Overview

Floor mounted pneumatic power positioner: 8 x 14 frame, 80 degrees rotation, 4,600 ft-lb stall torque, 1% repeatability, 2 scfm air consumption.

Key features

  • Floor mounted pneumatic torque type power positioner, 8 x 14 frame, 80 degrees of rotation
  • Stall torque 4,600 ft-lb (6,238 N·m); maximum friction load 1,100 ft-lb (1,492 N·m)
  • Repeatability 1% of full stroke or better; full stroke time 2.5 seconds unloaded
  • Air supply 45 to 120 psig at 2 scfm steady state; input 3-15 psig, 0-30 psig or 4-20 mA
  • Temperature limits 0 to 140 F, 160 F with increased maintenance
  • Air filter, clevis and pin included; options include manual operator, dust cover, fail safe, position transmitter and master/slave

Key specifications

Accuracy
Repeatability 1% of full stroke or better; full stroke time 2.5 seconds unloaded for an 8 in. stroke; standard cam gives a straight line signal-to-position relationship
Output signal
Stall torque 4,600 ft-lb (6,238 N·m) over an 8 inch stroke producing 80 degrees of rotation; maximum friction load 1,100 ft-lb (1,492 N·m) and maximum allowable weight load 1,600 ft-lb (2,170 N·m)
Diagnostics
Position transmitter, retransmitting potentiometer and limit switches provide feedback to the control system; limit switch ratings as listed for the 4 x 5 torque floor mounted type
Pressure range
Air supply 45 to 120 psig (310 to 827 kPa gauge) with 100 psig recommended; consumption 2 scfm steady state, roughly double the 6x10
Variants
Input signal 3-15 psig, 0-30 psig or 4-20 mA; options include manual operator (limited to 45 psi differential), air lock, dust cover, heater, I/P converter, position transmitter, fail safe, dual or heavy duty limit switches, retransmitting potentiometer and master/slave positioner
Application
Floor mounted pneumatic actuation of large primary and secondary air dampers on utility and industrial boilers, and furnace dampers too stiff for the 6x10 drive
See all specifications