Rosemount 975 Pipe Mount
No product images are published for this product yet.
Purchase options
From$78.36
- Availability
- Call for availability Originalx
Configurable — choose options to build the exact part number.
Independent supplier
Sproh is an independent supplier and is not an authorized distributor or official representative of Rosemount or Emerson.
Overview
Pipe mount bracket for the 975 detectors: clamps to a vertical pipe, 15.55 in overall length, two M25 or 3/4 NPT conduit entries.
Key features
- Pipe mount bracket that clamps a Rosemount 975 flame detector to a vertical pipe
- Overall length 15.55 in [395.0 mm], projection 6.10 in [155.0 mm], bracket width 5.12 in [130.0 mm]
- Two conduit entries, M25 x 1.5 or 3/4 NPT: one with a stainless steel plug, one with a temporary plug at the wiring entry
- Mechanical bracket only - no electronics, no sensing element, no certification of its own; the detector keeps its area approval
- Specified for stable structures, since the bracket's arm puts the detector into the pipe's own vibration path
- The tilt and pole mount is the alternative where the detector has to be aimed rather than fixed to an existing pipe
Key specifications
- Accuracy
- Defines the detector's position but adds no aiming joint: the tilt and pole mount is the version that can be aimed, so a coverage layout that needs an adjustable angle cannot be met by this bracket alone
- Output signal
- None - mechanical bracket only; the detector keeps its own outputs and hazardous area approval
- Diagnostics
- Ships with a stainless steel plug in one entry and a temporary plug at the wiring entry - a plastic plug left in an unused entry is a common water path into a detector, and this assembly supplies the right plug
- Pressure range
- Not applicable - mechanical bracket with no process connection
- Variants
- Pipe mount bracket with overall length 15.55 in [395.0 mm], projection 6.10 in [155.0 mm], bracket width 5.12 in [130.0 mm] and 6.96 in [176.8 mm] optical end offset; two conduit entries M25 x 1.5 or 3/4 NPT
- Application
- Clamping a 975 flame detector to a vertical pipe in a rack, column or structural post, where the steel already exists and a wall penetration would need hot work or a structural review
A stand that clamps to the pipe instead of bolting to the wall
The Rosemount 975 pipe mount bracket carries a 975 flame detector on a vertical pipe rather than on a wall or a pole. It is the mounting answer for the places where the steel is already there — a pipe rack, a column, a handrail stanchion — and where drilling a wall means a hot work permit, a structural review, or a surface that vibrates.
The geometry it adds
The assembly drawing gives an overall length of 15.55 in [395.0 mm], a projection of 6.10 in [155.0 mm] from the mounting face, and a 5.12 in [130.0 mm] bracket width, with the detector's optical end offset from the pipe by the bracket's own 6.96 in [176.8 mm] dimension. That projection matters twice: it sets how far the detector stands off the pipe, and it puts the bracket's arm into the wind and vibration path that the pipe already carries. A detector on a vibrating pipe is a detector whose window moves, which is why the pipe mount is specified for stable structures rather than for any convenient handrail.
Two conduit entries, one already plugged
The detector's housing on this assembly has two entries, M25 x 1.5 or 3/4 NPT — one supplied with a stainless steel plug and one with a temporary plug at the wiring entry. That is the detail that decides a cable schedule: the installer uses one, keeps the other sealed, and the stainless plug is the one that stays in the weather for the life of the installation. A plastic plug left in an unused entry is the most common source of a water path into a detector, and this assembly ships with the right plug for the job.
Pipe mount, pole mount or wall: three different problems
The pipe mount clamps to an existing vertical pipe and needs no foundation. The tilt and pole mount is for standing a detector up where there is no structure at all, and it brings the aiming joint with it. A wall bracket is for flat surfaces. Choosing by what is available rather than by what the aiming needs is how detectors end up looking at the wrong part of a room — the mount decides whether the detector can be pointed, and only the tilt version has that joint built in.
What it is
A mechanical bracket: no electronics, no sensing element, no certification of its own. The detector keeps its hazardous area approval; the bracket carries the load and defines the position. It is supplied with the hardware to clamp to the pipe, and the drawing is the authority for the pipe size range and the bolt pattern rather than a catalogue summary.
Where it fits
Pipe racks in process units, columns and structural posts on tank farms, and any installation where the detector can be clamped at the height and angle the coverage needs. Where the detector has to be aimed across a wide arc, the tilt mount does that job and the pipe mount is the fixed-position alternative.
Manufacturer reference: Rosemount 975 Flame Detector with Pipe Mount Bracket drawing.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | Defines the detector's position but adds no aiming joint: the tilt and pole mount is the version that can be aimed, so a coverage layout that needs an adjustable angle cannot be met by this bracket alone |
| Output signal | None - mechanical bracket only; the detector keeps its own outputs and hazardous area approval |
| Diagnostics | Ships with a stainless steel plug in one entry and a temporary plug at the wiring entry - a plastic plug left in an unused entry is a common water path into a detector, and this assembly supplies the right plug |
| Pressure range | Not applicable - mechanical bracket with no process connection |
| Variants | Pipe mount bracket with overall length 15.55 in [395.0 mm], projection 6.10 in [155.0 mm], bracket width 5.12 in [130.0 mm] and 6.96 in [176.8 mm] optical end offset; two conduit entries M25 x 1.5 or 3/4 NPT |
| Application | Clamping a 975 flame detector to a vertical pipe in a rack, column or structural post, where the steel already exists and a wall penetration would need hot work or a structural review |
| Mounting | Clamps to a vertical pipe with the supplied hardware; the drawing is the authority for the pipe size range and bolt pattern rather than a catalogue summary |
| Operating temperature (°C) | Governed by the detector and the installation; the bracket carries no separate rating |
Documents
Accessories and related items
Accessories and related items for this product are not available to order on Sproh yet. If the manufacturer lists them, an engineer can source them for you.
Ask an engineer