Rosemount 214C RTD
Purchase options
From$66.85
- Availability
- Call for availability Originalx
Configurable — choose options to build the exact part number.
Independent supplier
Sproh is an independent supplier and is not an authorized distributor or official representative of Rosemount or Emerson.
Overview
Pt100 RTD with alpha 0.00385 in a 1/4 in. sheath: thin film to 450 C, wire wound to 300 C, high temperature thin film to 600 C.
Key features
- Pt100 RTD with alpha 0.00385 in a 1/4 in. (6 mm) nominal diameter sheath, part of the 214C sensor family
- Three elements: RT thin film -50 to 450 C, RW wire wound -196 to 300 C, RH high temperature thin film -60 to 600 C
- Class A (A1) per IEC 60751 only over -50 to 300 C and only with the wire-wound RW element; B1 Class B across the range
- 321 SST sheath with a maximum operating limit of 816 C (1500 F), spring-loaded and compact spring-loaded mounting styles
- Callendar-Van Dusen constants supplied so a Rosemount transmitter can be matched to the individual element
- Available as transmitter-assembled-to-sensor and thermowell-assembled-to-sensor complete point solutions
Key specifications
- Accuracy
- A1 Class A per IEC 60751 over -50 to 300 C (-58 to 572 F), available ONLY with the wire-wound RW element; B1 Class B per IEC 60751 across the range; Callendar-Van Dusen constants supplied for matching to a Rosemount transmitter
- Output signal
- Pt100 resistance element with alpha 0.00385, single 3-wire or multi-element configurations, wired to a connection head or a transmitter assembled to the sensor
- Diagnostics
- Class A accuracy is restricted to the wire-wound element and to -50 to 300 C, so a Class A requirement above 300 C cannot be met by this sensor - the ordering table decides which combination is valid
- Pressure range
- Governed by the thermowell and the process connection selected with the sensor rather than by the sensor itself; the sheath is 1/4 in. (6 mm) nominal diameter in 321 SST
- Variants
- Three RTD element codes (RT, RW, RH), accuracy A1 or B1, single or multiple elements and 3-wire or 4-wire configurations, spring-loaded and compact spring-loaded mounting styles, 316 SST component options
- Application
- Process temperature measurement in pipes and vessels where a Pt100 is required, including chemical and refining process lines and utility points where thermocouple drift over time is unacceptable
An RTD where the element choice decides the temperature range, not the sheath
The Rosemount 214C is the platinum RTD half of Emerson's 214C sensor family: a Pt100 element with an alpha of 0.00385 inside a 1/4 inch nominal diameter sheath, offered in three element constructions that cover different parts of the temperature scale. The family also includes Type J, K and T thermocouples, but the RTD versions are the ones to choose where accuracy and stability matter more than the top of the range.
Three elements, three ranges
The code on the order decides the range, and choosing by range alone is how people end up with the wrong element. RT is a thin-film Pt100 from -50 to 450 °C (-58 to 842 °F), and thin film is the construction that survives vibration and physical shock best. RW is a wire-wound Pt100 from -196 to 300 °C (-321 to 572 °F) — the wire-wound element is the one for low temperature work, and it is also the only element that can carry Class A accuracy. RH is a high temperature thin-film Pt100 from -60 to 600 °C (-76 to 1112 °F), which is the version for the hot end of the RTD range.
Accuracy class and what it is tied to
The A1 accuracy code is Class A per IEC 60751, but only over -50 to 300 °C and only with the wire-wound RW element. B1 is Class B per IEC 60751 and is available across the range. A specification that says Class A and a temperature above 300 °C therefore cannot both be satisfied by this sensor, and the ordering table is the place that settles it rather than the datasheet summary.
Sheath and installation
The standard sheath material is 321 stainless steel, with a maximum operating limit of 816 °C (1500 °F) — a sheath limit well above the element limits, which is the right way round: the element fails first, and the number that constrains the application is the element's range. Sensors are available in spring-loaded and compact spring-loaded mounting styles, which is what keeps the tip in contact with the bottom of a thermowell as the well expands and the process cycles. All styles and lengths are standard in the 1/4 inch (6 mm) nominal diameter.
What the calibration buys
Emerson supplies Callendar-Van Dusen constants for these sensors, so a Rosemount transmitter can be matched to the individual element rather than to a nominal curve. That is the difference between a sensor and a matched sensor-transmitter pair: the CVD values take the element's own deviation into account and remove part of the interchangeability error that Class A alone leaves in place.
Complete point option
Emerson offers this family as a transmitter-assembled-to-sensor and thermowell-assembled-to-sensor configuration, delivered process-ready or hand-tight. For a project that is a schedule decision as much as an engineering one — it moves the assembly work off site — and it guarantees that the thermowell, the sensor length and the transmitter are the combination that was specified.
Where it fits
Process temperature measurement in pipes and vessels where a Pt100 is required: process lines in chemical and refining service, utility and balance-of-plant points, and any location where a thermocouple's drift over time is not acceptable. The version to choose depends on the range and on whether Class A is needed — which in practice means whether the wire-wound RW element is acceptable at the temperature involved.
Manufacturer reference: Rosemount 214C Temperature Sensors Product Data Sheet, RTD ordering information and Table 1 element codes.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | A1 Class A per IEC 60751 over -50 to 300 C (-58 to 572 F), available ONLY with the wire-wound RW element; B1 Class B per IEC 60751 across the range; Callendar-Van Dusen constants supplied for matching to a Rosemount transmitter |
| Output signal | Pt100 resistance element with alpha 0.00385, single 3-wire or multi-element configurations, wired to a connection head or a transmitter assembled to the sensor |
| Diagnostics | Class A accuracy is restricted to the wire-wound element and to -50 to 300 C, so a Class A requirement above 300 C cannot be met by this sensor - the ordering table decides which combination is valid |
| Pressure range | Governed by the thermowell and the process connection selected with the sensor rather than by the sensor itself; the sheath is 1/4 in. (6 mm) nominal diameter in 321 SST |
| Variants | Three RTD element codes (RT, RW, RH), accuracy A1 or B1, single or multiple elements and 3-wire or 4-wire configurations, spring-loaded and compact spring-loaded mounting styles, 316 SST component options |
| Application | Process temperature measurement in pipes and vessels where a Pt100 is required, including chemical and refining process lines and utility points where thermocouple drift over time is unacceptable |
| Mounting | Spring-loaded or compact spring-loaded styles keep the tip in contact with the bottom of the thermowell as it expands; all styles and lengths standard in 1/4 in. (6 mm) nominal diameter |
| Operating temperature (°C) | Element dependent: RT thin film -50 to 450 C (-58 to 842 F), RW wire wound -196 to 300 C (-321 to 572 F), RH high temperature thin film -60 to 600 C (-76 to 1112 F); 321 SST sheath limit 816 C (1500 F) |
Documents
Accessories and related items
Accessories and related items for this product are not available to order on Sproh yet. If the manufacturer lists them, an engineer can source them for you.
Ask an engineer