Rosemount 848T High Density Temperature Transmitter
Purchase options
From$1,424.65
- Availability
- Call for availability Originalx
Configurable — choose options to build the exact part number.
Independent supplier
Sproh is an independent supplier and is not an authorized distributor or official representative of Rosemount or Emerson.
Overview
Eight-channel high density temperature transmitter on FOUNDATION Fieldbus, with independently configurable RTD, thermocouple, ohm, mV and 4-20 mA inputs.
Key features
- Eight independently configurable temperature inputs in one transmitter
- RTD, thermocouple, ohm, millivolt and 4-20 mA inputs; 2- and 3-wire RTDs supported
- FOUNDATION Fieldbus output with eight AI blocks, two MAI blocks and backup LAS
- 600 Vdc channel-to-channel isolation, 10 Vdc under all conditions with up to 500 ft of sensor lead
- Bus powered 9.0 to 32.0 Vdc at 22 mA maximum; 1.5 s to read all eight inputs
- DIN rail or optional aluminium or stainless junction box; -40 to 85 C, 0 to 99% RH
Key specifications
- Accuracy
- Pt100 reference accuracy +/-0.30 °C at 20 °C; stability +/-0.1% of reading or 0.1 °C, whichever is greater, for two years on RTDs and one year on thermocouples; EMI correction with cold junction compensation
- Output signal
- Manchester-encoded FOUNDATION Fieldbus digital signal to IEC 61158 and ISA 50.02, with eight AI blocks, two MAI blocks, four ISEL blocks and backup LAS capability
- Power supply
- Bus powered over FOUNDATION Fieldbus, 9.0 to 32.0 Vdc at 22 mA maximum; transmitter terminals rated to 42.4 Vdc; 600 Vdc channel-to-channel isolation, and 10 Vdc under all conditions with up to 500 ft (152 m) of 18 AWG sensor lead
- Diagnostics
- Measurement validation diagnostics for sensor degradation, sensor wiring connectivity, high vibration affecting the measurement, and abnormal process variation; alarms configurable HI-HI, HI, LO and LO-LO
- Certifications
- Intrinsic safety, Type n, dust and Division 2 approvals by code for ATEX, IECEx, FM, CSA, Brazil and China; integral transient protection (T1) fitted at the factory
- Measurement range
- Eight independently configurable inputs: 2- and 3-wire RTDs, thermocouples, millivolts, 2- and 3-wire ohms, and 4-20 mA signals through optional connectors
Eight temperature points on one fieldbus segment
The Rosemount 848T is a high-density temperature transmitter: eight independently configurable sensor inputs in one housing, sending FOUNDATION Fieldbus back to the host. It exists because a plant with a hundred temperature points on a distillation column does not want a hundred transmitters, a hundred cable runs and a hundred marshalling terminations.
What eight channels change
Each input is configured on its own — 2- and 3-wire RTDs, thermocouples, millivolts, 2- and 3-wire ohms, and 4-20 mA signals through optional connectors — so one box covers a column's worth of mixed sensors rather than one box per sensor. The wiring arrives at the device and the digital signal leaves on a single segment, which is where the installation savings come from: less cable, fewer terminations, fewer enclosure entries.
Isolation, stated precisely
Channel-to-channel isolation is 600 Vdc, and 10 Vdc under all operating conditions with up to 500 ft (152 m) of 18 AWG sensor lead. That distinction matters: the 600 Vdc figure describes fault isolation between channels, while the 10 Vdc figure is what holds up in normal service with long sensor runs. Reading only the first number would overstate what a long thermocouple lead can tolerate.
Bus power and update time
The transmitter is powered over the fieldbus segment, 9.0 to 32.0 Vdc drawing at most 22 mA, with terminals rated to 42.4 Vdc. Reading all eight inputs takes approximately 1.5 seconds, and the unit is within specification less than 30 seconds after power is applied. On a slow process that is more than adequate; on a fast one, it is a number to design around.
Accuracy and stability
Reference accuracy for Pt100 at 20 °C is ±0.30 °C. Stability is ±0.1% of reading or 0.1 °C, whichever is greater, for two years on RTDs and one year on thermocouples. The measurement circuitry self-calibrates against internal references on every update, and EMI correction with cold junction compensation is built in — the second part being what makes thermocouple measurements honest inside a warm enclosure.
The diagnostic that earns its keep
Measurement validation diagnostics identify sensor degradation, sensor wiring connectivity problems, high vibration affecting the measurement, and abnormal process variation. In practice this is the difference between a channel that fails loudly and a channel that quietly reads two degrees low for a year.
Mounting
The transmitter mounts directly on DIN rail or in an optional junction box — aluminium with 9 × ½ in NPT nickel-plated brass glands, or stainless steel with 9 × M20 glands — which in turn mounts to a panel or a 2 in (51 mm) pipe stand. Ambient range is -40 to 85 °C in 0 to 99% non-condensing humidity, at 208 g for the transmitter alone. Intrinsically safe versions and the WirelessHART variant extend the same eight-channel design to locations where a segment cannot reach.
Manufacturer reference: Rosemount 848T High Density Temperature Measurement Family Product Data Sheet, 00813-0100-4697 Rev SD, August 2024.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | Pt100 reference accuracy +/-0.30 °C at 20 °C; stability +/-0.1% of reading or 0.1 °C, whichever is greater, for two years on RTDs and one year on thermocouples; EMI correction with cold junction compensation |
| Output signal | Manchester-encoded FOUNDATION Fieldbus digital signal to IEC 61158 and ISA 50.02, with eight AI blocks, two MAI blocks, four ISEL blocks and backup LAS capability |
| Power supply | Bus powered over FOUNDATION Fieldbus, 9.0 to 32.0 Vdc at 22 mA maximum; transmitter terminals rated to 42.4 Vdc; 600 Vdc channel-to-channel isolation, and 10 Vdc under all conditions with up to 500 ft (152 m) of 18 AWG sensor lead |
| Diagnostics | Measurement validation diagnostics for sensor degradation, sensor wiring connectivity, high vibration affecting the measurement, and abnormal process variation; alarms configurable HI-HI, HI, LO and LO-LO |
| Certifications | Intrinsic safety, Type n, dust and Division 2 approvals by code for ATEX, IECEx, FM, CSA, Brazil and China; integral transient protection (T1) fitted at the factory |
| Measurement range | Eight independently configurable inputs: 2- and 3-wire RTDs, thermocouples, millivolts, 2- and 3-wire ohms, and 4-20 mA signals through optional connectors |
| Application | High density temperature measurement for columns, tanks and skids where many sensor points sit close together, on a single FOUNDATION Fieldbus segment |
| Mounting | Direct DIN rail mounting, or an optional aluminium (9 x 1/2 in NPT glands) or stainless steel (9 x M20 glands) junction box for panel or 2 in (51 mm) pipe stand mounting |
| Dimensions | Transmitter 208 g (0.47 lb) alone; 2.2 kg (4.75 lb) in the aluminium junction box |
| Operating temperature (°C) | -40 to 85 °C (-40 to 185 °F) ambient; 0 to 99% relative humidity, non-condensing |
Documents
Accessories and related items
Accessories and related items for this product are not available to order on Sproh yet. If the manufacturer lists them, an engineer can source them for you.
Ask an engineer