Rosemount 802 Wireless Multi-Channel Discrete I/O Transmitter
Purchase options
From$401.37
- Availability
- Call for availability Originalx
Configurable — choose options to build the exact part number.
Independent supplier
Sproh is an independent supplier and is not an authorized distributor or official representative of Rosemount or Emerson.
Overview
WirelessHART discrete I/O node: eight channels, input or output, with 10 ms momentary event capture and cycle counting on one radio.
Key features
- WirelessHART (IEC 62591) transmitter with eight discrete channels, each configurable as a discrete input or a discrete output, on one radio and one power module
- Momentary discrete inputs of 10 ms or more are detected and reported at the next wireless update as both current state and an accumulating close-open cycle count, so a brief trip is not missed between radio updates
- That same count turns a channel into a totaliser for a pulse output meter, valve strokes or compressor cycles
- Each channel has a PWR OUT terminal providing continuous voltage up to 2 Vdc below the supply feeding the node, which can remove a separate supply run to the field
- Discrete output switches up to 28 Vdc at 100 mA with about 1 ohm on resistance; inputs are SPST dry contacts limited to simple switches to keep the intrinsic safety rating
- Self-organizing mesh with more than 99 percent data reliability; WK antenna at 10 mW EIRP or the extended range WM antenna at 18 mW
Key specifications
- Accuracy
- Discrete input threshold: open above 100 kOhm, closed below 5 kOhm, suitable for SPST dry contacts. Momentary inputs of 10 ms or more are detected, with a close-open cycle count that rolls over at a configurable 1 to 1,000,000 (default 1,000,000)
- Output signal
- WirelessHART IEC 62591 at 2.4 GHz into a self-organizing mesh with more than 99 percent data reliability. Update rate user-selectable from 1 second to 60 minutes. Discrete outputs switch up to 28 Vdc at 100 mA with about 1 ohm on resistance
- Diagnostics
- The momentary input count is the diagnostic: it catches trips that happen between wireless updates and turns a switch into a totaliser. To keep the intrinsic safety rating the input contacts must be simple switches, with no powered circuitry on the far end
- Pressure range
- Not applicable - a field mounted wireless transmitter with no process connection and no wetted parts
- Variants
- Eight discrete channels, each configurable as discrete input or output, with a third PWR OUT terminal per channel. Antenna adapters WK7 and WM7 are offered for the black power module or for use with a 10 to 30 Vdc external supply
- Application
- Clusters of discrete signals away from the control system: tank farm high level switches, pump run and fault contacts, valve open and closed feedbacks, remote wellhead alarms, and pulse counting on meters with no other path to the historian
Eight channels on one radio, one power module and one wireless path
The Rosemount 802 is a WirelessHART (IEC 62591) transmitter with eight discrete channels, each configurable as a discrete input or a discrete output. It reports on a user-selectable update rate from 1 second to 60 minutes, and the SmartPower module provides up to seven years of maintenance-free operation.
The channel count is the product. A small tank farm, a pump station or a remote wellhead usually has a handful of level switches, valve position feedbacks and alarm contacts clustered in one place. Built one device at a time, each of those needs its own transmitter, its own radio, its own join to the gateway and its own battery to change. Built on an 802, they share all four.
The momentary input is what makes a wireless discrete input trustworthy
A wireless device wakes, measures, transmits and sleeps. That duty cycle is a trap for discrete signals: if a limit switch closes for 200 milliseconds between radio updates, a device that only samples at the update will report the plant as normal, and the trip is never seen.
The 802 addresses that directly. Momentary discrete inputs of 10 milliseconds or more are detected, and at each wireless update the device reports both the current discrete state and an accumulating count of close-open cycles, with a rollover value configurable from 1 to 1,000,000 (default one million).
Two capabilities come out of that sentence. The first is event capture: a brief trip is latched and reported rather than missed, which is the difference between a wireless I/O that can be trusted with an alarm and one that quietly reports the state it happened to catch. The second is counting: a channel is not only a state, it is a counter, so a pulse-output meter, a stroke counter on a valve or a cycle count on a compressor can be totalised on the same node that reads the switches.
Each channel can power its own field device
All eight channels carry a third PWR OUT terminal that outputs a continuous voltage up to 2 Vdc below the supply feeding the 802 — 28 Vdc into the transmitter appears as about 26 Vdc at the terminal. For a dry contact that needs a wetting voltage, that removes a separate supply run to the field, which on a remote installation is often the most expensive part of the job.
The input side is deliberately simple and deliberately limited: SPST dry contacts, with an open threshold above 100 kΩ and a closed threshold below 5 kΩ. To keep the intrinsic safety rating, the contacts must be simple switches — no powered circuitry on the far end. That constraint is the price of putting the node in a hazardous area, and it is worth designing the field wiring around it rather than discovering it at commissioning.
Outputs, and the supply they need
Where a channel is configured as an output it switches up to 28 Vdc at 100 mA with a typical on-resistance of 1 Ω — enough for a relay coil, a solenoid pilot or a small annunciator, not enough for a motor starter. The PWR OUT terminals track an external supply, so an installation that both reads switches and drives devices is planned around that external feed rather than around the battery alone.
The radio, and the two antennas
The transmitter uses a self-organizing WirelessHART mesh at 2.4 GHz with time-synchronised channel hopping, delivering the datasheet's figure of more than 99 percent data reliability. Two external antenna options change the reach: the WK antenna at a maximum of 10 mW (10 dBm) EIRP, and the extended-range WM antenna at 18 mW (12.5 dBm) EIRP.
Choose the antenna from the site survey, not from the data sheet's ambition. A node mounted low against a tank wall with a metal structure between it and the next hop needs the extended version; a node with a clear path to a gateway does not. And because the network is a mesh, the antenna decision is not only about reaching the gateway — it is about whether this node can also relay for others.
Two ordering facts that cost a return visit
First, the black power module ships separately and must be ordered as its own item (model 701PBKKF); it is intrinsically safe and is not included with the transmitter. Second, the antenna adapters (WK7 and WM7) are offered either for the black power module or for use with a 10–30 Vdc external supply, so the choice of how the node is powered has to be made before the model code is assembled.
Where it fits
Clusters of discrete signals away from the control system: tank farm high-level switches, pump run and fault contacts, valve open and closed feedbacks, remote wellhead alarms, and pulse counting on meters that have no other path to the historian. It is the right instrument where the cost of the cable, not the cost of the transmitter, is what has kept the points unwired.
Manufacturer reference: Rosemount 802 Wireless Multi-Channel Discrete I/O Transmitter Product Data Sheet 00813-0100-4082 for channel configuration, discrete input and output ratings, momentary input behaviour, antenna options and power module ordering.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | Discrete input threshold: open above 100 kOhm, closed below 5 kOhm, suitable for SPST dry contacts. Momentary inputs of 10 ms or more are detected, with a close-open cycle count that rolls over at a configurable 1 to 1,000,000 (default 1,000,000) |
| Output signal | WirelessHART IEC 62591 at 2.4 GHz into a self-organizing mesh with more than 99 percent data reliability. Update rate user-selectable from 1 second to 60 minutes. Discrete outputs switch up to 28 Vdc at 100 mA with about 1 ohm on resistance |
| Diagnostics | The momentary input count is the diagnostic: it catches trips that happen between wireless updates and turns a switch into a totaliser. To keep the intrinsic safety rating the input contacts must be simple switches, with no powered circuitry on the far end |
| Pressure range | Not applicable - a field mounted wireless transmitter with no process connection and no wetted parts |
| Variants | Eight discrete channels, each configurable as discrete input or output, with a third PWR OUT terminal per channel. Antenna adapters WK7 and WM7 are offered for the black power module or for use with a 10 to 30 Vdc external supply |
| Application | Clusters of discrete signals away from the control system: tank farm high level switches, pump run and fault contacts, valve open and closed feedbacks, remote wellhead alarms, and pulse counting on meters with no other path to the historian |
| Mounting | Field mounted in a weather sealed blue enclosure with a mounting bracket and integral antenna, wired through cable glands into the terminal blocks. PWR OUT delivers continuous voltage up to 2 Vdc below the supply feeding the transmitter |
| Operating temperature (°C) | Humidity 0 to 100 percent relative humidity. Radio frequency power from the antenna is a maximum of 10 mW (10 dBm) EIRP with the WK antenna, and 18 mW (12.5 dBm) EIRP with the extended range WM antenna |
Documents
Accessories and related items
Accessories and related items for this product are not available to order on Sproh yet. If the manufacturer lists them, an engineer can source them for you.
Ask an engineer