Rosemount 214A Temperature Sensor
Purchase options
Request a quote
- Availability
- Call for availability Originalx
Independent supplier
Sproh is an independent supplier and is not an authorized distributor or official representative of Rosemount or Emerson.
Overview
RTD and thermocouple temperature sensor, -196 to 1200 C, in 2, 3 or 4-wire with spring-loaded well contact and ATEX options.
Key features
- Industrial temperature sensor in RTD and thermocouple forms: Pt100 and Pt1000 in Class A or B, and Type E, J, K, T or N thermocouples in class 1 or 2
- RTD range -196 to 600 C, thermocouple range -40 to 1200 C, in single or dual element versions
- 2, 3 or 4-wire connection: at about 0.385 ohm per degree for a Pt100, one ohm of lead resistance in a 2-wire run adds roughly 2.6 C to every reading, so the wire count decides accuracy more than the element class does
- Spring-loaded adapter holds the sensor tip against the bottom of a thermowell, because an air gap lags the reading and the usual diagnosis is to blame the transmitter damping
- Thin-film or wire-wound elements, Pt1000 with ten times the resistance so lead resistance matters ten times less, and 316, 321 or Alloy 600 sheaths
- ATEX flameproof, intrinsic safety and increased safety certification options
Key specifications
- Accuracy
- RTD Pt100 or Pt1000 in Class A or Class B per IEC 60751, whose permitted error grows with temperature; thermocouples in class 1 or 2. The practical error is often set by the wiring: one ohm of lead resistance in a 2-wire run is about 2.6 C, against a Pt100 sensitivity of roughly 0.385 ohm per degree
- Output signal
- Resistance or thermocouple millivolts, taken to a transmitter or directly to the control system. Available as a single or dual element in 2, 3 or 4-wire connection
- Diagnostics
- Certifications ATEX Flameproof, ATEX Intrinsic Safety and ATEX Increased Safety. Two error sources worth checking before blaming the element: the wire configuration, and whether the tip actually contacts the bottom of the well
- Pressure range
- Set by the thermowell and the process connection rather than by the sensor. Sheath materials are 316 or 321 stainless steel or Alloy 600
- Variants
- RTD Pt100 and Pt1000, thin-film or wire-wound, Class A or B. Thermocouple Type E, J, K, T or N, class 1 or 2. Wire configurations S2/S3/S4 single and D2/D3/D4 dual. Sheaths 316 SST, 321 SST or Alloy 600, with connection heads and a spring-loaded adapter option
- Application
- Process temperature measurement in pipe and vessel thermowells: utilities, chemical and hydrocarbon service with the appropriate sheath, and higher temperature work that needs a thermocouple above the practical ceiling of a platinum element
Most temperature errors are not the element
The Rosemount 214A is an industrial temperature sensor in both resistance and thermocouple forms: Pt100 and Pt1000 RTDs in Class A or Class B, thin-film or wire-wound, and Type E, J, K, T or N thermocouples in class 1 or 2. RTDs cover −196 to 600 °C, thermocouples −40 to 1200 °C, and the sensor is offered as a single or dual element in 2, 3 or 4-wire connection, with 316 or 321 stainless or Alloy 600 sheaths and ATEX flameproof, intrinsic safety or increased safety certification.
That is a lot of choice for a part that, in service, usually fails the measurement for one of two reasons that have nothing to do with the element inside it.
The wiring configuration is the first one
A Pt100 does not report temperature directly; it reports resistance, and the sensitivity of that relationship is the number everything else is measured against: roughly 0.385 Ω per degree Celsius. That sensitivity is what makes the wiring configurable matter so much, because the cable that connects the sensor to the transmitter has resistance of its own, and the transmitter cannot tell it apart from the element.
Do the arithmetic on a 2-wire connection. One ohm of total lead resistance — trivial for a hundred metres of ordinary copper — looks to the transmitter like 1 ÷ 0.385, which is about 2.6 °C of error, added to every reading, on every day, in the same direction. A Class A element with a fraction of a degree of tolerance has been buried by its own cable.
The three configurations exist to deal with exactly that:
| Connection | What it does with lead resistance |
|---|---|
| 2-wire | Adds it to the measurement. Acceptable only where the leads are short and the accuracy requirement is loose |
| 3-wire | Measures the loop and compensates for it, assuming the leads match. The normal industrial choice |
| 4-wire | Removes it entirely by using a separate pair to carry the measuring current. The choice when the reading has to be right |
So the ordering decision that most affects accuracy is not the class of the element — it is the number of wires, and it is made on the model code before anybody measures anything.
The second one is contact, and it is mechanical
An RTD or thermocouple in a thermowell measures the well, not the process. If the sensor tip does not touch the bottom of the well, the gap is a layer of air, and air is an insulator: the reading lags every change in the process and sits at a temperature that is a compromise between the process and the head.
That is what the spring-loaded adapter is for. It pushes the sensor tip against the bottom of the well so the heat path is metal to metal, and it absorbs the tolerance in well depth that no drawing ever quite matches. On a sensor without it, the same well that works perfectly on a bench reads sluggishly in service — and the usual response is to blame the transmitter's damping.
Choosing the element and the sheath
Class A or Class B is a tolerance class per IEC 60751, and the permitted error in a class grows with temperature. A class that is comfortable at 100 °C can be the largest error term at 400 °C, which is why the class decision belongs with the process temperature rather than with a default in the model code.
Thin-film against wire-wound is a construction choice: thin-film elements are the smaller and more vibration-tolerant of the two, wire-wound elements are the traditional high-stability form. The Pt1000 option is the same platinum element with ten times the resistance, which makes lead resistance ten times less significant — a real advantage on a 2-wire run, and the reason Pt1000 exists at all.
Sheath materials follow the same logic as any wetted part: 316 stainless for ordinary process and utility service, 321 where higher temperature strength is wanted, and Alloy 600 for the aggressive or high-temperature end of the range. Dual elements are for the case that needs two independent measurements from one penetration — a control loop and a safety trip, or a transmitter and a local indicator, without drilling a second hole in the pipe.
Where it fits
Process temperature measurement in pipe and vessel thermowells across the range the plant actually runs: utilities, chemical and hydrocarbon service with the right sheath, and the higher-temperature work that needs a thermocouple rather than an RTD above the platinum element's practical ceiling. Order the wire configuration from the cable run and the required accuracy, order the spring-loaded adapter whenever there is a thermowell, and treat the class and the sheath as consequences of the process rather than defaults.
Manufacturer reference: Rosemount 214A Temperature Sensor Product Data Sheet for sensor types, tolerance classes, temperature ranges, wire configurations, sheath materials and certifications.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | RTD Pt100 or Pt1000 in Class A or Class B per IEC 60751, whose permitted error grows with temperature; thermocouples in class 1 or 2. The practical error is often set by the wiring: one ohm of lead resistance in a 2-wire run is about 2.6 C, against a Pt100 sensitivity of roughly 0.385 ohm per degree |
| Output signal | Resistance or thermocouple millivolts, taken to a transmitter or directly to the control system. Available as a single or dual element in 2, 3 or 4-wire connection |
| Diagnostics | Certifications ATEX Flameproof, ATEX Intrinsic Safety and ATEX Increased Safety. Two error sources worth checking before blaming the element: the wire configuration, and whether the tip actually contacts the bottom of the well |
| Pressure range | Set by the thermowell and the process connection rather than by the sensor. Sheath materials are 316 or 321 stainless steel or Alloy 600 |
| Variants | RTD Pt100 and Pt1000, thin-film or wire-wound, Class A or B. Thermocouple Type E, J, K, T or N, class 1 or 2. Wire configurations S2/S3/S4 single and D2/D3/D4 dual. Sheaths 316 SST, 321 SST or Alloy 600, with connection heads and a spring-loaded adapter option |
| Application | Process temperature measurement in pipe and vessel thermowells: utilities, chemical and hydrocarbon service with the appropriate sheath, and higher temperature work that needs a thermocouple above the practical ceiling of a platinum element |
| Mounting | Installed in a thermowell with the spring-loaded adapter pushing the sensor tip against the bottom of the well, so the heat path is metal to metal and the tolerance in well depth is absorbed. Also available as a mineral insulated sensor with connection head and spring-loaded adapter |
| Operating temperature (°C) | RTD range -196 to 600 C, thermocouple range -40 to 1200 C, with thin-film or wire-wound element construction |