Skip to main content
Sold and shipped by Sproh

Rosemount 2130 Vibrating Fork Level Switch

Part number2130ManufacturerEmerson

Purchase options

From$376.97

Availability
Call for availability Originalx
Select option

Configurable — choose options to build the exact part number.

Independent supplier

Sproh is an independent supplier and is not an authorized distributor or official representative of Rosemount or Emerson.

Overview

Vibrating fork point level switch with electronic self-checking and condition monitoring, SIL 2 certified, for high and low level alarm in tanks and pipes.

Key features

  • Vibrating fork point level switch for high and low level alarm, overfill protection and pump control
  • Electronic self-checking with heartbeat LED: detects coated, blocked or damaged forks and extreme corrosion
  • Process temperature -70 to 260 C (high temperature version) or -40 to 180 C (mid-range)
  • Five self-checking output cassettes: direct load switching, PNP/PLC, DPCO relay, NAMUR and 8/16 mA
  • SIL 2 certified to IEC 61508 and SIL 3 capable; IP66/67 and NEMA 4X
  • Fast drip fork for viscous liquids; density to 500 kg/m3 with the low density option, viscosity to 10 000 cP

Key specifications

Process temperature
-70 to 260 °C (-94 to 500 °F) for the high temperature version; -40 to 180 °C (-40 to 356 °F) for the mid-range version
Enclosure rating
IP66/67 to EN 60529 and NEMA 4X, in aluminium alloy ASTM B85 A360.0 or 316 stainless steel housings
Output signal
Five self-checking plug-in electronics cassettes: direct load switching (mains two-wire) 20 to 264 Vac 50/60 Hz or 20 to 60 Vdc; PNP/PLC low voltage three-wire 20 to 60 Vdc; DPCO relay; NAMUR 8 Vdc; and 8/16 mA
Diagnostics
Continuous electronic self-checking detects internal and external fork damage, coating or blockage and extreme corrosion; heartbeat LED shows instrument health; magnetic test point allows functional testing without opening the housing
Certifications
SIL 2 certified to IEC 61508 as required by IEC 61511, and SIL 3 capable; general area, explosion-proof/flameproof and intrinsically safe approval options for ATEX, IECEx, FM, CSA, Brazil and China
Measurement range
Switching point 13 mm from the fork tip when mounted vertically, or 13 mm from the fork edge horizontally; hysteresis 2.5 mm in water; minimum density 600 kg/m³ standard or 500 kg/m³ with the low density range option; viscosity up to 10 000 cP in Normal mode
See all specifications