Endress+Hauser Indumax CLS54 Analog Conductivity Sensor
Purchase options
From$755.69
- Availability
- Call for availability Originalx
Configurable — choose options to build the exact part number.
Independent supplier
Sproh is an independent supplier and is not an authorized distributor or official representative of Endress+Hauser.
Overview
The INDUMAX CLS54 is an analytical sensor: it converts a chemical property of the process — pH, ORP, conductivity, oxygen, chlorine or turbidity — into a signal the transmitter can read.
Key specifications
- Measurement principle
- Measuring principle: Inductive
- Process temperature
- Process temperature: -20 to 135°C (-4 to 275°F) at 3.5bar/50psi absolute
- Process connection
- Process connection(s): Dairy pipe, aseptic fitting, ISO2852 Clamp, SMS 2in, Varivent N DN 40-125, Neumo Biocontrol D50
- Measurement range
- Measurement range: 100 µS/cm - 2000 mS/cm Cell constant k: 6,3 1/cm
- Response time
- Temperature response time: T90 Material(s): In contact with medium: Virgin PEEK
- Sensor
- Temperature sensor: Pt1000 (class A)
The wetted element ages
The measuring element is in contact with the process and is the part that ages: a glass membrane for pH, a toroidal coil for conductivity, a luminescent cap for oxygen. That is why the maintenance interval is set by the sensor rather than by the transmitter.
Memosens calibration
Memosens connectors carry the calibration in the sensor head, so a sensor can be calibrated in the workshop and swapped in the field without a wet calibration at the installation point.
Installation decides
The installation decision is usually about keeping the sensor wet, clean and at a representative temperature — a retractable fitting or a flow assembly does more for the measurement than any transmitter setting.
Specifications
| Attribute | Value |
|---|---|
| Measurement principle | Measuring principle: Inductive |
| Process temperature | Process temperature: -20 to 135°C (-4 to 275°F) at 3.5bar/50psi absolute |
| Process connection | Process connection(s): Dairy pipe, aseptic fitting, ISO2852 Clamp, SMS 2in, Varivent N DN 40-125, Neumo Biocontrol D50 |
| Measurement range | Measurement range: 100 µS/cm - 2000 mS/cm Cell constant k: 6,3 1/cm |
| Response time | Temperature response time: T90 Material(s): In contact with medium: Virgin PEEK |
| Sensor | Temperature sensor: Pt1000 (class A) |
Documents
Accessories and related items
Accessories and related items for this product are not available to order on Sproh yet. If the manufacturer lists them, an engineer can source them for you.
Ask an engineer