Rosemount FS Series Flame Simulators
Purchase options
From$2,365.58
- Availability
- Call for availability Originalx
Configurable — choose options to build the exact part number.
Independent supplier
Sproh is an independent supplier and is not an authorized distributor or official representative of Rosemount or Emerson.
Overview
Handheld flame simulators that emit each detector's own pattern for end-to-end proof testing, 40 ft range, ATEX Zone 1/2 and dust, 100 tests per charge.
Key features
- Handheld battery-powered flame simulator that emits the detector's own sequential radiation pattern, so the test exercises discrimination logic rather than just the sensor
- Tests the full chain: sensor, internal electronics, alarm activation software, window cleanliness, wiring integrity and relay operation - which a built-in test cannot represent
- Three families that are not interchangeable: FS-HR-975 for triple IR, FS-IR-975 for 975MR and 965 multi-spectrum IR, FS-UV/IR-975 for 975UF and 975UR units
- Range up to 40 ft (12 m), so a detector mounted at height can be tested from floor or deck level with no scaffold, ladder or hot-work permit
- ATEX-certified EExd for Zone 1 and Zone 2 plus Zones 21 and 22 dust - the simulator itself goes into the hazardous area
- Rechargeable lithium-ion battery, at least 100 tests per charge, with charger and battery nut removal tool in the standard kit and a spare battery kit available
Key specifications
- Accuracy
- Not an accuracy specification: the validity of the test comes from emitting the detector's own sequential radiation pattern, so the detector's discrimination logic is exercised rather than only its sensor
- Output signal
- An optical radiation signature in a unique sequential pattern per detector family. Detection range up to 40 ft (12 m), with per-detector ranges published in the datasheet because the range belongs to the simulator-detector pair
- Diagnostics
- Tests the chain a built-in optical test cannot represent: sensor, internal electronics, alarm activation software, viewing window cleanliness, wiring integrity and actual relay operation. A simulator matched to the wrong detector family either fails to trip it or trips it without representing the intended test, which is worse than no test at all
- Pressure range
- Not applicable - a handheld test instrument, not a process device
- Variants
- FS-HR-975 for triple infrared (IR3) detectors, FS-IR-975 for multi-spectrum infrared 975MR and 965 units, FS-UV/IR-975 for 975UF and 975UR ultraviolet/infrared units. Rechargeable lithium-ion battery with at least 100 tests per charge; spare battery kit and 16.8 V charger available separately
- Application
- Periodic proof-testing of Rosemount flame detectors on process units, tank farms, loading terminals and turbine enclosures, where the fire detection system is subject to loop testing by a local standard or an insurer
The only way to test the whole chain, and it has to match the detector
The Rosemount FS-975 flame simulators are handheld, battery-powered test units for Rosemount flame detectors. They emit electromagnetic radiation in a unique sequential pattern that the matching detector recognises as fire, so the detector can be tested under real-fire conditions without a fire — and, more importantly, tested end to end.
What a built-in test proves, and what it does not
An optical test built into a flame detector proves two things: the window is clean enough to pass light, and the sensor responds to light. Both matter, and both are a fraction of the system. The chain that actually has to work in a fire is longer: sensor, internal electronics, alarm activation software, viewing window cleanliness, wiring integrity, relay operation and the panel behind it. The datasheet lists exactly that sequence as what the external simulator exercises, and the reason is structural — a built-in source sits inside the same housing as the thing being tested.
An external simulator also tests the detector's discrimination logic, not just its photodiode. A flame detector's job is to ignore a welding arc, a hot surface and sunlight while responding to a flame, and that discrimination lives in the sequential pattern the electronics look for. A simulator that emitted a steady IR glow would trip a poorly functioning detector and prove nothing. Emitting the detector's own signature is what makes the test a test.
Matching the simulator to the detector is a specification, not a formality
The range covers three detector families and the codes are not interchangeable:
| Simulator | For |
|---|---|
| FS-HR-975 (triple IR, IR3) | Triple infrared detectors |
| FS-IR-975 (multi-spectrum IR) | 975MR and 965 multi-spectrum infrared units |
| FS-UV/IR-975 | 975UF and 975UR ultraviolet/infrared units |
Because the pattern is specific, a simulator aimed at the wrong family either fails to trip the detector or trips it in a way that does not correspond to the test it is supposed to represent. Either outcome is worse than no test: one produces a false pass on a safety device, and the other produces a false failure that gets written up as an instrument problem. The datasheet carries a table of detection ranges per detector and simulator pairing for the same reason — the range is a property of the pair, not of the lamp.
The simulator has to be safe in the area it is used in
It is ATEX-certified EExd for Zone 1 and Zone 2, with approvals covering Zones 21 and 22 for dust. This is easy to overlook because the simulator feels like test equipment rather than plant equipment — but it goes into the same hazardous area as the detector it tests, and a technician has to carry it there. A general-purpose test lamp is not an acceptable substitute, whatever its output spectrum.
Range, and why 40 feet decides whether testing happens
The units activate detectors at a range up to 40 ft (12 m). On a plant this is the feature that determines whether the periodic test is actually performed: a detector mounted at height is reachable from floor or deck level with the simulator, so the test needs no scaffold, no ladder and no hot-work permit. A test that requires access equipment gets deferred; a test that one person can perform from the deck gets done on the schedule — and a documented, repeatable test is what an auditor asks for.
The practical budget: 100 tests per charge
The simulator runs on a rechargeable lithium-ion battery and operates for at least 100 tests before recharging. On a site with a few dozen detectors that is a full round on one charge, and it is the number to plan a turnaround around rather than the number to discover mid-round. The standard kit includes the charger and a battery nut removal tool, and a spare battery kit is available separately — which on a campaign of testing is the difference between one shift and two.
Where it fits
Periodic proof-testing of Rosemount flame detectors on process units, tank farms, loading terminals, turbine enclosures and any installation where a fire detection system is subject to loop testing by a local standard or an insurer. It belongs in the maintenance plan next to the detectors themselves, matched to the detector families actually installed, with a spare battery and the charger treated as part of the kit rather than as an accessory.
Manufacturer reference: Rosemount FS-975 Flame Simulators Product Data Sheet 00813-0300-4975 for model codes, detection ranges per detector, certifications and kit contents.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | Not an accuracy specification: the validity of the test comes from emitting the detector's own sequential radiation pattern, so the detector's discrimination logic is exercised rather than only its sensor |
| Output signal | An optical radiation signature in a unique sequential pattern per detector family. Detection range up to 40 ft (12 m), with per-detector ranges published in the datasheet because the range belongs to the simulator-detector pair |
| Diagnostics | Tests the chain a built-in optical test cannot represent: sensor, internal electronics, alarm activation software, viewing window cleanliness, wiring integrity and actual relay operation. A simulator matched to the wrong detector family either fails to trip it or trips it without representing the intended test, which is worse than no test at all |
| Pressure range | Not applicable - a handheld test instrument, not a process device |
| Variants | FS-HR-975 for triple infrared (IR3) detectors, FS-IR-975 for multi-spectrum infrared 975MR and 965 units, FS-UV/IR-975 for 975UF and 975UR ultraviolet/infrared units. Rechargeable lithium-ion battery with at least 100 tests per charge; spare battery kit and 16.8 V charger available separately |
| Application | Periodic proof-testing of Rosemount flame detectors on process units, tank farms, loading terminals and turbine enclosures, where the fire detection system is subject to loop testing by a local standard or an insurer |
| Mounting | Handheld with a pistol grip, aimed at the detector from floor or deck level. The standard kit includes the charger and a battery nut removal tool |
| Operating temperature (°C) | Carried into the hazardous area it tests: ATEX-certified EExd for Zone 1 and Zone 2, with approvals covering Zones 21 and 22 for dust |
Documents