Overview
WirelessHART discrete transmitter: dual dry contacts measured continuously between updates, configurable input or output, and hydrocarbon leak detection with TraceTek cable.
Key features
- WirelessHART discrete transmitter for dry contacts, switch states and hydrocarbon leak detection
- Momentary inputs are continuously measured between wireless updates, so a two second event is not lost between hourly reports
- Code 32 dual dry contact input with counting, code 42 dual input or output configurable per channel, code 52 plunger arrival, code 61 liquid hydrocarbon detection
- Hydrocarbon detection uses TraceTek sensing cable, so the engineering is the cable route plus one transmitter rather than one device per leak point
- Antenna options include external (WK1), extended range (WM1), remote (WJ1) and high gain remote (WN1) for enclosures and pits
- Black 7.2 V SmartPower module, intrinsically safe and field replaceable, ships separately
Key specifications
- Accuracy
- Discrete, not analog: the reported value is a state. The functional equivalent of accuracy is that momentary inputs are continuously measured between wireless updates, so an event shorter than the update interval is still captured and counted
- Output signal
- WirelessHART (IEC 62591) at 2.4 GHz DSSS with user-configurable update rate. Code 32 is dual dry contact input with counting, code 42 is dual input or output configurable per channel, code 52 plunger arrival, code 61 liquid hydrocarbon detection
- Diagnostics
- With a discrete output configured, the loop depends on the radio link, so the output's state when the mesh is unreachable has to be decided in the control narrative before the device is ordered, not after it is wired
- Pressure range
- Not applicable - the transmitter is not in the pressure boundary; with the hydrocarbon option the sensing element is TraceTek cable laid where a leak would collect
- Variants
- Option codes 32, 42, 52 and 61 on the same 702 platform. Antenna options WK1 external, WM1 extended range, WJ1 remote and WN1 high gain remote, plus cable gland options. Black 7.2 V SmartPower module ships separately
- Application
- Pump and valve status on unwired skids, tank farm bund leak detection with TraceTek cable, plunger arrival on gas lift wells, and any dry contact that needs to reach the control system without a cable run
Discrete signals over a radio, including the ones that happen between updates
The Rosemount 702 is a WirelessHART transmitter for discrete signals: dry contacts, switch states, and — with the right sensing element — liquid hydrocarbon leaks. It is not a process transmitter; it does not convert a 4–20 mA loop or an RTD. It reads whether something is open or closed, and reports that over the mesh.
The problem a discrete wireless device normally has
A wireless transmitter that wakes up once a minute and reads its input at that moment will miss almost every event worth reporting. A pump start pulse, a valve proving switch, a level switch that closes for two seconds — all of it happens between reads, and the data that reaches the host is a series of calm snapshots of a process that is not calm. The 702's answer is in the data sheet and easy to skim past: momentary inputs are continuously measured between wireless updates. The radio is duty-cycled; the input is not. That is the difference between a device that reports the state of a plant and one that reports the state of a sample.
Four jobs behind one model number
The ordering codes are not variations on a theme, they are different functions:
- 32 — discrete dual input on dry contacts, detects momentary inputs and counts them
- 42 — dual input or output, each channel configurable
- 52 — plunger arrival detection, for use with the ETC Cyclops plunger arrival sensor
- 61 — liquid hydrocarbon detection, for use with TraceTek sensing cable
The distinction matters when someone specifies "a 702" without a code: counting dry contacts and detecting a hydrocarbon leak are different installations with different cabling, and only one of them is a leak detection system.
The output channel, and what it implies
With code 42, a channel can be a discrete output. A wireless device that can act is a different proposition from one that only reports: the loop now depends on the radio being up, and the consequence of a lost link has to be decided in advance — what state does the output hold when the mesh is unreachable, and is that state safe? That is a design question for the control narrative, not a configuration detail, and it belongs in the conversation before the device is ordered rather than after it is wired.
Leak detection is a system, not a switch
Option 61 is the one worth describing honestly. The 702 is the radio and the input; the sensing element is TraceTek cable, which is a length of cable that detects liquid hydrocarbon along its run — under a tank farm, in a bund, along a pipe trench. The transmitter reports what the cable detects. So the specification is not "one transmitter per leak point" but "a cable route plus one transmitter", and the engineering is in routing the cable where a leak would actually collect rather than where it is convenient to lay.
Radio, antenna and power
The radio is IEC 62591 (WirelessHART) at 2.4 GHz with a user-configurable update rate, and the antenna options are wider than on most of the family: an external antenna (WK1), extended range (WM1), a remote antenna (WJ1) and a high-gain remote antenna (WN1). The remote options exist for enclosures and pits where a radio inside a metal box hears nothing — a real constraint on tank farm installations. Power is the black 7.2 V SmartPower module, intrinsically safe and field replaceable, and it ships separately.
Where it fits
Pump and valve status on skids that were never wired, tank farm bund leak detection with TraceTek cable, plunger arrival on gas lift wells, and any contact that needs to appear in the control system without pulling a cable to it. It is also the device for a site that wants to know how often a safety shower, a door or a proving switch actually operates — because it counts.
Manufacturer reference: Rosemount 702 Wireless Discrete Transmitter Product Data Sheet 00813-0100-4702, ordering information and input options.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | Discrete, not analog: the reported value is a state. The functional equivalent of accuracy is that momentary inputs are continuously measured between wireless updates, so an event shorter than the update interval is still captured and counted |
| Output signal | WirelessHART (IEC 62591) at 2.4 GHz DSSS with user-configurable update rate. Code 32 is dual dry contact input with counting, code 42 is dual input or output configurable per channel, code 52 plunger arrival, code 61 liquid hydrocarbon detection |
| Diagnostics | With a discrete output configured, the loop depends on the radio link, so the output's state when the mesh is unreachable has to be decided in the control narrative before the device is ordered, not after it is wired |
| Pressure range | Not applicable - the transmitter is not in the pressure boundary; with the hydrocarbon option the sensing element is TraceTek cable laid where a leak would collect |
| Variants | Option codes 32, 42, 52 and 61 on the same 702 platform. Antenna options WK1 external, WM1 extended range, WJ1 remote and WN1 high gain remote, plus cable gland options. Black 7.2 V SmartPower module ships separately |
| Application | Pump and valve status on unwired skids, tank farm bund leak detection with TraceTek cable, plunger arrival on gas lift wells, and any dry contact that needs to reach the control system without a cable run |
| Mounting | Field-mounted transmitter with cable glands for the discrete wiring or the TraceTek cable. Remote antenna options exist because a radio inside a metal enclosure or a pit hears nothing - a real constraint on tank farm installations |
| Operating temperature (°C) | Ambient limits of the housing; the transmitter electronics sit in the field enclosure, and with option 61 the cable carries its own temperature limits along the route |
Documents
Accessories and related items
Accessories and related items for this product are not available to order on Sproh yet. If the manufacturer lists them, an engineer can source them for you.