Rosemount 8705 Flanged Magnetic Flow Meter Sensors
Purchase options
From$1,909.43
- Availability
- Call for availability Originalx
Configurable — choose options to build the exact part number.
Independent supplier
Sproh is an independent supplier and is not an authorized distributor or official representative of Rosemount or Emerson.
Overview
Fully welded flanged magmeter sensor for conductive liquids and slurries, 1/2 to 36 in, at 0.25 percent of rate and sized by velocity band.
Key features
- Flanged magnetic flow meter sensor, fully welded with a sealed coil housing, in line sizes from 1/2 to 36 inches
- Standard reference accuracy 0.25 percent of RATE, optional high accuracy 0.15 percent of rate - rate-based, so it does not degrade at low flow the way a DP measurement does
- Sizing is by velocity, not pipe size: preferred 2-20 ft/s for clean service but only 3-10 ft/s for abrasive slurries, which is what stops a correct meter being hydraulically wrong
- Process fluid conductivity must exceed 100 microsiemens/cm; below that no calibration helps and a different electrode configuration is required
- Electrode options include standard, grounding and bullet-nose types - grounding for unlined or non-conductive pipework, bullet-nose for abrasive service
- Pairs with the 8732 integral, 8712 remote or 8712H/8707 high-signal transmitter
Key specifications
- Accuracy
- 0.25 percent of RATE standard reference accuracy, 0.15 percent of rate with the optional high accuracy class. Rate-based accuracy stays roughly constant down to the bottom of the usable velocity band, unlike a square-root DP measurement
- Output signal
- The sensor produces an electrode signal; flow output comes from the transmitter it is paired with - 8732 integral, 8712 remote, or the 8712H/8707 high-signal pulsed DC system
- Diagnostics
- Conductivity limit is greater than 100 microsiemens/cm for the standard configuration; below that the electrode circuit cannot resolve a usable signal and a low-conductivity electrode option is required instead. A grounding electrode gives the fluid an earth reference in unlined or non-conductive pipework, and a bullet-nose electrode resists wear in abrasive service
- Pressure range
- Set by the flange class and liner selection; flanged ANSI, DIN and JIS flange standards are available across the 1/2 to 36 in line size range
- Variants
- Line sizes 1/2 to 36 in. Liner types and electrode materials per the selection tables; electrode types standard, grounding and bullet-nose. Standard 8705 flanged body, alongside the 8711 wafer and 8721 hygienic sensors in the same series
- Application
- Conductive liquids and slurries in water and wastewater, pulp and paper stock, chemical dosing, food-grade fluid transfer and mining slurries, where the fluid conducts above the threshold and the flow needs an unobstructed bore
You size a magnetic flow meter by velocity, not by pipe size
The Rosemount 8705 is the flanged magnetic flow meter sensor of the 8700 series: a fully welded flow tube in line sizes from ½ to 36 inches, for conductive liquids and slurries, with a standard reference accuracy of 0.25 percent of rate and an optional high accuracy of 0.15 percent of rate.
Those two figures describe what the instrument can do. What decides whether the installation works is something else in the same datasheet, and it is usually read too quickly.
The sizing table is the engineering
| Application | Velocity range |
|---|---|
| Normal service | 0–39 ft/s (0–12 m/s) |
| Preferred service | 2–20 ft/s (0.6–6.1 m/s) |
| Abrasive slurries | 3–10 ft/s (0.9–3.1 m/s) |
| Non-abrasive slurries | 5–15 ft/s (1.5–4.6 m/s) |
A magmeter generates a voltage proportional to velocity, so at very low velocity the signal is small and the measurement is at the mercy of noise and zero drift; at very high velocity the fluid erodes the liner and the electrodes. The bands above are the manufacturer's answer to both, and the useful part is that they are different for different fluids: an abrasive slurry is held to 3–10 ft/s while clean liquid is allowed 2–20. Sizing by pipe diameter alone produces a meter that is technically correct and hydraulically wrong, and the failure is not a fault — it is a meter reading accurately at a velocity that destroys it in two years.
The worked example in the datasheet makes the arithmetic concrete: a 4 inch sensor has a conversion factor of 39.679, so 300 gpm gives 7.56 ft/s — inside the preferred band for clean service. Take the same 300 gpm into a 6 inch line and the velocity falls to about 3.3 ft/s, which is still acceptable for a clean liquid and outside the band for an abrasive slurry. The flow rate did not change; the meter did.
"Of rate", which is why magmeters own wide turndown
The accuracy is quoted against the measured rate, not against a span. A differential pressure flow measurement has square-root behaviour and its uncertainty grows sharply at low flow; a magnetic meter's percentage error stays roughly the same down to the bottom of its usable velocity band. That is the property that makes a magmeter the right choice for a line that runs at 20 percent of design flow most of the time, and it is why the number on the datasheet is worth more than the same number on a DP device.
The conductivity gate
The fluid has to conduct. The standard requirement is a process fluid conductivity greater than 100 microsiemens/cm. Below that the electrode circuit cannot resolve a usable signal, and a low-conductivity fluid needs a different electrode configuration rather than a different calibration. This is a fluid property, not an installation detail, so it belongs in the specification before the line size is chosen: deionised water, some solvents and most hydrocarbons are simply not magmeter applications, and no amount of care in installation changes that.
Fully welded, and what that is protecting
The sensor is fully welded with a sealed coil housing. The coil that generates the magnetic field sits outside the wetted bore but inside the tube body, and a moisture path into it is how a magmeter fails in a wet or buried installation. Welding the housing closes that path rather than gasketing it, which is why this sensor is the one specified for below-grade, washdown and flooded locations. Electrode options include standard, grounding and bullet-nose types — the grounding electrode for unlined or non-conductive pipework where the fluid has no earth reference, and the bullet-nose profile for abrasive service where a flush electrode would wear at the leading edge.
Where it fits
Conductive liquids and slurries in water and wastewater, pulp and paper stock, chemical dosing lines, food-grade fluid transfer, and mining slurries — anywhere the fluid conducts above the threshold and the flow needs an unobstructed bore. It is a sensor, so it pairs with a transmitter from the same series: integral in the 8732, remote in the 8712, or the high-signal 8712H/8707 system for the most demanding pulsed-DC applications. Choose the liner and electrode for the chemistry and the abrasion, then size the line for the velocity band the fluid belongs to.
Manufacturer reference: Rosemount 8700 Series Magnetic Flowmeter Sensors Product Data Sheet for sizing guidelines, accuracy classes, conductivity limits, liner and electrode tables.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | 0.25 percent of RATE standard reference accuracy, 0.15 percent of rate with the optional high accuracy class. Rate-based accuracy stays roughly constant down to the bottom of the usable velocity band, unlike a square-root DP measurement |
| Output signal | The sensor produces an electrode signal; flow output comes from the transmitter it is paired with - 8732 integral, 8712 remote, or the 8712H/8707 high-signal pulsed DC system |
| Diagnostics | Conductivity limit is greater than 100 microsiemens/cm for the standard configuration; below that the electrode circuit cannot resolve a usable signal and a low-conductivity electrode option is required instead. A grounding electrode gives the fluid an earth reference in unlined or non-conductive pipework, and a bullet-nose electrode resists wear in abrasive service |
| Pressure range | Set by the flange class and liner selection; flanged ANSI, DIN and JIS flange standards are available across the 1/2 to 36 in line size range |
| Variants | Line sizes 1/2 to 36 in. Liner types and electrode materials per the selection tables; electrode types standard, grounding and bullet-nose. Standard 8705 flanged body, alongside the 8711 wafer and 8721 hygienic sensors in the same series |
| Application | Conductive liquids and slurries in water and wastewater, pulp and paper stock, chemical dosing, food-grade fluid transfer and mining slurries, where the fluid conducts above the threshold and the flow needs an unobstructed bore |
| Mounting | Bolted between pipeline flanges with the flow arrow in the direction of flow. Sizing is by velocity rather than pipe diameter: preferred service 2-20 ft/s (0.6-6.1 m/s), abrasive slurries only 3-10 ft/s (0.9-3.1 m/s), non-abrasive slurries 5-15 ft/s |
| Operating temperature (°C) | Set by the liner and electrode materials selected for the process chemistry and temperature. Fully welded construction with a sealed coil housing protects the coil from moisture ingress in wet, buried or washdown locations |