Overview
Integral orifice flow meter with plate, manifold and transmitter in one body: no impulse lines, 0.8 percent flow accuracy at 14:1 turndown.
Key features
- Integral orifice flow meter: orifice plate, manifold and 4051S differential pressure transmitter assembled in one body, configured at the factory for the application and reporting flow directly on the display
- There are no impulse lines, so the failure mode of a plugged, frozen or wrongly filled leg cannot happen - the differential is taken inside the body a few centimetres from the diaphragms
- Because the body is rigid, orientation becomes the installation: gas in a horizontal pipe mounts above it so condensate runs back, liquid or steam mounts below so gas bubbles rise away, vertical liquid must flow up and vertical gas must flow down
- Vertical liquid flowing down and vertical gas flowing up cannot use direct mount at all and require a remote mounted transmitter, which is a model code decision rather than a site instruction
- Direct mount is specified from -40 to 450 F (-40 to 232 C); above that the transmitter moves off the body onto a remote mount with the adapter giving 2, 2-1/8 or 2-1/4 in connection centres on the 1/2 in NPT ports
- Straight lengths are multiples of the pipe inside diameter measured from the upstream face of the orifice plate, not from the flange, and sizing depends on the true pipe inside diameter. A three or five valve manifold is required for direct mounting
Key specifications
- Accuracy
- Ultra-For-Flow 0.8 percent flow rate accuracy with 14:1 flow turndown, or 28:1 with the universal pressure range option. Classic 1.25 percent flow rate at 8:1. Because flow follows the square root of differential pressure, a 14:1 flow turndown is a 196:1 turndown of differential
- Output signal
- 4-20 mA with HART and Bluetooth on the 4051S platform, configured at the factory for the application and reporting volumetric flow, mass flow or totalized flow directly on the display. Two integral relay switches available
- Diagnostics
- The integral body removes the failure mode of a plugged, frozen or wrongly filled impulse line, because there are no legs - the differential is taken inside the body a few centimetres from the diaphragms. What replaces it is an orientation constraint that cannot be corrected after installation by re-routing anything, only by remote mounting the transmitter. A pipeline that has been re-rated or lined also changes the true inside diameter the plate was sized for, which shows up as a flow reading consistently a few percent off that no calibration removes
- Pressure range
- Set by the 4051S sensor module range code and the body and connection ratings. Direct mounting is specified over -40 to 450 F (-40 to 232 C); above that the transmitter must be remote mounted
- Application
- Flow measurement on small lines where a full orifice run would be disproportionate and the line is too small for an insertion probe: utilities, chemical dosing, steam to a small user, cooling water to a single machine and gas to a burner
- Mounting
- The body is rigid, so orientation is the installation: gas in a horizontal pipe mounts above it within a 90 degree zone so condensate runs back into the line, liquid or steam mounts below it so gas bubbles rise away, vertical liquid is only acceptable with flow upward, and vertical gas only with flow downward. Vertical steam must be remote mounted, and a three or five valve manifold is required when the transmitter is direct mounted
The integral body removes the impulse lines and replaces them with an orientation rule
The Rosemount 4051SFP is an integral orifice flow meter: an orifice plate, a manifold and a 4051S differential pressure transmitter assembled into one body, ordered by fluid type and line size and configured at the factory for the application. Performance is the family's two classes — Ultra-For-Flow at 0.8 % flow rate accuracy with 14:1 flow turndown (28:1 with the universal range option), or Classic at 1.25 % and 8:1 — and the local display reports flow directly, in the units the application was configured for.
Its virtue is the absence of something. On a conventional orifice installation the transmitter stands off from the pipe on two impulse lines, and those lines are the part that plugs, freezes, fills with the wrong phase, or leaks. An integral orifice has none: the differential is taken inside the body, between the taps either side of the plate, a few centimetres from the diaphragms.
That closes one failure mode and opens another, and the other one is harder to fix after the fact.
What orientation decides
The body is rigid. You cannot re-route a leg to keep condensate away from a diaphragm, because there are no legs. What you can do is mount the whole assembly so the phase that would collect cannot land on the sensing diaphragms — and the manufacturer's rules are one sentence applied four times.
| Installation | Rule | Because |
|---|---|---|
| Gas, horizontal pipe | Mount above the pipe, within a 90° zone | Condensate runs back into the line instead of collecting on the diaphragms |
| Liquid or steam, horizontal pipe | Mount below the pipe | Gas bubbles rise away instead of collecting on the diaphragms |
| Liquid, vertical pipe | Only with flow upward | Downward flow cannot be vented; vertical steam must be remote mounted |
| Gas, vertical pipe | Only with flow downward | Drain vent orientation; flowing up traps condensate with no way out |
Two of those rules are prohibitions, and they are the ones that get discovered late. A vertical liquid line flowing down cannot use a direct-mounted integral orifice at all; a vertical gas line flowing up cannot either. In both cases the answer is a remote-mounted transmitter — the body stays on the pipe and the transmitter moves to where the legs can be arranged correctly. That decision changes the model code, so it belongs in the specification and not in a site instruction.
Temperature is the other limit on direct mounting
Direct mounting is specified over −40 to 450 °F (−40 to 232 °C). Beyond that, the electronics are sitting too close to the process and the transmitter moves off the body onto a remote mount — with the adapter that gives 2, 2⅛ or 2¼ in connection centres on the ½ in NPT ports.
So the two reasons to go remote are orientation and temperature, and both are decided by the application rather than by preference. Worth checking both before the order is placed, because retrofitting a remote mount to a direct-mounted meter means new parts and a shutdown.
Straight run, measured from the plate
The installation requires straight lengths upstream and downstream expressed as multiples of the pipe inside diameter, measured from the upstream face of the orifice plate. That last clause is the one that catches installers: the requirement is measured from the plate, not from the flange or from where the meter body happens to end, so a layout drawn to the flange face can be short by the depth of the body.
And a detail worth keeping from the manual: the sizing depends on the true pipe inside diameter. A line that has been re-rated, lined, or is simply not the schedule the drawing says will size the plate for a pipe that is not there — which shows up as a flow reading that is consistently a few percent off and cannot be calibrated away.
A manifold is not optional
When a transmitter is direct mounted to the integral orifice body, the manual is explicit: always use a three- or five-valve manifold. The block valves isolate the transmitter from the process, the equaliser allows the transmitter to be zeroed at line pressure, and without them there is no way to service or verify the instrument on a live line.
It is also the reason the assembly is honest about what it is: a flow meter that can be isolated, vented and zeroed in place, without breaking a process joint.
The trade against an averaging pitot
An integral orifice and an Annubar sit at opposite ends of the same compromise. The orifice creates a larger permanent pressure loss — it is a full-bore restriction — and in exchange it develops a strong, well-understood differential in a small line. The averaging pitot creates much less loss and suits large lines, but in a 1 in pipe there is barely room for the probe.
So the selection question is the pipe: small line, integral orifice; large line, averaging pitot. Choosing an orifice meter on a 24 in main gives away energy every hour; choosing a pitot on a 1 in line is a mechanical problem before it is a measurement one.
Where it fits
Flow measurement on small lines — utilities, chemical dosing, steam to a small user, cooling water to a single machine, gas to a burner — where a full orifice run would be disproportionate and the line is too small for an insertion probe. Add the straight run to the layout, decide mount orientation and temperature against the tables above, specify the manifold, and keep the pipe's true inside diameter with the instrument record for the next time the plate is sized.
Manufacturer reference: Rosemount Integral Orifice Flow Meter Series Reference Manual 00809-0100-4686 for installation orientation by fluid and pipe direction, straight-length requirements, manifold requirements and remote mount adapters, with the 4051S DP flow meter data sheet for performance classes.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | Ultra-For-Flow 0.8 percent flow rate accuracy with 14:1 flow turndown, or 28:1 with the universal pressure range option. Classic 1.25 percent flow rate at 8:1. Because flow follows the square root of differential pressure, a 14:1 flow turndown is a 196:1 turndown of differential |
| Output signal | 4-20 mA with HART and Bluetooth on the 4051S platform, configured at the factory for the application and reporting volumetric flow, mass flow or totalized flow directly on the display. Two integral relay switches available |
| Diagnostics | The integral body removes the failure mode of a plugged, frozen or wrongly filled impulse line, because there are no legs - the differential is taken inside the body a few centimetres from the diaphragms. What replaces it is an orientation constraint that cannot be corrected after installation by re-routing anything, only by remote mounting the transmitter. A pipeline that has been re-rated or lined also changes the true inside diameter the plate was sized for, which shows up as a flow reading consistently a few percent off that no calibration removes |
| Pressure range | Set by the 4051S sensor module range code and the body and connection ratings. Direct mounting is specified over -40 to 450 F (-40 to 232 C); above that the transmitter must be remote mounted |
| Application | Flow measurement on small lines where a full orifice run would be disproportionate and the line is too small for an insertion probe: utilities, chemical dosing, steam to a small user, cooling water to a single machine and gas to a burner |
| Mounting | The body is rigid, so orientation is the installation: gas in a horizontal pipe mounts above it within a 90 degree zone so condensate runs back into the line, liquid or steam mounts below it so gas bubbles rise away, vertical liquid is only acceptable with flow upward, and vertical gas only with flow downward. Vertical steam must be remote mounted, and a three or five valve manifold is required when the transmitter is direct mounted |
| Operating temperature (°C) | Direct mount from -40 to 450 F (-40 to 232 C). Beyond that the transmitter moves off the body to a remote mount, using the adapter that gives 2, 2-1/8 or 2-1/4 in (51, 54 or 57 mm) connection centres on the 1/2 in NPT ports |
| Measuring range | Line sizes and the orifice bore are selected from the application during sizing, which depends on the true pipe inside diameter. Straight lengths upstream and downstream are expressed as multiples of that inside diameter and measured from the upstream face of the orifice plate, not from the flange - a layout drawn to the flange face can be short by the depth of the body |