Rosemount 935/936 Pole Mount
No product images are published for this product yet.
Purchase options
From$187.53
- Availability
- Call for availability Originalx
Configurable — choose options to build the exact part number.
Independent supplier
Sproh is an independent supplier and is not an authorized distributor or official representative of Rosemount or Emerson.
Overview
Pole mounting kit and tilt mount assembly for the Rosemount 935 and 936 open path gas detectors, with the alignment range a long beam requires.
Key features
- Pole mounting kit for the Rosemount 935 and 936 open path gas detectors, supplied as a tilt mount assembly
- The bracket is what makes alignment possible: the detector's own misalignment tolerance is +/-0.5 degrees, which is about 1.75 m of lateral error at the far head on a 200 m span
- Tilt adjustment is checked against the received signal, not by eye, because nobody can judge a beam that has travelled 200 m
- The heads are not field-repairable - their alignment and calibration are done at the factory - so the mount is the installer's only alignment control
- One kit per detector head: an open path pair needs two mounted heads
Key specifications
- Accuracy
- The mount carries the alignment, and the alignment tolerance of the detector is +/-0.5 degrees displacement/misalignment. Projected across a long path that tolerance is tight: about 0.5 m of lateral error at 60 m and roughly 1.75 m at 200 m
- Output signal
- No electrical function. Alignment is confirmed through the detector's received signal, read with the host software, because a beam that has crossed 200 m cannot be judged by eye
- Diagnostics
- Align, verify the received signal, then lock - and check the signal again after the final tightening, because hardware that shifts while being locked moves the head. The detector heads are not field-repairable, so the mount is the installer's only control over alignment
- Pressure range
- Not applicable - a mounting bracket with no process connection and no wetted parts
- Variants
- One kit per detector head. The same kit serves both the 935 combustible and 936 toxic open path families, and is used with the tilt mount assembly shown on the manufacturer drawing
- Application
- Mounting the Rosemount 935 and 936 open path gas detector heads on a vertical pole, where a fence line, tank farm perimeter, loading rack or open process area has no wall or dedicated structure to carry them
The bracket is the only alignment mechanism the installer has
The Rosemount pole mount is the mounting kit for the 935 and 936 open path gas detectors: a tilt mount assembly that carries a detector head on a vertical pole. On a point instrument a bracket is a convenience. On an open path detector it is a load-bearing part of the measurement, because the two heads have to be aimed at each other to a tolerance that a fixed bracket cannot express.
Why the tilt matters more than the pole
An open path detector works on the light that crosses the gap between its source and its receiver. That gap can be 660 ft (200 m) on the long-range pair, and the optics will only accept a small angular error between the two heads — the manufacturer's own figure for the detector is a displacement/misalignment tolerance of ±0.5 degrees.
Half a degree sounds forgiving until it is projected across a long path. At 60 m it is about half a metre of lateral error at the far head. At 200 m it is roughly 1.75 m — a bracket that is a hand-span out of aim at one end can put the beam entirely off the far window. On a short duct installation the same tolerance is easy; on a 200 m span the mount has to be adjustable in small, repeatable steps, and that is what a tilt mount provides that a simple pole clamp does not.
The pole itself has a second job, which is height. Both heads need a clear line above vehicles, walkways and low pipework, and they need to be mounted to something that does not move — a structural column or a dedicated pole, not a handrail that shakes when someone leans on it.
Adjust, check, then lock
The alignment sequence on this family of detectors is deliberate, and the bracket is built around it: aim the units, verify the received signal, and then tighten. The signal verification step exists precisely because the eye cannot judge a beam that has travelled 200 m — the received signal is the only feedback that says the pair is on target, and it also reveals a dirty window or a failing lamp at the same time.
Which is why the tightening order matters. An alignment done with loose hardware and confirmed by signal is worthless if locking the bracket afterwards moves the head, so the check belongs both before and after the final tightening. The detector's own documentation treats the heads as not field-repairable, citing the meticulous alignment and calibration of the sensors — meaning everything that protects that alignment in the field is the installer's responsibility, and the mount is most of it.
What to check before ordering
Three things decide whether a given site can use this kit:
- The pole. The mount clamps to a vertical pole of the appropriate diameter. If the site intends to use an existing structural column, confirm the clamping range rather than assuming a column is a pole.
- The detector family. This kit is specified for the 935 and 936 series. The same kit is used for both, which is convenient on a site that runs combustible and toxic open path detection together.
- The environment. The detector heads are specified for dust, fog, rain, snow and vibration, and the mount should be no weaker. A pole that deflects in wind moves the beam, and beam movement reads as a signal change in an instrument whose whole diagnostic method is signal change.
Where it fits
Fence lines, tank farm perimeters, loading racks and open process areas — anywhere the detector pair is installed on poles rather than on a wall or a dedicated structure. Buy one per detector head: an open path pair needs two mounted heads, and a spare bracket on site is cheap compared with a return visit to re-aim one.
Manufacturer reference: Rosemount 935/936 open path gas detector and tilt mount assembly dimensional drawing for the bracket assembly and its mounting dimensions.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | The mount carries the alignment, and the alignment tolerance of the detector is +/-0.5 degrees displacement/misalignment. Projected across a long path that tolerance is tight: about 0.5 m of lateral error at 60 m and roughly 1.75 m at 200 m |
| Output signal | No electrical function. Alignment is confirmed through the detector's received signal, read with the host software, because a beam that has crossed 200 m cannot be judged by eye |
| Diagnostics | Align, verify the received signal, then lock - and check the signal again after the final tightening, because hardware that shifts while being locked moves the head. The detector heads are not field-repairable, so the mount is the installer's only control over alignment |
| Pressure range | Not applicable - a mounting bracket with no process connection and no wetted parts |
| Variants | One kit per detector head. The same kit serves both the 935 combustible and 936 toxic open path families, and is used with the tilt mount assembly shown on the manufacturer drawing |
| Application | Mounting the Rosemount 935 and 936 open path gas detector heads on a vertical pole, where a fence line, tank farm perimeter, loading rack or open process area has no wall or dedicated structure to carry them |
| Mounting | Clamps to a vertical pole. Confirm the clamping range against the intended pole diameter before ordering, and do not assume a structural column is within that range. Mount to a structure that does not move when someone leans on it |
| Operating temperature (°C) | Intended for the same outdoor service as the detectors it carries, which are specified for dust, fog, rain, snow, vibration and condensation. A pole that deflects in wind moves the beam and reads as a signal change |