Overview

Eight-channel high density temperature transmitter on FOUNDATION Fieldbus, with independently configurable RTD, thermocouple, ohm, mV and 4-20 mA inputs.

Key features

  • Eight independently configurable temperature inputs in one transmitter
  • RTD, thermocouple, ohm, millivolt and 4-20 mA inputs; 2- and 3-wire RTDs supported
  • FOUNDATION Fieldbus output with eight AI blocks, two MAI blocks and backup LAS
  • 600 Vdc channel-to-channel isolation, 10 Vdc under all conditions with up to 500 ft of sensor lead
  • Bus powered 9.0 to 32.0 Vdc at 22 mA maximum; 1.5 s to read all eight inputs
  • DIN rail or optional aluminium or stainless junction box; -40 to 85 C, 0 to 99% RH

Key specifications

Accuracy
Pt100 reference accuracy +/-0.30 °C at 20 °C; stability +/-0.1% of reading or 0.1 °C, whichever is greater, for two years on RTDs and one year on thermocouples; EMI correction with cold junction compensation
Output signal
Manchester-encoded FOUNDATION Fieldbus digital signal to IEC 61158 and ISA 50.02, with eight AI blocks, two MAI blocks, four ISEL blocks and backup LAS capability
Power supply
Bus powered over FOUNDATION Fieldbus, 9.0 to 32.0 Vdc at 22 mA maximum; transmitter terminals rated to 42.4 Vdc; 600 Vdc channel-to-channel isolation, and 10 Vdc under all conditions with up to 500 ft (152 m) of 18 AWG sensor lead
Diagnostics
Measurement validation diagnostics for sensor degradation, sensor wiring connectivity, high vibration affecting the measurement, and abnormal process variation; alarms configurable HI-HI, HI, LO and LO-LO
Certifications
Intrinsic safety, Type n, dust and Division 2 approvals by code for ATEX, IECEx, FM, CSA, Brazil and China; integral transient protection (T1) fitted at the factory
Measurement range
Eight independently configurable inputs: 2- and 3-wire RTDs, thermocouples, millivolts, 2- and 3-wire ohms, and 4-20 mA signals through optional connectors
See all specifications