Rosemount 3308 Wireless Level Transmitter
Purchase options
From$1,675.30
- Availability
- Call for availability Originalx
Independent supplier
Sproh is an independent supplier and is not an authorized distributor or official representative of Rosemount or Emerson.
Overview
WirelessHART guided wave radar level and interface transmitter: +/-3 mm high performance accuracy, no wiring at the tank, probe cut to fit on site.
Key features
- WirelessHART guided wave radar (TDR) level and interface transmitter, IEC 62591, with no wiring at the tank
- Reference accuracy +/-0.12 in. (+/-3 mm) high performance profile, +/-0.25 in. (+/-6 mm) standard profile
- Process conditions -15 psig (-1 bar) to 580 psig (40 bar) at 302 F (150 C)
- Coaxial, rigid single lead 8 mm and 13 mm, flexible single and twin lead and segmented probe options, cut to fit on site
- Interface measurement requires a fully submerged probe; PTFE covered probes start at 4 ft 11 in. (1.5 m)
- Also available as level-only (code 1) or level-and-interface (code 2)
Key specifications
- Accuracy
- Reference accuracy +/-0.12 in. (+/-3 mm) with the high performance profile (code U) and +/-0.25 in. (+/-6 mm) with the standard profile (code S)
- Output signal
- IEC 62591 (WirelessHART) communication through a self-organizing wireless network and gateway, so no signal cable is required at the vessel
- Diagnostics
- Guided radar is largely indifferent to vapour, gas mixtures, density, turbulence, boiling, pH and viscosity, but the product's dielectric constant sets the usable range - a low-dielectric medium reflects weakly and shortens it
- Pressure range
- -15 psig (-1 bar) to 580 psig (40 bar) at 302 F (150 C), with the probe and process connection determining the limit for a given installation
- Variants
- Level-only (code 1) or level-and-interface (code 2, interface requires a fully submerged probe). Probes: coaxial perforated, rigid single lead 8 mm and 13 mm, flexible single lead, flexible twin lead with weight, segmented rigid single lead; minimum length 1 ft 4 in. (0.4 m), or 4 ft 11 in. (1.5 m) for PTFE covered probes
- Application
- Aggregate level on liquids and semi-liquids and liquid/liquid interface in separators, in locations where wiring is the obstacle: tank farms, remote sumps, water and wastewater wet wells, and small vessels on skids
Wireless solves the wiring, not the physics
The Rosemount 3308 is a guided wave radar (time domain reflectometry) level and interface transmitter that communicates over WirelessHART. It exists because a large share of the tanks a plant wants to measure have no power and no signal cable at them — a remote sump, a separator on a far skid, a tank that was never instrumented because pulling cable to it cost more than the instrument. The 3308 removes that cost. It does not remove the physics.
What TDR does and where it stops
A low-energy pulse is launched down a probe and reflects from the change in dielectric constant at the product surface; the time of flight gives the level. Because the pulse is guided rather than radiated, the measurement is largely indifferent to vapour, gas mixtures, density, turbulence, boiling, pH and viscosity — the conditions that make ultrasonic and free-space radar difficult. What it is not indifferent to is the dielectric constant of the product: a low-dielectric medium reflects weakly, and the usable measuring range falls accordingly. A tank that measures perfectly on water can be marginal on a light hydrocarbon, with the same instrument and the same probe.
Accuracy, stated in two grades
Reference accuracy is ±0.12 in (±3 mm) with the high performance profile and ±0.25 in (±6 mm) with the standard profile. Process conditions run from -15 psig (-1 bar) to 580 psig (40 bar) at 302 °F (150 °C). The transmitter is available as level-only or level-and-interface, and the interface measurement requires a fully submerged probe — which is a real constraint on how the probe is ordered, not a software option.
The probe is the installation
Options include coaxial (perforated, for level and interface), rigid single lead in 8 mm and 13 mm, flexible single lead, flexible twin lead with a weight, and segmented rigid single lead, in lengths from 1 ft 4 in (0.4 m) up. Three details decide whether one works in a given tank: a coaxial probe is the most tolerant of a stilling well and of low-dielectric product, but its annulus can plug in dirty service; a single lead does not plug but needs centring discs to keep it away from the wall; and a PTFE-covered probe has a longer minimum length — 4 ft 11 in (1.5 m) — than the bare version. Probes are cut to fit on site, which is what makes commissioning fast and also what makes the probe selection a decision to get right before the box is opened.
What the battery figure really says
The instrument is marketed on long battery life, no wires, no moving parts and no re-calibration. The honest reading of a battery life figure is that it belongs to an update interval: a device reporting every minute and a device reporting every hour do not have the same battery life, and the number in a brochure is measured at one of those. The choice of update rate is therefore a maintenance decision disguised as a network setting, and it should be made with the loop that consumes the value — a tank watched for overfill does not need the same freshness as one used for inventory.
Where it fits
Aggregate level on liquids and semi-liquids, and liquid/liquid interface in separators, in locations where wiring is the obstacle: tank farms, remote sumps, water and wastewater wet wells, and small vessels on skids that were never instrumented. It is also the pragmatic answer where a wired installation would need a hazardous-area cable run and a permit to open an existing conduit.
Manufacturer reference: Rosemount 3308 Series Wireless Guided Wave Radar Level and Interface Transmitter Product Data Sheet 00813-0100-4308.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | Reference accuracy +/-0.12 in. (+/-3 mm) with the high performance profile (code U) and +/-0.25 in. (+/-6 mm) with the standard profile (code S) |
| Output signal | IEC 62591 (WirelessHART) communication through a self-organizing wireless network and gateway, so no signal cable is required at the vessel |
| Diagnostics | Guided radar is largely indifferent to vapour, gas mixtures, density, turbulence, boiling, pH and viscosity, but the product's dielectric constant sets the usable range - a low-dielectric medium reflects weakly and shortens it |
| Pressure range | -15 psig (-1 bar) to 580 psig (40 bar) at 302 F (150 C), with the probe and process connection determining the limit for a given installation |
| Variants | Level-only (code 1) or level-and-interface (code 2, interface requires a fully submerged probe). Probes: coaxial perforated, rigid single lead 8 mm and 13 mm, flexible single lead, flexible twin lead with weight, segmented rigid single lead; minimum length 1 ft 4 in. (0.4 m), or 4 ft 11 in. (1.5 m) for PTFE covered probes |
| Application | Aggregate level on liquids and semi-liquids and liquid/liquid interface in separators, in locations where wiring is the obstacle: tank farms, remote sumps, water and wastewater wet wells, and small vessels on skids |
| Mounting | Flange or 1 in., 1-1/2 in. and 2 in. thread, or tri-clamp depending on probe type. Probes are cut to fit on site, and single lead probes need centring discs to keep them clear of the vessel wall |
| Operating temperature (°C) | Process to 302 F (150 C); the transmitter electronics and battery sit in the housing, so ambient temperature at the mounting point is the practical limit for battery life |