Rosemount A0701PBU Wireless SmartPower Blue Power Module
Purchase options
$136.74
- Availability
- Call for availability Originalx
Independent supplier
Sproh is an independent supplier and is not an authorized distributor or official representative of Rosemount or Emerson.
Overview
Intrinsically safe SmartPower Blue Power Module: 7.2 V lithium primary cell, up to 10 years at a one-minute update rate, changeable in a hazardous area.
Key features
- SmartPower Blue Power Module for wireless transmitters: a 7.2 V lithium-thionyl chloride primary cell in a PBT enclosure, 405 g, with a keyed connector
- The up to ten year life is quoted at a one-minute update rate, and the datasheet names the three variables: wireless update rate as the main driver, extreme temperature, and wireless network conditions - which is why an online life estimator exists instead of a single figure
- It doubles the lifetime of the Black Power Module and is specified as its replacement in energy-intensive applications: fast updates, cold locations, or positions at the edge of the mesh where retries cost radio energy
- Intrinsically safe, so it can be changed in a hazardous area without removing the transmitter from the process, and the keyed connection means it cannot be fitted the wrong way round
- An extended cover is required because the module is physically larger, and the module is currently available only as a spare part - a module ordered alone arrives with nothing to close the housing over it
- The module declares approximately 10 g of lithium metal on its own label, which makes it a hazardous article for transport with a safety data sheet, and the label forbids recharging, disassembly, heating above 100 C, incineration and contact with water
Key specifications
- Accuracy
- Not a measuring device. Its performance figure is energy: rated voltage 7.2 V, lithium-thionyl chloride primary cell, 405 g (0.89 lb) in a polybutylene terephthalate enclosure, with short circuit protection and EMC to EN 61326-1 and EN 61326-2-3
- Output signal
- Not applicable. The connection is keyed so the module cannot be fitted the wrong way round, which is a mechanical fail-safe rather than a procedure, and the transmitter reports low power module level so replacement is planned from an alert rather than discovered when a device goes silent
- Diagnostics
- The Blue module doubles the lifetime of the Black Power Module and is specified as its replacement in energy-intensive applications - fast updates, cold locations, or positions where retries cost radio energy. It is intrinsically safe so it can be changed in a hazardous area without removing the transmitter from the process. The module's own label declares approximately 10 g of lithium metal, which makes it a hazardous article for transport with a safety data sheet, and forbids recharging, disassembly, heating above 100 C, incineration and contact with water
- Pressure range
- Not applicable - an internal power module with no process connection and no wetted parts
- Application
- Wireless transmitters in energy-intensive duty: fast update rates on pressure and flow, cold climates and unheated structures, remote wellheads and tank farms at the edge of the mesh, and any instrument where a battery change means an entry permit
- Mounting
- Replaced in the housing of the compatible wireless transmitter. An extended cover is required because the Blue module is physically larger, and the module is currently available only as a spare part - ordered alone it arrives with nothing to close the housing over it
“Up to ten years” is a function of three variables, and only one of them is the battery
The Rosemount A0701PBU is the SmartPower Blue Power Module: a 7.2 V lithium-thionyl chloride primary cell in a polybutylene terephthalate enclosure, 405 g (0.89 lb), with a keyed connector, intrinsically safe so that it can be changed in a hazardous area, and rated for a life of up to ten years.
Ten years is the headline and it comes with conditions that decide whether you get them. The datasheet states them plainly: the life figure is quoted at a one-minute update rate, and power module life for a given transmitter is mainly a function of the wireless update rate, with extreme temperature and wireless network conditions also taking their share.
The three variables
Update rate. A wireless transmitter spends most of its energy on the radio, and it transmits once per update. Halving the interval roughly doubles the radio work per day. This is why the same module can last a decade on a slow tank level and a fraction of that on a fast pressure loop — and why the first question about a battery life claim should always be at what update rate.
Temperature. A lithium primary cell loses capacity faster at temperature extremes, in both directions. A module on a sunlit pipe in summer and a module on an unheated Christmas tree in winter are both spending more than the datasheet's nominal case.
Network conditions. A device far from the mesh, or one whose neighbours come and go, retries more and routes through more hops. Every retry is radio energy. This is the variable that surprises people, because it is not a property of the site — it is a property of the radio path, and it can change when a structure goes up or a node is removed.
Because the answer depends on three variables and the specific device, Emerson publishes an online Power Module Life Estimator rather than a single number. That is not a marketing hedge; it is the honest form of the calculation, and it is worth running before promising a maintenance interval to a plant.
Why this module exists alongside the black one
The Blue module is specified as a replacement for the Black Power Module in energy-intensive applications and is described as doubling its lifetime. The applications that qualify are the ones where the three variables above are working against you: fast update rates, cold locations, and positions at the edge of the mesh.
That makes the selection a straight comparison rather than a preference. If the device updates slowly in a temperate sheltered spot with good neighbours, the standard module is the cheaper answer. If it updates quickly, or sits in the cold, or retries constantly, the blue module is not an upgrade — it is the only one that reaches the maintenance interval the site expects.
Changing it is the point
The module is intrinsically safe, which in practice means it can be replaced in a hazardous area and the transmitter does not have to be removed from the process. For a device on a live hydrocarbon line, that is the difference between a battery change and a shutdown with a work permit, a gas test and a re-commissioning.
Two design details support it. The connection is keyed, so the module cannot be fitted the wrong way round — a fail-safe mechanical decision rather than a procedure. And the transmitter reports low power module level, so the replacement is planned from an alert rather than discovered when a device goes silent.
One ordering trap: the cover
Because the blue module is physically larger, it requires an extended cover. The datasheet notes that the module is only available as a spare part at this time, and that the extended cover is required to accommodate the larger size.
So a spare module ordered on its own arrives with nothing to close the housing over it. Order the cover with the first module, or confirm the housing already has one, and label the instrument so the next technician knows which module belongs in it — because a standard cover will not fit and looks, briefly, like it might.
It is a lithium cell, and that has consequences
The label on the module itself declares approximately 10 g of lithium metal, and the warnings around it are the ones that matter to a technician and to a shipping clerk: do not recharge, do not disassemble, do not heat above 100 °C, do not incinerate, do not expose the contents to water. The datasheet is accompanied by a material safety data sheet, and the module is a hazardous article for transport rather than a box of hardware.
That affects spares planning in a way that catches sites out: a module cannot be flown or shipped on the same terms as an O-ring, and a cabinet full of them is a stored-energy inventory with its own fire response. Keep the MSDS with the spares, and keep the count low enough to be defensible.
Where it fits
Wireless transmitters in energy-intensive duty: fast update rates on pressure and flow, cold climates and unheated structures, remote wellheads and tank farms at the edge of the mesh, and any instrument where a battery change means an entry permit. It is also the sensible first module for a device whose life estimate is marginal, because the cost difference is small against the cost of an unplanned site visit.
Manufacturer reference: Rosemount SmartPower Solutions Blue Power Module data sheet for life expectancy, rated voltage, cell chemistry, weight, temperature and humidity limits, compatibility list, certifications and ordering information.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | Not a measuring device. Its performance figure is energy: rated voltage 7.2 V, lithium-thionyl chloride primary cell, 405 g (0.89 lb) in a polybutylene terephthalate enclosure, with short circuit protection and EMC to EN 61326-1 and EN 61326-2-3 |
| Output signal | Not applicable. The connection is keyed so the module cannot be fitted the wrong way round, which is a mechanical fail-safe rather than a procedure, and the transmitter reports low power module level so replacement is planned from an alert rather than discovered when a device goes silent |
| Diagnostics | The Blue module doubles the lifetime of the Black Power Module and is specified as its replacement in energy-intensive applications - fast updates, cold locations, or positions where retries cost radio energy. It is intrinsically safe so it can be changed in a hazardous area without removing the transmitter from the process. The module's own label declares approximately 10 g of lithium metal, which makes it a hazardous article for transport with a safety data sheet, and forbids recharging, disassembly, heating above 100 C, incineration and contact with water |
| Pressure range | Not applicable - an internal power module with no process connection and no wetted parts |
| Application | Wireless transmitters in energy-intensive duty: fast update rates on pressure and flow, cold climates and unheated structures, remote wellheads and tank farms at the edge of the mesh, and any instrument where a battery change means an entry permit |
| Mounting | Replaced in the housing of the compatible wireless transmitter. An extended cover is required because the Blue module is physically larger, and the module is currently available only as a spare part - ordered alone it arrives with nothing to close the housing over it |
| Operating temperature (°C) | Extreme temperature is one of the three variables that reduce life, in both directions. A module on a sunlit pipe in summer and one on an unheated structure in winter are both spending more than the nominal case, and humidity limits are 0 to 100 percent relative humidity |
| Measuring range | Not applicable. Life expectancy is up to ten years at a one-minute update rate, and the datasheet names the three drivers: wireless update rate as the main one, extreme temperature, and wireless network conditions. The online Power Module Life Estimator exists because the answer depends on those three and on the specific device |
Documents
Accessories and related items
Accessories and related items for this product are not available to order on Sproh yet. If the manufacturer lists them, an engineer can source them for you.
Ask an engineer