Rosemount 1495 Orifice Plate
Purchase options
From$107.45
- Availability
- Call for availability Originalx
Configurable — choose options to build the exact part number.
Independent supplier
Sproh is an independent supplier and is not an authorized distributor or official representative of Rosemount or Emerson.
Overview
Paddle or universal orifice plate with concentric bore in 316/316L: beta ratios 0.40 to 0.65, for turbulent DP flow measurement in any line size.
Key features
- Paddle or universal orifice plate with concentric square-edged bore, machined from 316/316L stainless
- Specified for liquid, gas or vapour turbulent flow above Re 4,000 under AGA-3, or 5,000 and 170 Beta2 D under ASME MFC-3M and ISO-5167
- Beta ratio options 0.40, 0.50 and 0.65: a smaller beta gives more differential and more permanent loss
- The handle carries the line tag, size, flange class, bore, material and the word Inlet on the upstream face
- Installed with the high side upstream and thermowells downstream of the element; straight run is part of the accuracy claim
- With a 1496 flange union the temperature limit is set by the gasket: compressed sheet -100 to 250 F, graphite spiral wound -350 to 900 F, high temperature filler to 1250 F
Key specifications
- Accuracy
- Validity requires turbulent flow above Re 4,000 under AGA-3, or 5,000 and 170 Beta2 D (whichever is higher) under ASME MFC-3M and ISO-5167; below that limit the discharge coefficient assumed by the calculation no longer applies
- Output signal
- None directly - the plate generates a differential pressure read by a DP transmitter; beta ratios 0.40, 0.50 and 0.65 trade differential and permanent pressure loss against usable range
- Diagnostics
- No electronics; accuracy is a property of geometry and of the standard it was machined to, and the installation's straight run upstream and downstream is part of that accuracy claim
- Pressure range
- Maximum working pressure follows ASME B16.36 and B16.5 for WN, SO, TH and RJ flange types, or EN-1092-1 for DN flanges; with a 1496 union the gasket sets the temperature limit as well
- Variants
- Paddle type with retaining handle or universal type; concentric square-edged bore as standard with other bore profiles per the reference manual; 316/316L stainless steel construction
- Application
- Differential pressure flow measurement of liquid, gas or vapour in lines from small bore to very large pipe, wherever a DP transmitter and adequate straight run exist
The flow element that has never needed a firmware update
The Rosemount 1495 is a machined orifice plate: a stainless disc with a precision bore that clamps between two flanges and creates the differential pressure a transmitter measures. There is no electronics in it and nothing to drift. In a market full of smart meters it remains the cheapest accurate way to measure flow in a large line, and the reason is that its accuracy comes from geometry and from the standard it was made to, not from calibration.
Paddle or universal
The paddle type is the one with a handle — the plate and its retaining tab are one piece, and it drops between flange faces with the handle sticking out. The universal type is a plain disc that fits a wider range of holder arrangements. Both are square-edged concentric by default; the reference manual also covers other bore profiles for services where the standard square edge is not appropriate. The handle is where the plate tells you what it is: line tag, size, flange class, bore, material and the word Inlet on the upstream face.
What the standard actually requires
The plate is only accurate inside its published regime, and that regime is turbulence, not just flow. The 1495 is specified for liquid, gas or vapour turbulent flow with pipe Reynolds numbers above 4,000 under AGA-3, or 5,000 and 170β²D (whichever is higher) under ASME MFC-3M and ISO-5167. That second form matters: the requirement rises with beta ratio and pipe diameter, so a large line at low velocity can sit below the limit while looking perfectly reasonable on a flow sheet. Below the limit, the discharge coefficient the calculation assumes is no longer the coefficient the plate delivers.
Beta ratio is a design choice, not an option code
Bore sizes are offered at beta ratios of 0.40, 0.50 and 0.65. A small beta gives a larger differential for the same flow — better resolution at low flow, more permanent pressure loss. A large beta gives a lower differential and less loss, but a shorter usable range and a greater sensitivity to the pipe's own roughness and to installation effects. Choosing it is a flow-calculation decision, which is why the plates are ordered to a calculated bore rather than picked from a table.
Installation rules that carry real money
The manual is specific about orientation: the Inlet stamp faces upstream, the high side of the transmitter goes to the upstream tap, and temperature taps and thermowells go downstream of the element so the wake does not disturb the measurement. Straight-run requirements upstream and downstream are part of the accuracy claim — a plate installed two diameters downstream of an elbow measures the elbow's swirl as much as the flow.
The flange union is where temperature lives
When the 1495 is supplied with a 1496 orifice flange union, the temperature limit is set by the gasket, not by the plate: compressed sheet is rated -100 to 250 °F, PTFE-filled spiral wound -350 to 250 °F, graphite spiral wound -350 to 900 °F, and the high-temperature filler option reaches 1250 °F subject to the flange material. Maximum working pressure follows ASME B16.36 and B16.5 for the flange types, or EN-1092-1 for DN flanges. A hot-service enquiry that quotes only the flange rating and not the gasket is incomplete.
Where it fits
Steam, gas, water and process lines from small bore to very large pipe, anywhere a DP transmitter and a straight run exist and the budget matters. It is also the element that survives what smart meters do not: high temperature, high pressure, vibration, and a plant that has no power at the measurement point.
Manufacturer reference: Rosemount 1495 Orifice Plate and 1496 Orifice Flange Union Reference Manual 00809-0100-4792, and Rosemount DP Flow Meters Product Data Sheet specifications for the 1495 and 1496.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | Validity requires turbulent flow above Re 4,000 under AGA-3, or 5,000 and 170 Beta2 D (whichever is higher) under ASME MFC-3M and ISO-5167; below that limit the discharge coefficient assumed by the calculation no longer applies |
| Output signal | None directly - the plate generates a differential pressure read by a DP transmitter; beta ratios 0.40, 0.50 and 0.65 trade differential and permanent pressure loss against usable range |
| Diagnostics | No electronics; accuracy is a property of geometry and of the standard it was machined to, and the installation's straight run upstream and downstream is part of that accuracy claim |
| Pressure range | Maximum working pressure follows ASME B16.36 and B16.5 for WN, SO, TH and RJ flange types, or EN-1092-1 for DN flanges; with a 1496 union the gasket sets the temperature limit as well |
| Variants | Paddle type with retaining handle or universal type; concentric square-edged bore as standard with other bore profiles per the reference manual; 316/316L stainless steel construction |
| Application | Differential pressure flow measurement of liquid, gas or vapour in lines from small bore to very large pipe, wherever a DP transmitter and adequate straight run exist |
| Mounting | Clamped between flange faces; the handle is stamped Inlet on the upstream face, the high side of the transmitter goes to the upstream tap, and thermowells are located downstream of the element |
| Operating temperature (°C) | Set by the flange union and gasket when supplied with a 1496: compressed sheet -100 to 250 F, PTFE-filled spiral wound -350 to 250 F, graphite spiral wound -350 to 900 F, high temperature filler to 1250 F subject to flange material |