Overview
Commissioning and maintenance kit for 935/936 open path detectors: alignment tool, six check filters, USB RS-485 harness. One kit per site.
Key features
- Extended commissioning kit P/N 888257, required for commissioning and for future maintenance checks of the 935 and 936 open path detectors
- Only ONE kit is required per site: it is the shared tool the maintenance team owns, so the cost per detector falls with every pair on site
- Contents are alignment tool 888240, six functional check filters, USB RS-485 harness and Allen keys - optical alignment, digital access and mechanical access in one case
- A functional check cannot use gas across a 200 m beam, so a calibrated optical filter stands in for a known gas cloud and proves the whole installed path
- Six filters cover the propane, methane and ethylene bands, which is what allows one kit to serve every detector on a plant
- Signal verification is the companion test: alignment drift, a dirty window and a failing lamp all look like a falling signal, so it catches a detector going quietly blind
Key specifications
- Accuracy
- The kit carries the reference for the check rather than a measurement specification of its own: the six check filters each state a known equivalent concentration in LEL.m, from 110-270 and 270-490 LEL.m propane through methane and ethylene bands up to 490-760 LEL.m ethylene
- Output signal
- USB RS-485 harness connects a PC running the host software to the detector for signal verification and the functional check
- Diagnostics
- Signal verification measures the received signal through the PC host software and confirms the open path itself is healthy - alignment, window cleanliness, transmitter and receiver. Alignment drift, a dirty window and a failing lamp all present as a falling signal, which is how a detector going quietly blind is caught before the next functional check
- Pressure range
- Not applicable - a tool kit with no process connection and no wetted parts
- Variants
- Kit P/N 888257 covers the 935 family: alignment tool 888240, six functional check filters, USB RS-485 harness and Allen keys. The 936 family is listed separately as 888897-1 for hydrogen sulfide and 888897-2 for ammonia, each including the auxiliary IS/RS-485 and HART harness
- Application
- Commissioning and periodic maintenance checks of Rosemount 935 and 936 open path gas detectors: optical alignment, signal verification and the functional check that proves an installed pair reads correctly
One kit per site, because it is a shared tool rather than a per-detector accessory
The Rosemount Extended Commissioning Kit, P/N 888257, is required for commissioning and for future maintenance checks of the 935 and 936 open path gas detectors. The line in the manual that changes how it is bought is short: only one kit is required per site.
That single sentence reframes the purchase. This is not an accessory that multiplies with the number of detectors — it is the tool the maintenance team owns, uses to bring each new pair into service, and then keeps using for the periodic checks the detectors need for the rest of their lives. On a site with six detectors, the cost per instrument is a sixth of the price.
What is in the kit, and why each part is there
| Item | Why it is needed |
|---|---|
| Alignment tool (P/N 888240) | Points the two heads at each other to the tolerance the optics require |
| Six functional check filters | Prove the installed pair reads correctly, without gas in the beam |
| USB RS-485 harness | Connects a PC to the detector for signal verification and the functional check |
| Allen keys | Opens the enclosure and adjusts the brackets with the right tool, on site |
Read as a list, that is the three things commissioning actually needs: optical alignment, digital access, and mechanical access. A site that improvises any one of them either cannot complete the functional check or cannot document that it did.
Why the check uses filters and not gas
A point detector is function-tested by putting calibration gas on it. That approach cannot be scaled to a beam: no one carries a gas cloud 200 metres across a tank farm, and no permit would allow it.
So the functional check replaces the gas with a calibrated optical filter placed in the beam. The filter absorbs a known amount of the infrared the detector is looking for, which the instrument cannot distinguish from the absorption a gas cloud would produce — so a filter with a stated LEL·m equivalent is, for testing purposes, a known gas cloud. The reading either lands in the expected band or it does not, and the detector has been proven end to end: source, path, window, receiver and electronics, in the installed condition.
Six filters, because one kit has to serve every gas
The six filters span the gas and range combinations a site can hold, and that is exactly why one kit covers a whole plant:
| Check filter | Equivalent concentration |
|---|---|
| 888260-1 | 110 to 270% LEL·m propane |
| 888260-2 | 270 to 490% LEL·m propane |
| 888260-3 | 140 to 250% LEL·m methane |
| 888260-4 | 270 to 480% LEL·m methane |
| 888260-5 | 180 to 370% LEL·m ethylene |
| 888260-3 or 888260-6 | 490 to 760% LEL·m ethylene |
Match the filter to the gas the detector is set for and to the band its full scale covers. A filter from the wrong band will still be seen by the detector — which is the dangerous part, because it will produce a reading. The check is only meaningful when the expected value is the one the filter was made for, and the filters are individually part-numbered so that the box states which is which.
The check is periodic, not one-off
The kit is required for commissioning, and then again for maintenance. The detector's own schedule calls for a functional check at intervals during service, alongside a signal verification and a baseline (zero) reset whenever the transmitter or receiver is disturbed.
Signal verification is the companion test and answers a different question: it confirms that the open path itself is healthy — that the two heads are aligned, the windows are clean, and neither the transmitter nor the receiver has a problem — by measuring the received signal through the PC host software. Alignment drift, a dirty window and a failing lamp all look like a falling signal, so this is the check that catches a detector going quietly blind before the next functional check would.
Buying notes
Buy one kit per site, not one per detector pair, and hold it with the maintenance team rather than in the project material. Note that the 935 and 936 versions differ in their harness part numbers (the 936 kits are listed as 888897-1 for hydrogen sulfide and 888897-2 for ammonia, each including the auxiliary IS/RS-485 and HART harness) — so confirm the kit matches the detector family on site, and if a plant runs both families, confirm with the manufacturer which kit covers both.
Manufacturer reference: Rosemount 935 Reference Manual 00809-0100-4035 Appendix B.7 for the commissioning kit contents and the check filter table; the 936 product data sheet lists the corresponding 888897 kit variants.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | The kit carries the reference for the check rather than a measurement specification of its own: the six check filters each state a known equivalent concentration in LEL.m, from 110-270 and 270-490 LEL.m propane through methane and ethylene bands up to 490-760 LEL.m ethylene |
| Output signal | USB RS-485 harness connects a PC running the host software to the detector for signal verification and the functional check |
| Diagnostics | Signal verification measures the received signal through the PC host software and confirms the open path itself is healthy - alignment, window cleanliness, transmitter and receiver. Alignment drift, a dirty window and a failing lamp all present as a falling signal, which is how a detector going quietly blind is caught before the next functional check |
| Pressure range | Not applicable - a tool kit with no process connection and no wetted parts |
| Variants | Kit P/N 888257 covers the 935 family: alignment tool 888240, six functional check filters, USB RS-485 harness and Allen keys. The 936 family is listed separately as 888897-1 for hydrogen sulfide and 888897-2 for ammonia, each including the auxiliary IS/RS-485 and HART harness |
| Application | Commissioning and periodic maintenance checks of Rosemount 935 and 936 open path gas detectors: optical alignment, signal verification and the functional check that proves an installed pair reads correctly |
| Mounting | Only one kit is required per site: it is held by the maintenance team and reused for every detector pair, not fitted to each instrument |
| Operating temperature (°C) | A service tool, used during commissioning and maintenance rather than left installed. The detectors it serves are rated for harsh outdoor environments including snow, ice and condensation |