Rosemount 3D39398G02 Pilot Valve
No product images are published for this product yet.
Purchase options
$494.87
- Availability
- Call for availability Originalx
Independent supplier
Sproh is an independent supplier and is not an authorized distributor or official representative of Rosemount or Emerson.
Overview
Pilot valve assembly for Hagan pneumatic power positioners, 3-15 psi signal, supplied without stem, built in groups G01 to G04.
Key features
- Pilot valve assembly for Hagan pneumatic power positioners, supplied without stem, 3-15 psi signal
- Converts a small control signal into supply air flow to one side of the drive cylinder and vents the other
- Built in four groups G01 to G04: G01/G02 with top loading spring, G03/G04 with the taller cover and EPT retainer
- Valve body 3039396H02; diaphragms 171323 and 170960; seats, centre post and block, sleeve retainer and boot
- Wear parts are the diaphragms and seats, so a rebuild is a kit of items rather than a whole positioner
- Confirm the group code against the top cover and retainer already fitted before ordering
Key specifications
- Accuracy
- The pilot valve is the element that sets the positioner's repeatability in service: worn diaphragms and seats show up as hunting, overshoot on small signal changes and continuous air at the vent
- Output signal
- Pneumatic output to the drive cylinder, one side pressurised and the other vented, following the 3-15 psi input and the feedback from the drive arm
- Diagnostics
- Repair is by diaphragm and seat replacement: valve body 3039396H02, diaphragms 171323 and 170960, top and bottom diaphragm seats, bottom stem seat, centre post and block, sleeve retainer and boot are all listed separately
- Pressure range
- 3-15 psi control signal; the valve passes the positioner's supply air, which for the Hagan family is 45 to 120 psig with 100 psig recommended
- Variants
- Four build groups: G01 and G02 with the top loading spring and two 1/4-20 x 1.25 socket head cap screws; G03 and G04 with the taller top diaphragm cover, top spring retainer and a different screw set for electronic position transmitter arrangements
- Application
- Pilot valve inside a Hagan pneumatic power positioner: compares the control signal against drive feedback and ports supply air to one side of the cylinder while venting the other
The relay that actually ports the air on a Hagan positioner
This is the pilot valve assembly for the Hagan pneumatic power positioners — part 3D39398G02, supplied without stem, for a 3-15 psi signal. It is the piece that turns a small pressure signal into a large flow of supply air to one side of the drive cylinder, so it is the component that fails first on a positioner that has been in service for years: the diaphragms harden, the seats erode, and the drive starts hunting or drifting.
What it does in the loop
The positioner compares the incoming 3-15 psi control signal against feedback from the drive arm. The difference is applied to the pilot valve's diaphragms, which move a stem that opens one seat and closes the other, admitting supply air to one side of the piston and venting the opposite side. Nothing else in the positioner moves the drive — which is why a worn pilot valve shows up as poor repeatability, overshoot at small signal changes, and air leaking continuously at the vent.
Build groups
The assembly is built in four configurations. G01 and G02 carry the top loading spring and the two 1/4-20 socket head cap screws that go with it; G03 and G04 use the taller top diaphragm cover with the retainer for the top spring and a different screw set, the arrangement used with an electronic position transmitter. The signal label differs between the pairs as well (1A98542H02 on G01/G03, 1A98542H01 on G02/G04), which is how the factory marks the signal range and action on the cover.
What is inside
The assembly is built on valve body 3039396H02 with two diaphragms (171323 and 170960), bottom and top diaphragm seats, a bottom stem seat, a centre post and centre block, a sleeve retainer, a boot, and the loading springs. Those are the parts that wear: the valve body and the covers normally survive, the diaphragms and seats do not. Because the parts list is documented, a rebuild is a matter of ordering the diaphragm and seat items rather than replacing the whole positioner.
Ordering note
This listing is the assembly without stem. The stem is a separate item on the Hagan positioner, so check what is in the existing unit before ordering — a valve supplied without a stem will not repair a positioner whose stem is worn or bent. The four build groups are not interchangeable without checking the top cover and retainer arrangement, and mixing a G01/G02 body with G03/G04 covers leaves the top spring unsupported.
Where it fits
Hagan pneumatic power positioners in boiler and fan damper service: the pilot valve sits inside the positioner housing and is replaced as part of a rebuild. It is a service part rather than a system component, and it is normally ordered when a positioner is overhauled, not when a new drive is specified. Confirm the frame and the cover arrangement against the drive's own parts list before ordering, because the group code on this assembly has to match the cover and retainer that are already fitted.
Manufacturer reference: Rosemount Analytical pilot valve parts list, assembly 3D39398G02 groups G01 to G04.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | The pilot valve is the element that sets the positioner's repeatability in service: worn diaphragms and seats show up as hunting, overshoot on small signal changes and continuous air at the vent |
| Output signal | Pneumatic output to the drive cylinder, one side pressurised and the other vented, following the 3-15 psi input and the feedback from the drive arm |
| Diagnostics | Repair is by diaphragm and seat replacement: valve body 3039396H02, diaphragms 171323 and 170960, top and bottom diaphragm seats, bottom stem seat, centre post and block, sleeve retainer and boot are all listed separately |
| Pressure range | 3-15 psi control signal; the valve passes the positioner's supply air, which for the Hagan family is 45 to 120 psig with 100 psig recommended |
| Variants | Four build groups: G01 and G02 with the top loading spring and two 1/4-20 x 1.25 socket head cap screws; G03 and G04 with the taller top diaphragm cover, top spring retainer and a different screw set for electronic position transmitter arrangements |
| Application | Pilot valve inside a Hagan pneumatic power positioner: compares the control signal against drive feedback and ports supply air to one side of the cylinder while venting the other |
| Mounting | Fitted inside the positioner housing; this listing is the assembly WITHOUT stem, and the stem is a separate item, so the existing unit must be checked before ordering |
| Operating temperature (°C) | Rated with the host positioner, 0 to 140 F (-18 to 60 C) across the Hagan pneumatic drives, with 160 F (71 C) permitted under increased maintenance |
Accessories and related items
Accessories and related items for this product are not available to order on Sproh yet. If the manufacturer lists them, an engineer can source them for you.
Ask an engineer