Rosemount 975UF Flame Detector
Purchase options
From$1,561.45
- Availability
- Call for availability Originalx
Configurable — choose options to build the exact part number.
Independent supplier
Sproh is an independent supplier and is not an authorized distributor or official representative of Rosemount or Emerson.
Overview
Ultraviolet/infrared flame detector for explosive and fast fires: 20 ms flash response, hydrogen and silane detection, SIL3 compatible.
Key features
- Ultraviolet/infrared flame detector with hydrogen and silane detection, the fastest responder in the 975 family
- Ultra-fast response 20 ms for a flash pan fire at 10 ft (3 m); 50 ms for an LPG/air explosion at 32.8 ft (10 m)
- Range 93 ft (28 m) for gasoline against 300 ft for the IR3 models - speed is bought with reach, and the page says so
- UV 0.185 to 0.260 micrometres plus IR 2.5 to 3.0 micrometres; both must agree to alarm
- Silane 67 ft (20 m), hydrogen 70 ft (21 m), ammonia 30 ft (9 m); three sensitivity ranges; field of view 100 x 95 degrees
- Operating range -76 to +185 F (-60 to +85 C), SIL3 compatible, hazardous area certified, 120 mA (2.9 W) at 24 Vdc
Key specifications
- Accuracy
- Detection at 1 ft2 pan fire: gasoline 93 ft (28 m), methane and LPG 60 ft (18 m), hydrogen 70 ft (21 m), silane 67 ft (20 m), ammonia 30 ft (9 m); coverage area 6,900 ft2 (641 m2)
- Output signal
- Alarm and fault outputs with analog voltage output for the ultra-fast and high-speed modes; 24 Vdc at 120 mA (2.9 W) normal, up to 320 mA (7.7 W) heater with alarm
- Diagnostics
- Smart field of view integrity test reports a blocked window as a fault; SIL3 compatible and certified for hazardous areas; both UV and IR signatures must agree before an alarm
- Pressure range
- Not applicable to the sensing function; the detector is housed for hazardous area service and bracket mounted outside the process
- Variants
- 975UF ultraviolet/infrared with hydrogen and silane detection; three sensitivity ranges; field of view 100 degrees horizontal by 95 degrees vertical; spectral response UV 0.185-0.260 um plus IR 2.5-3.0 um
- Application
- Explosive and fast-developing fire risks: gas cloud and flash fire scenarios, energetic material handling, hydrogen and silane processes, and enclosures where detection must be faster than the fire grows
Speed instead of reach: the UV/IR detector for fires that are over before an IR3 has decided
The Rosemount 975UF is the ultraviolet/infrared member of the 975 family. Where the IR3 models look a long way across a tank farm, the UF answers a different question — how fast can a detector declare a fire — and the answer is 20 milliseconds for a flash pan fire at 10 ft (3 m) on the analog output. It is the model for explosive and fast-developing fires, and the price of that speed is range.
What UV adds to IR
An ultraviolet channel responds over 0.185 to 0.260 micrometres, and the UF's infrared channel covers 2.5 to 3.0 micrometres — bands a hydrocarbon flame emits strongly and which daylight does not reach the ground in (the solar-blind principle). Combining UV with IR means the detector requires both signatures to agree, so an arc welding source that fools a UV-only detector, or a hot surface that fools an IR-only one, does not produce an alarm. The UF also carries the hydrogen channel and is the only 975 model with a silane detection range — 67 ft (20 m) — which is why it turns up in semiconductor and solar manufacturing rather than only in fuel storage.
The range trade, stated plainly
On the same 1 ft² pan fire the UF sees gasoline at 93 ft (28 m) where the IR3 models see 300 ft, methane and LPG at 60 ft (18 m), hydrogen at 70 ft (21 m). Coverage falls to 6,900 ft² (641 m²) against 68,200 ft² for the MR. That is not a defect; it is the consequence of a detector tuned to answer in tens of milliseconds. A layout that needs both — wide area at distance and fast local response — uses both models, and the coverage figures are what decide where each one goes.
Three response figures again
Standard response is typically 5 seconds at 93 ft (28 m). Ultra-fast response is 20 ms for a flash pan fire from 10 ft (3 m) via the analog voltage output. High-speed response is 50 ms for a 1 ft (0.3 m) LPG/air explosion at 32.8 ft (10 m). For a flash fire or a gas cloud ignition, the 20 ms figure is the one that gets the deluge valve open while there is still something to protect.
Field of view and settings
The UF has a 100 degree horizontal by 95 degree vertical field of view — the same optics envelope as the MR — with three sensitivity ranges rather than six, because a UV/IR detector's operating margins are set differently. The same accessory range applies: bracket mounting and a field of view limiter.
Environment and power
Operating range is -76 to +185 °F (-60 to +85 °C), non-condensing humidity to 100 percent, SIL3 compatible and certified for hazardous areas, factory calibrated. Power at 24 Vdc is 120 mA (2.9 W) in normal operation, 180 mA (4.3 W) in low power heater mode with alarm and 320 mA (7.7 W) in standard heater mode with alarm.
Where it fits
Explosive and fast-developing fire risks: gas cloud and flash fire scenarios, munitions and energetic material handling, hydrogen and silane processes, and any enclosure where the detection has to be faster than the fire grows. For the long open-area coverage that a tank farm needs, the IR3 models are the right tool and this detector is the complement to them rather than a substitute.
Manufacturer reference: Rosemount 975 Flame Detectors Product Data Sheet, 975UF detection ranges and general specifications.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | Detection at 1 ft2 pan fire: gasoline 93 ft (28 m), methane and LPG 60 ft (18 m), hydrogen 70 ft (21 m), silane 67 ft (20 m), ammonia 30 ft (9 m); coverage area 6,900 ft2 (641 m2) |
| Output signal | Alarm and fault outputs with analog voltage output for the ultra-fast and high-speed modes; 24 Vdc at 120 mA (2.9 W) normal, up to 320 mA (7.7 W) heater with alarm |
| Diagnostics | Smart field of view integrity test reports a blocked window as a fault; SIL3 compatible and certified for hazardous areas; both UV and IR signatures must agree before an alarm |
| Pressure range | Not applicable to the sensing function; the detector is housed for hazardous area service and bracket mounted outside the process |
| Variants | 975UF ultraviolet/infrared with hydrogen and silane detection; three sensitivity ranges; field of view 100 degrees horizontal by 95 degrees vertical; spectral response UV 0.185-0.260 um plus IR 2.5-3.0 um |
| Application | Explosive and fast-developing fire risks: gas cloud and flash fire scenarios, energetic material handling, hydrogen and silane processes, and enclosures where detection must be faster than the fire grows |
| Mounting | Bracket mounted with field of view limiter accessory; factory calibrated for immediate use in an existing detection system |
| Operating temperature (°C) | -76 to +185 F (-60 to +85 C) operating and storage, non-condensing relative humidity up to 100% |