Overview
Welded protection tubes, threaded or flanged, with hydrostatic and dye penetrant test options and material traceability.
Key features
- Protection tubes made from metal tubing sealed with a welded end cap at the tip, where the process seal is the flange or a machined threaded fitting welded along the tube
- The pressure boundary is therefore made of welds, which is why an external hydrostatic pressure test (Q5) and a dye penetrant test (Q73) are offered as evidence rather than as extras
- Typical uniform stem profile: simpler and more robust than a tapered well, with a thicker tip and therefore a slower response
- Three lengths decide whether it works: immersion length against the wall, extension length against insulation and vibration, and the sensor length measured from the sensor tip to the bottom of the DIN plate
- Ordering options assemble the sensor to the specific protection tube or transmitter, which takes the length match away from the site
- Material certification (Q8) for traceability on a wetted part whose failure mode is corrosion from the inside
Key specifications
- Accuracy
- No measurement of its own, but the tube inserts a layer of metal between process and sensor: wall thickness, material, immersion depth and sensor fit all set the response lag. The uniform stem profile is thicker at the tip than a tapered well, so response is slower
- Output signal
- Not applicable - a mechanical protection tube with no electrical function
- Diagnostics
- The failure modes of a protection tube are dimensional or metallurgical, not electrical: an immersion length too short reads the wall, a sensor shorter than the tube floats off the tip and lags, and a weld defect admits process into the sensor head
- Pressure range
- Set by the flange or the machined threaded fitting welded along the tube. An external hydrostatic pressure test (Q5) is available to prove the assembly holds pressure before installation
- Variants
- Threaded and flanged versions with a uniform stem profile and a welded end cap. Options Q5 external hydrostatic pressure test, Q73 dye penetrant test and Q8 material certification, plus assembly of the sensor to a specific transmitter or protection tube
- Application
- Temperature measurement where the sensor must be protected and replaceable without breaking into the process: pipe and vessel installations across the pressure and temperature range the flange or thread allows, threaded or flanged
A pressure boundary that costs you response time
The Rosemount 114P is a protection tube: metal tubing sealed with a welded end cap at the tip, where the process seal is made by a flange or a machined threaded fitting welded along the tube. Typically the tubes have a uniform stem profile. Options include an external hydrostatic pressure test (Q5), a dye penetrant test (Q73) and material certification (Q8) for traceability.
Read the first sentence carefully, because it is the whole engineering problem of a protection tube. The tube has to hold the process inside a pipe while a sensor sits inside the tube measuring something that is not in the pipe. Everything the tube does well for the plant, it does at the expense of the measurement.
The weld is the seal, and the weld is what gets tested
A protection tube is not a pocket that happens to be closed. The end cap is welded, and the fitting that carries the thread or the flange is welded along the tube — which means the pressure boundary consists of welds, and welds are the part of a fabricated component that can be wrong without looking wrong.
That is why the two test options exist. A hydrostatic pressure test proves the assembly holds pressure before it is installed, and a dye penetrant test finds surface-breaking defects in the welds that a pressure test might pass and corrosion might later open. On a high-pressure or hazardous service, neither is a luxury: they are the evidence that the boundary is a boundary, and they cost a fraction of what a leak into a sensor head costs.
The material certificate is the same argument for the metal itself. On a wetted part whose failure mode is corrosion from the inside, knowing which heat of steel went into the tube is the difference between investigating a failure and guessing at one.
Heat has to cross the wall, so the wall is the lag
The tube protects the sensor from pressure, flow, abrasion and corrosion, and in doing so it inserts a layer of metal between the process and the element. Everything that makes the tube strong makes the measurement slower: wall thickness, material, immersion depth and the fit between sensor and tube.
A uniform stem profile — the standard form here — is a straight tube rather than a tapered well. It is simpler to manufacture and to certify, and it is mechanically robust; the trade is a tip that is thicker than a tapered well's, so the response is slower. On a control loop that matters, on a slow thermal process it does not.
Three lengths, and only one of them is on the drawing
The datasheet gives the measurement instruction that prevents most of the mistakes, and it is worth following literally: measure the sensor length from the tip of the sensor to the bottom of the DIN plate, and use that length (X) to specify the sensor insertion length.
| Dimension | What goes wrong if it is wrong |
|---|---|
| U — immersion length | Too short and the tip sits in the nozzle or against the wall, measuring the pipe rather than the fluid |
| N — extension length | Too short and the connection head sits against hot insulation; too long and the assembly is a lever in vibration |
| X — sensor length | Mismatched and the sensor either floats short of the tip, adding lag and a temperature offset, or bottoms out and is strained against the end cap |
Of the three, the sensor length is the one that gets assumed. A protection tube ordered with an immersion length and an extension length looks complete on a specification sheet, and the sensor that arrives may be a different length from the one the tube was designed around — which is why the ordering options include assemble sensor to specific transmitter and assemble sensor to specific protection tube. Buying the pair assembled removes the length match from the site's responsibility and puts it on the manufacturer's.
Where it fits
Temperature measurement where the sensor must be protected and replaceable without breaking into the process: pipe and vessel installations across the pressure and temperature range the flange or thread allows, in the materials the service needs. Order the test options where the pressure boundary matters, take the material certificate where traceability is required, and either measure the sensor properly or have the assembly built — the tube is a simple part whose failure modes are all dimensional or metallurgical.
Manufacturer reference: Rosemount 114P Protection Tubes Product Data Sheet for tube construction, threaded and flanged versions, the dimensional definitions of sensor, extension and immersion length, and the test and certification options.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | No measurement of its own, but the tube inserts a layer of metal between process and sensor: wall thickness, material, immersion depth and sensor fit all set the response lag. The uniform stem profile is thicker at the tip than a tapered well, so response is slower |
| Output signal | Not applicable - a mechanical protection tube with no electrical function |
| Diagnostics | The failure modes of a protection tube are dimensional or metallurgical, not electrical: an immersion length too short reads the wall, a sensor shorter than the tube floats off the tip and lags, and a weld defect admits process into the sensor head |
| Pressure range | Set by the flange or the machined threaded fitting welded along the tube. An external hydrostatic pressure test (Q5) is available to prove the assembly holds pressure before installation |
| Variants | Threaded and flanged versions with a uniform stem profile and a welded end cap. Options Q5 external hydrostatic pressure test, Q73 dye penetrant test and Q8 material certification, plus assembly of the sensor to a specific transmitter or protection tube |
| Application | Temperature measurement where the sensor must be protected and replaceable without breaking into the process: pipe and vessel installations across the pressure and temperature range the flange or thread allows, threaded or flanged |
| Mounting | The flange or thread welded along the tube is the process seal. Three dimensions govern the installation: immersion length U into the flowing stream, extension length N clear of insulation, and the sensor length X measured from the sensor tip to the bottom of the DIN plate |
| Operating temperature (°C) | Set by the tube material and the process. Material certification (Q8) provides traceability, and a dye penetrant test (Q73) finds surface-breaking weld defects that a pressure test can pass |