Overview
Duct mount 00975-9000-0002 for the 975 detectors: optical window into hot ducts, 70 x 70 degree field of view, rated -55 to 200 C.
Key features
- Duct mount PN 00975-9000-0002 for any Rosemount 975 detector, letting it look into a hot duct through an optical window
- Limits the field of view to 70 degrees horizontal by 70 degrees vertical, against 100 x 95 for a bare detector
- Rated for installation temperatures -67 to 392 F (-55 to 200 C) - it keeps the detector out of the heat rather than making it heat tolerant
- Mount close to a riding girder connection on a stable, vibration-free surface; the duct gets an optical hole and a screw pattern from the layout drawing
- Mechanical and optical accessory only: the detector keeps its own approval and electronics
- For ducts cool enough to mount directly, the tilt mount keeps the full field of view
Key specifications
- Accuracy
- Limits the detector's cone of vision to 70 degrees horizontal and 70 degrees vertical, against 100 x 95 for a bare detector, so coverage must be recalculated for the reduced field of view
- Output signal
- None - the mount is passive; the detector behind the window keeps its own outputs and its own hazardous area approval
- Diagnostics
- No electronics; the assembly is mechanical and optical, so commissioning checks are the detector's built-in test plus a physical check that the window is clean and the cone unobstructed
- Pressure range
- Not stated as a pressure rating; the mount is a window arrangement bolted to the duct skin, so the duct's own pressure class governs and the installation has to be sealed at the flange
- Variants
- PN 00975-9000-0002, used with any Rosemount 975 Flame Detector; a specific high temperature optical window is part of the arrangement
- Application
- Flame detection in hot ducts and chambers where a detector cannot survive inside, or where it cannot be installed in the protected area at all: combustion air and flue ducts on boilers and furnaces, burner front compartments
A window into the duct, so the detector stays outside the heat
The Rosemount 975 duct mount (PN 00975-9000-0002) is the accessory that puts a 975 flame detector on the outside of a hot duct and lets it look in through an optical window. It exists for two situations: ducts and chambers where the temperature would destroy a detector installed inside, and spaces where a detector physically cannot be mounted in the protected area at all.
The trade is field of view, and it is a big one
A bare 975 sees 100 degrees horizontally by 95 degrees vertically. Through the duct mount the cone is limited to 70 degrees horizontal and 70 degrees vertical, because the window assembly becomes the aperture. That is not a small adjustment: the covered solid angle falls by roughly half, so a layout drawn for a bare detector in that duct is wrong by the time the mount is fitted. The coverage has to be recalculated with 70 by 70 as the field of view, or the duct gets a detector that watches a circle in the middle of the hazard.
Temperature
The mount is rated for installation temperatures from -67 to 392 °F (-55 to 200 °C). That range is the reason the product exists — it is the window and the mount that stand between a hot duct and the detector's own more limited operating range. Note which number the installation has to satisfy: the duct mount's window sees the duct temperature, so the 200 °C limit is the one to check against the process, not the detector's 85 °C.
Fitting it to the duct
The instructions are specific about the surface, and the reasons are mechanical. Mount as close as possible to a riding girder connection, because the duct skin between stiffeners flexes and the mount plus detector is a lever hanging off it; and mount on a surface that is stable and free of vibration, because the detector's optical path is the measurement and a vibrating window is a moving aperture. The duct then gets a hole for the optical path and screw holes for the flange, drilled from a layout drawing rather than measured in the field.
What it is, and what it is not
This is a mechanical and optical accessory: a duct mounting arrangement with a specific high-temperature optical window. The detector behind it keeps its own approval and its own electronics; the mount adds the window and the geometry. What it does not do is extend the detector's temperature rating — it keeps the detector out of the heat rather than making the detector heat-tolerant, which is exactly why the assembly works.
Where it fits
Combustion air and flue ducts on boilers and furnaces, burner front compartments, and any ducted process where a flame has to be seen from outside because the inside is too hot or inaccessible. Where the duct is cool enough for a direct mount, the tilt mount is cheaper and keeps the full field of view.
Manufacturer reference: Rosemount 975 Duct Mount Quick Start Guide 00825-0600-4975, description and installation procedure.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | Limits the detector's cone of vision to 70 degrees horizontal and 70 degrees vertical, against 100 x 95 for a bare detector, so coverage must be recalculated for the reduced field of view |
| Output signal | None - the mount is passive; the detector behind the window keeps its own outputs and its own hazardous area approval |
| Diagnostics | No electronics; the assembly is mechanical and optical, so commissioning checks are the detector's built-in test plus a physical check that the window is clean and the cone unobstructed |
| Pressure range | Not stated as a pressure rating; the mount is a window arrangement bolted to the duct skin, so the duct's own pressure class governs and the installation has to be sealed at the flange |
| Variants | PN 00975-9000-0002, used with any Rosemount 975 Flame Detector; a specific high temperature optical window is part of the arrangement |
| Application | Flame detection in hot ducts and chambers where a detector cannot survive inside, or where it cannot be installed in the protected area at all: combustion air and flue ducts on boilers and furnaces, burner front compartments |
| Mounting | Install close to a riding girder connection on a stable surface free of vibration; the duct is drilled for the optical path and the screw pattern from the layout drawing, and the mount is disassembled for fitting |
| Operating temperature (°C) | -67 to 392 F (-55 to 200 C) at the installation; the mount keeps the detector out of the heat rather than extending the detector's own temperature rating |