Rosemount Incus Ultrasonic Gas Leak Detector

Part numberGDU-IncusManufacturerEmerson

Purchase options

From$7,956.65

Availability
Call for availability Originalx
Select option

Configurable — choose options to build the exact part number.

Independent supplier

Sproh is an independent supplier and is not an authorized distributor or official representative of Rosemount or Emerson.

Overview

Ultrasonic gas leak detector with four acoustic sensors: detects pressurized gas releases in under a second, 40 m coverage in low noise, 316 stainless enclosure.

Key features

  • Ultrasonic gas leak detector with four independent acoustic sensors, model GDU-Incus
  • Detects toxic, combustible and inert pressurized gas releases within one second
  • Detection band 25 to 100 kHz; coverage 40 m in low noise (~54 dB) and 20 m in high noise (~74 dB)
  • Immune to poisoning, wind direction, gas dilution and stratification
  • 4-20 mA (0-2 mA fault) with two form C relays and HART standard; 24 Vac (15 to 30 Vdc) at 6 W
  • AISI 316 stainless steel enclosure, IP66/IP67 and Type 4X, -40 to 85 C standard or -55 C heated

Key specifications

Accuracy
Output follows the highest ultrasound signal measured by any one of the four heads; 4-20 mA mapped to a 40-200 dB scale or the standard 40-120 dB scale, so the reading is acoustic intensity rather than gas concentration
Output signal
4-20 mA with 0-2 mA fault outputs, two form C relay contacts (configurable alarm and configurable fault) and HART protocol as standard; response instantaneous, under 1 second on the HART output, with a customer programmable alarm delay in 1 second increments
Power supply
24 Vac nominal, operating 15 to 30 Vdc; 6 W during normal operation on the standard unit, heated unit up to 1.5 A at maximum display brightness with heaters at full current
Diagnostics
Continuous electronic self-test of sensor integrity; four independent sensing heads so a failed head degrades coverage rather than removing it, with a dedicated test transmitter available for proof testing without releasing gas
Certifications
Certified for hazardous locations worldwide, with ATEX low temperature and EAC certification options; cable entry 1 in. NPT signal entry or double M20 entry where certification allows; 36 month warranty
Measurement range
Detection frequency band 25 kHz to 100 kHz; coverage 40 m in low noise applications (~54 dB) and 20 m in high noise applications (~74 dB)
See all specifications