Rosemount 5408 Radar Level Transmitter
Purchase options
From$1,910.78
- Availability
- Call for availability Originalx
Configurable — choose options to build the exact part number.
Independent supplier
Sproh is an independent supplier and is not an authorized distributor or official representative of Rosemount or Emerson.
Overview
Two-wire FMCW radar level transmitter with a PTFE seal that needs no O-ring: +/-1 mm accuracy, range to 40 m or 150 m extended, HART or Fieldbus.
Key features
- Two-wire FMCW non-contacting radar level transmitter for liquids and solids, with a PTFE process seal that requires no O-ring
- Reference accuracy +/-0.04 in. (+/-1 mm) in the ultra accuracy performance class
- Maximum measuring range 130 ft. (40 m), extended to 492 ft. (150 m) with the extended range option
- Cone antenna options trade pressure against temperature: CAC reaches 1450 psig at 100 C, CAD reaches 250 C but only 44 psig
- Smart Echo Supervision separates the product echo from agitator blades, welds and antenna build-up
- Smart Diagnostics Suite gives early alerts for antenna build-up and weak power supply, on a 4-20 mA HART or FOUNDATION Fieldbus loop
Key specifications
- Accuracy
- Reference accuracy +/-0.04 in. (+/-1 mm) in the ultra accuracy performance class. Maximum measuring range 130 ft. (40 m), extended to 492 ft. (150 m) with the extended range option ER
- Output signal
- Two-wire 4-20 mA with HART communication (HART 7 from factory, HART 6 with option HR6) or FOUNDATION Fieldbus; minimum lift-off voltage 12 Vdc on HART and 9 Vdc on Fieldbus
- Diagnostics
- Smart Echo Supervision separates the product echo from agitator blades, tank welds and antenna build-up; the Smart Diagnostics Suite raises early alerts for antenna build-up and weak power supply before the measurement stops
- Pressure range
- Set by the antenna option: CAA to 363 psig (25 bar), CAB to 725 psig (50 bar), CAC to 1450 psig (100 bar), CAD to 44 psig (3 bar), CBF (PEEK seal, FVMQ) to 754 psig (52 bar). For applications where saturated steam may occur, Emerson asks for factory consultation
- Variants
- Cone antennas (CAA, CAB, CAC, CAD) with a PTFE process seal that needs no O-ring, plus a PEEK seal option (CBF) and process seal antennas; antenna and process connection in 316L, Alloy C-276, Alloy 400 and other wetted materials; extended range option ER for 150 m
- Application
- Non-contacting level measurement of liquids and solids in buffer and storage tanks, reactor and mixing vessels with agitation, solids silos and hoppers, and aggressive or high purity service where a contacting probe would foul
Radar level without the O-ring
The Rosemount 5408 is a two-wire FMCW radar level transmitter for non-contacting measurement of liquids and solids. Its headline feature is not the accuracy figure or the range — it is the PTFE process seal that requires no O-ring. That sounds like a detail until you have maintained a radar on a tank where the O-ring was the part that failed, the part that had to be matched to the fluid, and the part that decided how often the instrument came off the nozzle.
Why removing the O-ring is the whole idea
An O-ring is an elastomer in contact with the process, held in compression, and it is the one component in a radar that ages. It swells or hardens depending on what the tank contains, it takes a compression set every time the instrument is removed and refitted, and on a vessel with emission rules it is a potential leak path that has to be managed rather than designed out. The 5408's PTFE seal closes the process boundary with a material that is chemically inert across a very wide range and does not depend on an elastomer to work. The practical result is fewer part numbers to stock, fewer material-compatibility questions at the specification stage, and a seal that does not decide the maintenance interval.
The table that decides the antenna, and the trade inside it
Cone antenna options carry their own pressure and temperature envelope, and the numbers are worth reading as a set because they trade against each other:
- CAA — up to 363 psig (25 bar), -76 to 392 °F (-60 to 200 °C)
- CAB — up to 725 psig (50 bar), -40 to 302 °F (-40 to 150 °C)
- CAC — up to 1450 psig (100 bar), -40 to 212 °F (-40 to 100 °C)
- CAD — up to 44 psig (3 bar), -76 to 482 °F (-60 to 250 °C)
- CBF — PEEK seal with FVMQ, up to 754 psig (52 bar), -76 to 338 °F (-60 to 170 °C)
The pattern is the point: the highest pressure option is limited to the lowest temperature, and the highest temperature option (CAD) holds only 3 bar. A process that is both hot and pressurised is not covered by any single cone option, and the answer is a different antenna or a different technology — not a relaxed reading of the table. Where saturated steam may occur, Emerson asks for factory consultation rather than a selection.
Range and accuracy
Maximum measuring range is 130 ft (40 m), extended to 492 ft (150 m) with the extended range option. Reference accuracy is ±0.04 in (±1 mm) in the ultra accuracy performance class. Those two figures belong to different questions: accuracy is what the instrument can resolve at a good reflection, and range is what it can reach when the reflection is poor. A low-dielectric product, foam, or a tank with internal structures reduces the usable range long before the nominal figure is reached — which is why Emerson publishes separate guidance for solids by dielectric constant rather than one number.
What keeps it reading
FMCW with Smart Echo Supervision is the signal processing that separates the product echo from the false ones — the agitator blade, the tank bottom weld, the build-up on the antenna. The Smart Diagnostics Suite adds early alerts for antenna build-up, weak power supply and other conditions that degrade a measurement before they stop it. On a tank that is never opened, an alert that says the antenna is coating is worth more than a specification that says the instrument is accurate.
Where it fits
Buffer and storage tanks, reactor and mixing vessels with agitation, solids silos and hoppers, and any tank where a non-contacting measurement avoids the fouling and cleaning problems of a contacting probe. The two-wire HART or FOUNDATION Fieldbus loop keeps it compatible with existing control systems, and the no-O-ring seal is what makes it practical on aggressive or high-purity service.
Manufacturer reference: Rosemount 5408 and 5408:SIS Level Transmitters Product Data Sheet 00813-0100-4408, antenna and process connection tables.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | Reference accuracy +/-0.04 in. (+/-1 mm) in the ultra accuracy performance class. Maximum measuring range 130 ft. (40 m), extended to 492 ft. (150 m) with the extended range option ER |
| Output signal | Two-wire 4-20 mA with HART communication (HART 7 from factory, HART 6 with option HR6) or FOUNDATION Fieldbus; minimum lift-off voltage 12 Vdc on HART and 9 Vdc on Fieldbus |
| Diagnostics | Smart Echo Supervision separates the product echo from agitator blades, tank welds and antenna build-up; the Smart Diagnostics Suite raises early alerts for antenna build-up and weak power supply before the measurement stops |
| Pressure range | Set by the antenna option: CAA to 363 psig (25 bar), CAB to 725 psig (50 bar), CAC to 1450 psig (100 bar), CAD to 44 psig (3 bar), CBF (PEEK seal, FVMQ) to 754 psig (52 bar). For applications where saturated steam may occur, Emerson asks for factory consultation |
| Variants | Cone antennas (CAA, CAB, CAC, CAD) with a PTFE process seal that needs no O-ring, plus a PEEK seal option (CBF) and process seal antennas; antenna and process connection in 316L, Alloy C-276, Alloy 400 and other wetted materials; extended range option ER for 150 m |
| Application | Non-contacting level measurement of liquids and solids in buffer and storage tanks, reactor and mixing vessels with agitation, solids silos and hoppers, and aggressive or high purity service where a contacting probe would foul |
| Mounting | Flanged or threaded process connection on a tank nozzle, cone antenna facing down into the vessel. The PTFE seal closes the process boundary without an elastomer O-ring, which removes the component that normally sets the maintenance interval |
| Operating temperature (°C) | Set by the antenna option: CAA -76 to 392 F (-60 to 200 C), CAB -40 to 302 F (-40 to 150 C), CAC -40 to 212 F (-40 to 100 C), CAD -76 to 482 F (-60 to 250 C), CBF -76 to 338 F (-60 to 170 C) |
Documents
Accessories and related items
Accessories and related items for this product are not available to order on Sproh yet. If the manufacturer lists them, an engineer can source them for you.
Ask an engineer