Rosemount 975HR Flame Detector
Purchase options
From$2,326.64
- Availability
- Call for availability Originalx
Configurable — choose options to build the exact part number.
Independent supplier
Sproh is an independent supplier and is not an authorized distributor or official representative of Rosemount or Emerson.
Overview
Triple infrared flame detector with QuadSense processing and hydrogen detection: 300 ft range, sub-2 s response, SIL3 compatible.
Key features
- Triple infrared (IR3) flame detector with QuadSense processing and an added hydrogen fire detection channel
- Detection up to 300 ft (90 m) for gasoline and n-heptane, 207 ft for diesel and kerosene, 185 ft for alcohol
- Response: typically under 2 s at 131 ft and 10 s at 300 ft; ultra-fast under 1 s at 100 ft; 50 ms for an LPG/air explosion at 66 ft
- Six sensitivity ranges; field of view 90 x 90 degrees on hydrogen and 80 x 80 degrees for other fuels
- Operating range -76 to +185 F (-60 to +85 C), non-condensing humidity to 100%, SIL3 compatible, hazardous area certified
- Factory calibrated, smart field of view integrity test, 100 mA (2.2 W) at 24 Vdc without heater
Key specifications
- Accuracy
- Detection at the highest sensitivity on a 1 ft2 pan fire: gasoline and n-heptane 300 ft (90 m), diesel and kerosene 207 ft (63 m), alcohol and IPA 185 ft (55 m); coverage area 58,405 ft2 (5,426 m2)
- Output signal
- Alarm and fault outputs to the fire and gas system, with analog voltage output used for the ultra-fast and high-speed response modes; 24 Vdc power at 100 mA (2.2 W) without heater
- Diagnostics
- Smart field of view integrity test detects a blocked or dirty window as a fault rather than a silent loss of coverage; SIL3 compatible and certified for hazardous areas worldwide
- Pressure range
- Not applicable to the sensing function; the detector is housed for hazardous area service and mounted on a bracket or field of view limiter rather than installed in the process
- Variants
- 975HR with QuadSense triple infrared and hydrogen detection; six sensitivity ranges; field of view 90 x 90 degrees on hydrogen and 80 x 80 degrees for other fuels
- Application
- Long range flame detection in fuel storage and tank farms, loading racks, turbine and compressor enclosures and hydrogen handling areas, where the detector must look across an open area and reject welding, sunlight and hot surfaces
The IR3 detector that also sees hydrogen
The Rosemount 975HR is a triple infrared flame detector with QuadSense processing: three IR bands compared against each other, which is what gives a flame detector its false-alarm immunity without giving up the ability to see a small fire at a distance. It has the same 300 ft detection range as the 975MR, and it adds a hydrogen fire detection channel — which is what covers a fuel that burns with almost no visible or IR signature of its own.
Range is the specification that decides the layout
At the highest sensitivity setting, on a 1 ft² (0.1 m²) pan fire, the 975HR sees gasoline and n-heptane at 300 ft (90 m), diesel and kerosene at 207 ft (63 m), and alcohol at 185 ft (55 m). The higher alcohols and IPA fall to 185 ft. That is the number that sets detector spacing and the number that gets the coverage area to 58,405 ft² (5,426 m²) — a volume figure of 11.4 million cubic feet. Emerson's own framing is that the extended range more than doubles the coverage of a conventional IR detector, which is a reduction in the number of units and in the cable and mounting work that goes with them.
Response time has three different meanings
The datasheet quotes three, and they answer different questions. Standard response is typically under 2 seconds at 131 ft (40 m) and 10 seconds at 300 ft (90 m) — that is how long the detector takes to declare a pan fire at that distance. Ultra-fast response is under 1 second at 100 ft (30 m) on the analog voltage output, the mode used where the hazard is a flash fire. High-speed response is 50 ms for a 1 ft (0.3 m) LPG/air explosion at 66 ft (20 m). A specification that says "fast" without naming which of these three it means is not comparable to another detector's datasheet.
Field of view, and where hydrogen differs
For conventional fuels the field of view is 80 degrees horizontal by 80 degrees vertical. The hydrogen channel is different: 90 by 90, because the hydrogen flame's radiation and the optical path that detects it are not the same as a hydrocarbon pool fire. That is also the reason the hydrogen capability is a distinct model rather than an option applied to a standard IR detector.
What makes it survive a plant
The operating range is -76 to +185 °F (-60 to +85 °C) — a cold-start figure that matters on an LNG or a northern-latitude site — with non-condensing humidity to 100 percent. It is SIL3 compatible, certified for hazardous areas worldwide, factory calibrated so it works in an existing detection system without a site calibration, and it carries a smart field-of-view integrity test so a blocked or dirty window is detected as a fault rather than silently reducing coverage. Power at 24 Vdc is 100 mA (2.2 W) in normal operation without a heater, rising to 280 mA (7.6 W) in standard heater mode with alarm.
Where it fits
Fuel storage and tank farms, loading racks, turbine and compressor enclosures, and hydrogen-handling areas — anywhere the detector has to look a long way across an open area and still tell a fire from a welding arc, sunlight or a hot surface. Six sensitivity ranges let one model serve both a large outdoor area and a smaller enclosure without a different part number.
Manufacturer reference: Rosemount 975 Flame Detectors Product Data Sheet, 975HR detection ranges and general specifications.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | Detection at the highest sensitivity on a 1 ft2 pan fire: gasoline and n-heptane 300 ft (90 m), diesel and kerosene 207 ft (63 m), alcohol and IPA 185 ft (55 m); coverage area 58,405 ft2 (5,426 m2) |
| Output signal | Alarm and fault outputs to the fire and gas system, with analog voltage output used for the ultra-fast and high-speed response modes; 24 Vdc power at 100 mA (2.2 W) without heater |
| Diagnostics | Smart field of view integrity test detects a blocked or dirty window as a fault rather than a silent loss of coverage; SIL3 compatible and certified for hazardous areas worldwide |
| Pressure range | Not applicable to the sensing function; the detector is housed for hazardous area service and mounted on a bracket or field of view limiter rather than installed in the process |
| Variants | 975HR with QuadSense triple infrared and hydrogen detection; six sensitivity ranges; field of view 90 x 90 degrees on hydrogen and 80 x 80 degrees for other fuels |
| Application | Long range flame detection in fuel storage and tank farms, loading racks, turbine and compressor enclosures and hydrogen handling areas, where the detector must look across an open area and reject welding, sunlight and hot surfaces |
| Mounting | Bracket mounted with a field of view limiter available as an accessory; factory calibrated so it commissions into an existing detection system without site calibration |
| Operating temperature (°C) | -76 to +185 F (-60 to +85 C) operating and storage, with non-condensing relative humidity up to 100% |