Overview
In-line pressure transmitter with no impulse lines, 0.025 percent span Ultra accuracy, 20-year stability and a 40 ms response option.
Key features
- In-line pressure transmitter with the sensor module at the process connection, so there are no impulse lines, no taps and no manifold
- Removing the impulse lines removes a class of slow failures: plugged taps that lag instead of failing, frozen or steam-traced legs, leg density error from two legs at different temperatures, and every bolted joint in a manifold as a leak point
- Ultra class reference accuracy is 0.025 percent of span, and below ten to one it becomes a pure ratio, 0.004 x URL/Span percent of span, with no fixed term: 0.04 percent at 10:1, 0.4 percent at 100:1 and 0.8 percent at 200:1
- Range 5 in the same table is quoted as 0.004 percent of URL, which does not degrade with span at all because the denominator is not the span - two adjacent lines with two different denominators
- With one process connection there is no differential, so flow across an orifice, level by hydrostatic head and filter monitoring cannot be done by this version; those need the Coplanar module
- Overpressure limit, not static pressure effect, is the relevant secondary limit on an in-line transmitter, and it is set by the sensor rating or by whichever is lower with the flange rating. The local display shows process pressure and module temperature together
Key specifications
- Accuracy
- Ultra 0.025 percent of span on ranges 1 to 4; below a ten to one span it becomes a pure ratio of 0.004 x (URL/Span) percent of span, with no fixed term: 0.04 percent at 10:1, 0.4 percent at 100:1 and 0.8 percent at 200:1. Range 5 Ultra is 0.04 percent of span, and below 10:1 it is 0.004 percent of URL - a different denominator that does not degrade with span at all
- Output signal
- 4-20 mA with HART digital signal and Bluetooth connectivity for configuration and service in hazardous locations, configurable for pressure, level, volume, flow or totalized flow in the device
- Diagnostics
- The in-line module removes the failure modes that belong to impulse lines: a tap that fouls and lags instead of failing, a water-filled leg that freezes when its heat trace fails, two vertical legs at different temperatures exerting different heads, and every bolted joint in a manifold as a potential weep. What is left is the sensor, the seal at the process connection, and the electronics
- Pressure range
- Ranges 1 through 5 in gauge (4051S_TG) and absolute (4051S_TA) variants, with 200:1 rangedown in the Ultra class. Overpressure limit is set by the sensor rating, and on flanged versions by whichever is lower between the flange rating and the sensor rating - check it against the real process, including water hammer, not just the normal operating pressure
- Application
- Gauge and absolute pressure on process and utility lines, steam headers, vacuum service and compressor discharge, where the pipe already has a threaded or flanged connection to mount into. Not for flow, level or filter monitoring, which are differential measurements and need the Coplanar module
- Operating temperature (°C)
- Set by the sensor module and fill fluid selected. The local display shows the process pressure and the module temperature beneath it, which is a diagnostic in its own right: a module running far above ambient is one sitting on a hot line, and temperature effect on the reading is then a known quantity rather than a suspicion
Deleting the impulse lines deletes a class of failure — and costs you the differential
The Rosemount 4051ST is the in-line member of the 4051S family: the sensor module sits directly at the process connection, under the same blue electronics housing, with the same 0.025 % of span Ultra class, 20-year stability, Bluetooth configuration and 40 ms time response option as the Coplanar version.
What separates it is what is not there. A Coplanar transmitter measures a difference, so it needs two pressure paths: two taps, two lengths of impulse line, a manifold, and the discipline to keep all of it right. An in-line transmitter measures one pressure at the point where it is screwed into the process. There are no legs to plug, freeze, steam-trace, vent, or fill.
What disappears with the impulse lines
The failures that go away are specific, and most of them are slow rather than sudden:
Plugged taps. A tap that partially blocks still transmits pressure, just more slowly and with a lag that grows as it fouls. The reading stays plausible while the loop's response quietly deteriorates.
Frozen and traced legs. A water-filled leg in winter is a maintenance route with a heat trace and an insulation jacket, and if the trace fails the leg freezes and the transmitter reads the wrong number until someone notices the weather.
Leg density error. Two vertical legs filled with liquid at different temperatures exert different heads. The transmitter faithfully measures the difference between the pressures it receives, which is not the difference the process has.
The manifold as a leak point. Every joint in a bolted manifold is a place a fitter has to tighten correctly, and on a steam or hydrocarbon line a weep at a manifold is a reportable event.
Removing all of that is a real reliability gain, and it is why in-line transmitters are the default on straightforward pressure measurement.
The accuracy table is not the Coplanar one
This is where the in-line version deserves its own reading rather than a reference to its sibling. For in-line absolute and gauge ranges 1 to 4 in the Ultra class the reference accuracy is ±0.025 % of span, and below a ten-to-one span it becomes:
±(0.004 × [URL / Span]) % of span
Note what is missing compared with the Coplanar differential table: there is no fixed term. The Coplanar equation carries a 0.005 constant that limits how far the number can improve at shallow spans; the in-line equation is a pure ratio. Worked out, it gives 0.04 % at 10:1, 0.4 % at 100:1 and 0.8 % at 200:1 — a cleaner curve, and a steeper one at the far end.
Then the same table changes units for Range 5: Ultra is ±0.04 % of span, and for spans below 10:1 it is ±0.004 % of URL. That is not a typo, and it matters: a specification expressed as a percentage of the upper range limit does not degrade as the span is reduced, because it is not a percentage of the span at all. Two adjacent lines, two different denominators — and one of them is immune to turndown.
So the honest summary for this transmitter is: 0.025 % at spans down to a tenth of the range, then a ratio that reaches 0.8 % of span at the full 200:1, with one range code that behaves differently because its tolerance is quoted against the URL.
What the in-line version cannot do
With one process connection there is no second pressure, so there is no differential. That rules out the three things differential pressure is most often bought for:
Flow across an orifice, venturi or averaging pitot — all of them are differential devices. Level by hydrostatic head, which needs the difference between the head pressure and the vessel's vapour space. Filter and strainer monitoring, which is differential by definition.
If the application is any of those, the Coplanar version is the correct instrument and this one cannot substitute, however much simpler its installation looks. The selection question is not "which is better" but "is the measurement a pressure, or a difference between two pressures".
Overpressure is the limit that matters here
On a differential transmitter the interesting secondary effect is static pressure, which shifts the zero while the process is running normally. On an in-line transmitter the process pressure is the measurement, so the number that matters is the overpressure limit — how far past the sensor's range the process can go before the module is damaged. That limit is set by the sensor rating, and on flanged versions by whichever is lower, the flange rating or the sensor rating.
Worth checking against the real process rather than the normal operating pressure: a line that normally runs at 10 bar and occasionally sees a 40 bar water hammer is a line where the overpressure limit is the specification, not the range.
What the local display is telling you
On this version the display shows the process pressure and, beneath it, the module temperature — the sensor's own view of how hot it is. That is a diagnostic in its own right: a module running far above ambient is a module sitting on a hot line, and the temperature effect on the reading is one of the things a technician can check without a laptop.
Where it fits
Gauge and absolute pressure on process and utility lines, steam headers, vacuum service, compressor discharge and anywhere the pipe already has a threaded or flanged connection to screw into. Choose it for pressure; choose the Coplanar when the measurement is a difference. Take the 40 ms option only where the pressure is the event rather than a condition, and take the 20-year stability claim as what it is — an argument for a longer calibration interval, not for skipping the first verification.
Manufacturer reference: Rosemount 4051S Pressure Transmitter Product Data Sheet, in-line sensor module section, for reference accuracy by range and class, overpressure limits, response options and ordering codes.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | Ultra 0.025 percent of span on ranges 1 to 4; below a ten to one span it becomes a pure ratio of 0.004 x (URL/Span) percent of span, with no fixed term: 0.04 percent at 10:1, 0.4 percent at 100:1 and 0.8 percent at 200:1. Range 5 Ultra is 0.04 percent of span, and below 10:1 it is 0.004 percent of URL - a different denominator that does not degrade with span at all |
| Output signal | 4-20 mA with HART digital signal and Bluetooth connectivity for configuration and service in hazardous locations, configurable for pressure, level, volume, flow or totalized flow in the device |
| Diagnostics | The in-line module removes the failure modes that belong to impulse lines: a tap that fouls and lags instead of failing, a water-filled leg that freezes when its heat trace fails, two vertical legs at different temperatures exerting different heads, and every bolted joint in a manifold as a potential weep. What is left is the sensor, the seal at the process connection, and the electronics |
| Pressure range | Ranges 1 through 5 in gauge (4051S_TG) and absolute (4051S_TA) variants, with 200:1 rangedown in the Ultra class. Overpressure limit is set by the sensor rating, and on flanged versions by whichever is lower between the flange rating and the sensor rating - check it against the real process, including water hammer, not just the normal operating pressure |
| Application | Gauge and absolute pressure on process and utility lines, steam headers, vacuum service and compressor discharge, where the pipe already has a threaded or flanged connection to mount into. Not for flow, level or filter monitoring, which are differential measurements and need the Coplanar module |
| Operating temperature (°C) | Set by the sensor module and fill fluid selected. The local display shows the process pressure and the module temperature beneath it, which is a diagnostic in its own right: a module running far above ambient is one sitting on a hot line, and temperature effect on the reading is then a known quantity rather than a suspicion |
| Response time | Standard update rate for normal process loops, with a 40 ms time response option for compressor surge, hydraulic transients and test stands - loops where the pressure is the event rather than a condition |
| Stability | 20-year stability with a matching twenty-year limited warranty. On an in-line transmitter the secondary limit that matters is overpressure rather than static pressure effect, because the process pressure is the measurement itself and there is no second port whose static pressure could shift a zero |