Rosemount 935 Open Path Combustible Gas Detector
Purchase options
From$3,040.68
- Availability
- Call for availability Originalx
Configurable — choose options to build the exact part number.
Independent supplier
Sproh is an independent supplier and is not an authorized distributor or official representative of Rosemount or Emerson.
Overview
Open path combustible gas detector for hydrocarbons and ethylene across up to 200 m, reading in LEL.m with under 3 s response and SIL2.
Key features
- Open path combustible gas detector using infrared flash technology, covering up to 660 ft (200 m) of line-of-sight
- Measures in LEL.m, not percent LEL: the reading is gas integrated along the beam, so a thin cloud over 200 m and a dense pocket over 2 m can read the same
- Response in under three seconds to T90, with SIL2 rating by TUV
- Tolerates up to 95 percent obscuration from dust, fog, rain, snow and vibration, which is what lets an optical detector survive a winter instead of being bypassed
- Source range options T1 7-20 m, T2 15-40 m, T3 35-100 m, T4 80-200 m; a long-range source is not a superset, so the range is chosen from the measured span
- Sold as two heads on aiming brackets: source 935TXF... and detector/receiver 935R1F00..., both required, aligned during commissioning
Key specifications
- Accuracy
- Reading expressed in LEL.m (lower explosive limit times metres), methane full scale 5 LEL.m default, because the instrument integrates gas along the beam. Spectral response 2.0 to 3.0 micron. Response time 3 seconds to T90
- Output signal
- Detector/receiver head with alarm and fault signalling to the plant gas detection system. Rated SIL2 by TUV
- Diagnostics
- A range option is not a superset: a long-range source cannot span a short gap, so the range is chosen from the measured distance. Commissioning requires the 935/936 commissioning kit, which is a required purchase rather than an accessory
- Pressure range
- Not applicable - an open path optical detector with no process connection and no wetted parts
- Variants
- Source options by range: T1 23 to 66 ft (7 to 20 m), T2 50 to 132 ft (15 to 40 m), T3 115 to 330 ft (35 to 100 m), T4 265 to 660 ft (80 to 200 m). Source and detector are separate part numbers (935TXF... and 935R1F00...), both required
- Application
- Perimeter and fence-line monitoring, tank farms, loading racks, compressor and turbine enclosures, and open process areas where a gas cloud drifts through rather than sitting at a point. Detects alkanes C1 to C8 (methane to hexane) and ethylene
The unit on the datasheet is LEL·m, not percent LEL — and that is not a formatting choice
The Rosemount 935 is an open path combustible gas detector: an infrared source on one side of an area and a receiver on the other, watching a beam across up to 660 ft (200 m) for alkanes from methane to hexane and for ethylene. Response is under three seconds to T90, the design is rated SIL2 by TÜV, and it keeps working where dust, fog, rain, snow or vibration would otherwise destroy the optical signal — up to 95 percent obscuration.
What an open path detector actually measures
A point detector answers the question how much gas is at this spot? An open path detector cannot answer that question, because it has no spot — it has a line. What it measures is the gas it finds integrated along that line, which is why the reading is in LEL·m (lower explosive limit times metres) and why the default methane full scale is quoted as 5 LEL·m.
The consequence is easy to get wrong when the instrument is specified. A thin cloud of gas stretching the whole 200 m path and a dense pocket covering two metres can produce the same LEL·m value — and one of those is a plant emergency while the other may not be. The instrument is honest about this: it reports what it can see. It is not a substitute for point detection at a flange or a compressor seal, and point detection is not a substitute for it. The two answer different questions, and a specification that compares their readings numerically has compared a sum with a sample.
What the open path buys in exchange is coverage without gaps. A line of point detectors along a tank farm is a line of holes between the detectors; a beam across the same area has no holes, and a cloud that drifts between two fixed heads still crosses it.
The range option has to match the distance you are spanning
The source is ordered in four ranges, and they are not interchangeable:
| Source option | Range |
|---|---|
| T1 | 23 to 66 ft (7 to 20 m) |
| T2 | 50 to 132 ft (15 to 40 m) |
| T3 | 115 to 330 ft (35 to 100 m) |
| T4 | 265 to 660 ft (80 to 200 m) |
With the long-range source and the R1 detector, the permitted installation distance runs from 265 ft (80 m) minimum to 660 ft (200 m) maximum. The minimum is the part that surprises people: a long-range pair is not a superset of a short one, so a T4 source cannot be installed across a 30 m gap and expected to work. The range is chosen from the measured span, not from the largest number on the list.
Visibility, because a detector that stops seeing stops reporting
Optical detectors fail in a specific and unpleasant way in bad weather: the received signal falls, the instrument cannot distinguish attenuation from absorption, and the honest options are an alarm it cannot justify or a reading it cannot trust. The 935 uses infrared flash technology and is specified to tolerate up to 95 percent obscuration — dust, fog, rain, snow — and vibration, which is the practical difference between a detector that survives a winter and one that has to be put in bypass.
Two heads, two part numbers, one installation
The system is ordered as separate components: a source (935TXF…) and a detector/receiver (935R1F00…). Both are needed, they are separate line items, and they are aligned to each other. That also means the alignment is a commissioning activity rather than a plug-in: two stainless heads on aiming brackets, one at each end, with the beam as the only feedback that the pair is pointing at each other.
Commissioning is treated as its own step in the product family — there is a commissioning kit for the 935 and 936 series, and it is a required purchase rather than an optional convenience. Plan for it in the same order.
Where it fits
Perimeter and fence-line monitoring, tank farms, loading racks, compressor and turbine enclosures, and open process areas where a gas cloud would drift through rather than sit at a point. Choose it where the geometry is a line of sight across the hazard — not where the hazard is a specific flange you can put a point detector on.
Manufacturer reference: Rosemount 935 Open Path Combustible Gas Detector Product Data Sheet for detection ranges, response time, obscuration tolerance, SIL rating and model codes.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | Reading expressed in LEL.m (lower explosive limit times metres), methane full scale 5 LEL.m default, because the instrument integrates gas along the beam. Spectral response 2.0 to 3.0 micron. Response time 3 seconds to T90 |
| Output signal | Detector/receiver head with alarm and fault signalling to the plant gas detection system. Rated SIL2 by TUV |
| Diagnostics | A range option is not a superset: a long-range source cannot span a short gap, so the range is chosen from the measured distance. Commissioning requires the 935/936 commissioning kit, which is a required purchase rather than an accessory |
| Pressure range | Not applicable - an open path optical detector with no process connection and no wetted parts |
| Variants | Source options by range: T1 23 to 66 ft (7 to 20 m), T2 50 to 132 ft (15 to 40 m), T3 115 to 330 ft (35 to 100 m), T4 265 to 660 ft (80 to 200 m). Source and detector are separate part numbers (935TXF... and 935R1F00...), both required |
| Application | Perimeter and fence-line monitoring, tank farms, loading racks, compressor and turbine enclosures, and open process areas where a gas cloud drifts through rather than sitting at a point. Detects alkanes C1 to C8 (methane to hexane) and ethylene |
| Mounting | Two stainless steel heads on adjustable aiming brackets, one at each end of the path, aligned to each other during commissioning. With the R1 detector and T4 source the permitted distance runs from 265 ft (80 m) to 660 ft (200 m) |
| Operating temperature (°C) | Specified for harsh environments where dust, fog, rain, snow or vibration cause heavy signal reduction, with detection retained up to 95 percent obscuration |