Overview
Pilot valve assembly for Hagan pneumatic power positioners, 0-30 psi signal, supplied without stem, G03 group.
Key features
- Pilot valve assembly for Hagan pneumatic power positioners, supplied without stem, 0-30 psi signal
- Wider signal span version of the same relay; the range must match the controller or I/P that drives the positioner
- G03 group: taller top diaphragm cover, top spring retainer for EPT arrangements and the matching screw set
- Valve body 3039396H02; diaphragms 171323 and 170960; seats, centre post and block, sleeve retainer and boot
- Wear parts are the diaphragms and seats, so a rebuild is a set of items rather than a whole positioner
- Supplied without stem - the stem is a separate item and must be inspected on the existing unit
Key specifications
- Accuracy
- The valve sets the positioner's repeatability in service; a worn unit shows as hunting, overshoot on small signal changes and continuous air at the vent
- Output signal
- Pneumatic output to the drive cylinder, one side pressurised and the other vented, following the 0-30 psi input and the feedback from the drive arm
- Diagnostics
- Repair by diaphragm and seat replacement: valve body 3039396H02, diaphragms 171323 and 170960, top and bottom diaphragm seats, bottom stem seat, centre post and block, sleeve retainer and boot listed separately
- Pressure range
- 0-30 psi control signal; the valve passes the positioner's supply air, which for the Hagan family is 45 to 120 psig with 100 psig recommended
- Variants
- G03 group: taller top diaphragm cover, top spring retainer for electronic position transmitter arrangements and the matching screw set; the G01/G02 build uses the short cover with the top loading spring instead
- Application
- Pilot valve inside a Hagan pneumatic power positioner on a 0-30 psi signal branch: compares the control signal against drive feedback and ports supply air to one side of the cylinder while venting the other
The 0-30 psi version of the Hagan pilot valve
This is pilot valve assembly 3D39398G03 for the Hagan pneumatic power positioners, supplied without stem, built for a 0-30 psi control signal rather than the 3-15 psi of the G02 part. It is the same relay inside the positioner — the diaphragm stack that compares signal against feedback and ports supply air to one side of the drive cylinder — with the signal range and the springing that go with the wider span.
When the 0-30 psi version is the right one
The signal range is not a preference, it belongs to the control system that drives the positioner. A 0-30 psi branch is used where the pneumatic controller or the I/P converter outputs a wider span, and fitting a 3-15 psi assembly into that branch gives a drive that is at full travel by half the signal. The reverse mistake is worse: a 0-30 psi assembly on a 3-15 psi signal never reaches the ends of its stroke, so the damper is throttled short of open and short of closed and the operator finds a limit that no amount of calibration removes. The part number on the existing unit is the thing to read before ordering.
What is inside the assembly
The build is on valve body 3039396H02 with diaphragms 171323 and 170960, top and bottom diaphragm seats, a bottom stem seat, a centre post and centre block, a sleeve retainer, a boot and the loading springs. These are the wear items: the body and covers survive, the elastomer and the seats do not; a rebuilt positioner usually needs the diaphragms and seats rather than a new valve.
Group note
This is the G03 group, which carries the taller top diaphragm cover, the top spring retainer for electronic position transmitter arrangements, and the corresponding screw set. The signal label 1A98542H02 marks the range on the cover. Because the cover and retainer differ from the G01/G02 build, a G03 assembly does not drop into a positioner whose top cover is the short type without the matching parts.
Supplied without stem
The listing is the assembly without stem. The stem is a separate item on the Hagan positioner, so an existing unit must be inspected first: a valve without a stem cannot repair a positioner whose stem is worn or bent, and a stem that is reused with new diaphragms is often the source of the last few percent of drift the rebuild was meant to remove.
Where it fits
Inside the positioner housing of Hagan pneumatic drives in boiler and fan damper service, on branches that run a 0-30 psi signal. It is a service part: ordered when a positioner is overhauled, not when a drive is specified.
Manufacturer reference: Rosemount Analytical pilot valve parts list, assembly 3D39398G03, group G03.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | The valve sets the positioner's repeatability in service; a worn unit shows as hunting, overshoot on small signal changes and continuous air at the vent |
| Output signal | Pneumatic output to the drive cylinder, one side pressurised and the other vented, following the 0-30 psi input and the feedback from the drive arm |
| Diagnostics | Repair by diaphragm and seat replacement: valve body 3039396H02, diaphragms 171323 and 170960, top and bottom diaphragm seats, bottom stem seat, centre post and block, sleeve retainer and boot listed separately |
| Pressure range | 0-30 psi control signal; the valve passes the positioner's supply air, which for the Hagan family is 45 to 120 psig with 100 psig recommended |
| Variants | G03 group: taller top diaphragm cover, top spring retainer for electronic position transmitter arrangements and the matching screw set; the G01/G02 build uses the short cover with the top loading spring instead |
| Application | Pilot valve inside a Hagan pneumatic power positioner on a 0-30 psi signal branch: compares the control signal against drive feedback and ports supply air to one side of the cylinder while venting the other |
| Mounting | Fitted inside the positioner housing; the listing is the assembly WITHOUT stem, so the existing stem must be inspected before ordering |
| Operating temperature (°C) | Rated with the host positioner, 0 to 140 F (-18 to 60 C) across the Hagan pneumatic drives, with 160 F (71 C) permitted under increased maintenance |