Rosemount 3051SAL Liquid Level Transmitter
Purchase options
From$1,712.66
- Availability
- Call for availability Originalx
Independent supplier
Sproh is an independent supplier and is not an authorized distributor or official representative of Rosemount or Emerson.
Overview
Liquid level transmitter on the 3051S platform with a diaphragm seal at the process, available direct-mounted or as a Tuned-System with an 1199 remote seal.
Key features
- Liquid level transmitter on the 3051S platform with a diaphragm seal at the process
- Direct-mount flanged seal, or 1199 remote seal as a Tuned-System where the tap is out of reach
- Reference accuracy +/-0.055% of span (Ultra) or +/-0.065% (Classic) on ranges 2 to 5
- Diaphragms in 316L SST, Alloy C-276, Alloy 400, Tantalum, or gold-plated for hydrogen service
- 4-20 mA with HART, FOUNDATION Fieldbus or WirelessHART; 10.5 to 42.4 Vdc
- Measures level through a sealed diaphragm, so the transmitter never contacts the product
Key specifications
- Accuracy
- Reference accuracy +/-0.055% of span with Ultra and +/-0.065% with Classic on ranges 2 to 5, degrading below 10:1 span to +/- (0.015 + 0.005[URL/Span])% of span
- Output signal
- 4-20 mA with HART digital signal; FOUNDATION Fieldbus and WirelessHART available on the 3051S platform
- Power supply
- 10.5 to 42.4 Vdc with no load for the standard 4-20 mA transmitter
- Diagnostics
- 3051S platform diagnostics including the Advanced HART diagnostics suite, with sensor and electronics temperature available to the host
- Measurement range
- Level ranges 2 to 5 on the 3051S platform; the measured DP span corresponds to the liquid head between the two taps
- Application
- Liquid level measurement by differential pressure with a diaphragm seal at the process, direct-mounted or as a Tuned-System with an 1199 remote seal
Level measured behind a diaphragm, not in the fluid
The Rosemount 3051SAL is the liquid level member of the 3051S platform: a differential pressure transmitter with a diaphragm seal at the process, arranged either directly on the flange or remotely through a capillary as a Tuned-System. It measures level by measuring the head of liquid above a tap, which is the oldest and still the most common way to know what is in a tank.
Why a seal at all
A plain DP transmitter at the bottom of a tank has process fluid inside its impulse piping and against its own diaphragm. That is fine for clean water and unacceptable for anything that crystallises, polymerises, solidifies when it cools, or eats 316 stainless. The seal puts a thin diaphragm against the process and fills the space behind it with a stable fluid, so the transmitter measures pressure without ever touching the product.
Direct mount or Tuned-System
Direct mount puts the seal on the transmitter's own flange — compact, no capillary, and the least temperature error. When the tap is not where the transmitter can live, an 1199 remote seal with a capillary makes it a Tuned-System, and the capillary's fill fluid then becomes part of the measurement: its volume changes with ambient temperature, and that change appears as level error. The choice between the two is usually made by access, not by preference.
Accuracy
Reference accuracy is ±0.055% of span with Ultra and ±0.065% with Classic on ranges 2 to 5, degrading below 10:1 span to ±(0.015 + 0.005[URL/Span])% of span. Those figures are for the transmitter; the seal assembly and capillary add their own contribution, which is why a Tuned-System is specified as a system rather than as a sum of parts.
Wetted materials and process compatibility
Diaphragms are available in 316L stainless steel, Alloy C-276, Alloy 400, Tantalum, and gold-plated Alloy 400 or 316L — the last two for hydrogen service, where a gold barrier is what stops the gas diffusing into the fill fluid. Seal bodies, flanges and gaskets follow the same material logic as the rest of the 1199 range.
Where it fits
Tanks and vessels holding viscous, corrosive, hygienic or high-temperature product: food and pharmaceutical vessels, chemical reactors, pulp and paper stock lines, and any level measurement where a wet leg or a dry leg would need heat tracing and constant attention.
Electronics
4-20 mA with HART on the 3051S platform, with FOUNDATION Fieldbus and WirelessHART available, 10.5 to 42.4 Vdc with no load, and the platform's diagnostics and remote display options carried across.
Manufacturer reference: Rosemount 3051S Series of Instrumentation Product Data Sheet, 00813-0100-4801 Rev UV, August 2025.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | Reference accuracy +/-0.055% of span with Ultra and +/-0.065% with Classic on ranges 2 to 5, degrading below 10:1 span to +/- (0.015 + 0.005[URL/Span])% of span |
| Output signal | 4-20 mA with HART digital signal; FOUNDATION Fieldbus and WirelessHART available on the 3051S platform |
| Power supply | 10.5 to 42.4 Vdc with no load for the standard 4-20 mA transmitter |
| Diagnostics | 3051S platform diagnostics including the Advanced HART diagnostics suite, with sensor and electronics temperature available to the host |
| Measurement range | Level ranges 2 to 5 on the 3051S platform; the measured DP span corresponds to the liquid head between the two taps |
| Application | Liquid level measurement by differential pressure with a diaphragm seal at the process, direct-mounted or as a Tuned-System with an 1199 remote seal |
| Mounting | Direct mount of the seal on the transmitter flange, or remote mount through a capillary to an 1199 seal as a Tuned-System when the tap is out of reach |
| Material of construction | Diaphragms available in 316L SST, Alloy C-276, Alloy 400, Tantalum, gold-plated Alloy 400 and gold-plated 316L SST; seal bodies and flanges follow the 1199 range |