Rosemount 148 Temperature Transmitter
Purchase options
From$100.82
- Availability
- Call for availability Originalx
Configurable — choose options to build the exact part number.
Independent supplier
Sproh is an independent supplier and is not an authorized distributor or official representative of Rosemount or Emerson.
Overview
DIN B head-mount temperature transmitter with a universal RTD, thermocouple and ohm input, two-wire 4-20 mA output and PC configuration.
Key features
- DIN B head-mount temperature transmitter; fits inside the sensor connection head
- Universal single-sensor input: RTD, thermocouple or ohms, selected in software
- Two-wire 4-20 mA output, linear with temperature or input
- 12 to 42.4 Vdc supply (12 to 30 V in intrinsic safety), 12 Vdc minimum across terminals
- Update rate under 0.5 s, specification performance within 6 s of power-up
- -40 to 85 °C operating, 0 to 95% non-condensing humidity, NAMUR NE-21 and NE-43
Key specifications
- Accuracy
- Update rate under 0.5 s; specification performance within six seconds of power-up; damping 32 s maximum, 5 s default; maximum deviation under 1% of span during EMC disturbance
- Output signal
- Two-wire 4-20 mA DC, linear with temperature or input
- Power supply
- 12 to 42.4 Vdc standard, 12 to 30 Vdc with intrinsic safety; 12 Vdc minimum across terminals; input/output isolation tested to 500 Vac rms (707 Vdc) at 50/60 Hz
- Diagnostics
- Configurable alarm and saturation levels compliant with NAMUR NE-43, with hardware failures driving the output above 23 mA
- Certifications
- ATEX, IECEx, FM and CSA intrinsic safety and Type n options, with explosion-proof and dust approvals available by code
- Measurement range
- Universal single-sensor input for RTD, thermocouple and ohm signals, selected in software; recommended minimum measuring span 10 °C (18 °F)
The transmitter that lives inside the connection head
The Rosemount 148 is a DIN B head-mount temperature transmitter: it sits inside the sensor's connection head, accepts the RTD or thermocouple directly, and sends a linear 4-20 mA signal back to the control system. It is the basic member of the family, and it is the right answer for a monitoring point that does not justify anything more elaborate.
Why not wire the sensor straight to the DCS
Because a bare RTD resistance travels badly. Long runs of copper extension wire pick up noise, drift with the ambient temperature of the cable tray, and need a dedicated input card at the other end. Converting to 4-20 mA at the sensor makes the signal robust over distance and lets it land on an ordinary analog input. The 148 also compensates for ambient temperature internally, which the cable cannot do.
One input, chosen by configuration
A single universal sensor input accepts RTD, thermocouple and ohm signals, selected in software — the same transmitter covers a Pt100 in a water line and a type K in an oven flue. Configuration is done from a PC with the interface kit, so a site can stock one transmitter model and set it per point.
Numbers that matter on a panel
Two-wire 4-20 mA output, 12 to 42.4 Vdc supply (12 to 30 V in intrinsic safety), with a 12 Vdc minimum across the terminals. Input/output isolation is tested to 500 Vac rms. Update rate is under 0.5 seconds and the transmitter is within specification less than six seconds after power-up, with damping configurable to 32 seconds, 5 seconds by default. It operates from -40 to 85 °C in 0 to 95% non-condensing humidity, and meets NAMUR NE-21 for EMC with under 1% span deviation during disturbance, plus NE-43 for the signal-level breakdown it reports on failure.
Practical mounting
DIN B form, with a range of enclosure options from no enclosure (fitting an existing head) through aluminium and stainless heads to a sanitary connection head. A DIN rail mounting kit is available for panel use. The small puck shape with spring-loaded screws is what makes installation in a head a two-minute job rather than a wiring exercise.
Manufacturer reference: Rosemount 148 Temperature Transmitter Product Data Sheet, 00813-0100-4148 Rev HB, December 2023.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | Update rate under 0.5 s; specification performance within six seconds of power-up; damping 32 s maximum, 5 s default; maximum deviation under 1% of span during EMC disturbance |
| Output signal | Two-wire 4-20 mA DC, linear with temperature or input |
| Power supply | 12 to 42.4 Vdc standard, 12 to 30 Vdc with intrinsic safety; 12 Vdc minimum across terminals; input/output isolation tested to 500 Vac rms (707 Vdc) at 50/60 Hz |
| Diagnostics | Configurable alarm and saturation levels compliant with NAMUR NE-43, with hardware failures driving the output above 23 mA |
| Certifications | ATEX, IECEx, FM and CSA intrinsic safety and Type n options, with explosion-proof and dust approvals available by code |
| Measurement range | Universal single-sensor input for RTD, thermocouple and ohm signals, selected in software; recommended minimum measuring span 10 °C (18 °F) |
| Application | Basic head-mount temperature transmitter for monitoring points, replacing direct sensor wiring to the control system |
| Mounting | DIN B head mount; enclosure options from no enclosure to aluminium, stainless steel and sanitary connection heads; DIN rail kit available |
| Operating temperature (°C) | -40 to 85 °C (-40 to 185 °F) operating; -50 to 120 °C (-58 to 248 °F) storage; 0 to 95% relative humidity, non-condensing |
Documents
Accessories and related items
Accessories and related items for this product are not available to order on Sproh yet. If the manufacturer lists them, an engineer can source them for you.
Ask an engineer