Overview
HART-to-analog signal converter that turns one multivariable transmitter's digital signal into up to three additional 4-20 mA analog outputs.
Key features
- Converts a HART burst-mode signal into one, two or three additional 4-20 mA outputs
- Electrically isolated analog output channels
- External power supply per channel, 11 to 42.4 Vdc; channel 1 must be powered
- Reference accuracy +/-0.045% of span
- Failure alarm drives all channels below 3.75 mA or above 21.75 mA, by model
- Three DIN rail mounting options; FM and CSA ordinary locations
Key specifications
- Accuracy
- Reference accuracy +/-0.045% of span; ambient temperature effect +/-0.15% of span per 50 °F (28 °C)
- Output signal
- One, two or three user-selectable 4-20 mA output signals on electrically isolated channels
- Power supply
- External power supply required for each channel, 11 to 42.4 Vdc; channel 1 must be powered for the Tri-Loop to operate
- Diagnostics
- On a Tri-Loop or transmitter failure, all analog channels are driven below 3.75 mA or above 21.75 mA, high or low alarm depending on the model
- Certifications
- Approved for FM ordinary locations and CSA ordinary locations only
- Application
- Converting the digital HART burst signal of a multivariable transmitter into additional analog outputs for a control system that has only current-loop inputs
Three analog signals out of one HART device
The 333 Tri-Loop takes the digital HART burst signal from a multivariable transmitter and turns it into up to three additional 4-20 mA analog outputs. It exists because the transmitter knows more than the control system can accept: a 3051S measures differential pressure, static pressure and temperature, but an older PLC has analog inputs, not HART.
Why not just use HART
Because the receiving system may not speak it. A plant with a legacy DCS or a chart recorder expects a current loop, and replacing that infrastructure to read a second variable is not a project anyone wants. The Tri-Loop puts each additional variable on its own isolated 4-20 mA channel, so the measurement upgrades without touching the control system.
What it needs to work
An external power supply for every channel in use, 11 to 42.4 Vdc, and channel 1 must be powered for the unit to operate at all — a detail that catches out a panel builder wiring only the channels they intend to use. Loop resistance follows the usual current-loop rule: maximum resistance is the supply voltage minus 11, divided by 0.022. Analog outputs are within specification five seconds after power-up.
Accuracy and alarms
Reference accuracy is ±0.045% of span, with a ±0.15% ambient temperature effect per 50 °F — good enough that the converter is not the weak link in a multivariable measurement. On a fault, every channel is driven either below 3.75 mA or above 21.75 mA, high or low alarm depending on the model ordered, so the control system sees the failure rather than a plausible mid-scale value.
Where it goes
DIN rail, with three mounting options. Approved for FM and CSA ordinary locations, ambient 10 to 40 °C. It is panel equipment, not field equipment, and it is specified as an accessory to the 3051S MultiVariable, 3051S Advanced Diagnostics, 3144P or any HART device with a burst mode output.
Where it fits
Revamps and upgrades where a multivariable transmitter has to feed an existing analog control system, and skids where several process variables come from one device but the PLC has fixed analog cards.
Manufacturer reference: Rosemount 333 HART Tri-Loop Product Data Sheet, 00813-0100-4754 Rev GB.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | Reference accuracy +/-0.045% of span; ambient temperature effect +/-0.15% of span per 50 °F (28 °C) |
| Output signal | One, two or three user-selectable 4-20 mA output signals on electrically isolated channels |
| Power supply | External power supply required for each channel, 11 to 42.4 Vdc; channel 1 must be powered for the Tri-Loop to operate |
| Diagnostics | On a Tri-Loop or transmitter failure, all analog channels are driven below 3.75 mA or above 21.75 mA, high or low alarm depending on the model |
| Certifications | Approved for FM ordinary locations and CSA ordinary locations only |
| Application | Converting the digital HART burst signal of a multivariable transmitter into additional analog outputs for a control system that has only current-loop inputs |
| Mounting | DIN rail, with three mounting options |
| Transmitter compatibility | 3051S MultiVariable, 3051S Advanced HART Diagnostics, 3144P, or any HART device with a burst mode output |