Skip to main content
Sold and shipped by Sproh

Rosemount 702 Wireless Discrete Transmitter

Part number702ManufacturerEmerson

No product images are published for this product yet.

Purchase options

From$898.86

Availability
Call for availability Originalx
Select option

Configurable — choose options to build the exact part number.

Independent supplier

Sproh is an independent supplier and is not an authorized distributor or official representative of Rosemount or Emerson.

Overview

WirelessHART discrete transmitter: dual dry contacts measured continuously between updates, configurable input or output, and hydrocarbon leak detection with TraceTek cable.

Key features

  • WirelessHART discrete transmitter for dry contacts, switch states and hydrocarbon leak detection
  • Momentary inputs are continuously measured between wireless updates, so a two second event is not lost between hourly reports
  • Code 32 dual dry contact input with counting, code 42 dual input or output configurable per channel, code 52 plunger arrival, code 61 liquid hydrocarbon detection
  • Hydrocarbon detection uses TraceTek sensing cable, so the engineering is the cable route plus one transmitter rather than one device per leak point
  • Antenna options include external (WK1), extended range (WM1), remote (WJ1) and high gain remote (WN1) for enclosures and pits
  • Black 7.2 V SmartPower module, intrinsically safe and field replaceable, ships separately

Key specifications

Accuracy
Discrete, not analog: the reported value is a state. The functional equivalent of accuracy is that momentary inputs are continuously measured between wireless updates, so an event shorter than the update interval is still captured and counted
Output signal
WirelessHART (IEC 62591) at 2.4 GHz DSSS with user-configurable update rate. Code 32 is dual dry contact input with counting, code 42 is dual input or output configurable per channel, code 52 plunger arrival, code 61 liquid hydrocarbon detection
Diagnostics
With a discrete output configured, the loop depends on the radio link, so the output's state when the mesh is unreachable has to be decided in the control narrative before the device is ordered, not after it is wired
Pressure range
Not applicable - the transmitter is not in the pressure boundary; with the hydrocarbon option the sensing element is TraceTek cable laid where a leak would collect
Variants
Option codes 32, 42, 52 and 61 on the same 702 platform. Antenna options WK1 external, WM1 extended range, WJ1 remote and WN1 high gain remote, plus cable gland options. Black 7.2 V SmartPower module ships separately
Application
Pump and valve status on unwired skids, tank farm bund leak detection with TraceTek cable, plunger arrival on gas lift wells, and any dry contact that needs to reach the control system without a cable run
See all specifications