA and 12-20 mA split ranges for two valves on one loop. Output 0.2 to 1.0 bar (3-15 psig), 0.4 to 2.0 bar (6-30 psig) or 0.14 to 2.3 bar (2-33 psig) depending on the model. Reference accuracy is ±1.0 percent of full scale output span with hysteresis, linearity and deadband combined — one number rather than three, which is the honest way to state it.
Air and capacity
Maximum output capacity is 8.04 m3/h (300 scfh) at 1.4 bar supply, enough to drive a small actuator or a positioner directly. Supply should be 0.3 bar above the upper output limit, maximum 3.4 bar, and the medium can be air or non-corrosive natural gas — which matters on a gas-powered instrument loop with no instrument air.
Mounting
Compact enough to mount on a yoke or in a panel, and available with hazardous-area approvals (the IECEx supplement is in the documents). On a retrofit it usually replaces a torque-motor transducer in the same footprint.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | Reference accuracy ±1.0 percent of full scale output span, hysteresis, linearity and deadband combined |
| Output signal | Input 4-20 mA DC standard; 4-12 mA or 12-20 mA split range |
| Power supply | Supply recommended 0.3 bar above upper output limit; maximum 3.4 bar (50 psig); air or non-corrosive natural gas |
| Pressure range | Output 0.2-1.0 bar (3-15 psig), 0.4-2.0 bar (6-30 psig) or 0.14-2.3 bar (2-33 psig) |
| Material of construction | Piezo-electric actuator with booster relay; no moving armature |
| Response time | Maximum output capacity 8.04 m3/h (300 scfh) at 1.4 bar supply |
Documents
Accessories and related items
Accessories and related items for this product are not available to order on Sproh yet. If the manufacturer lists them, an engineer can source them for you.
Ask an engineer