Overview
IO-Link master for PROFINET or EtherNet/IP in four and eight port versions. Class A ports with a digital input on pin 2, 3.6 A total sensor supply.
Key features
- IO-Link master for PROFINET (FB-5104 four port, FB-5108 eight port) or EtherNet/IP (FB-5204, FB-5208)
- All IO-Link ports are Class A, so every port also exposes a digital input on pin 2 - 16 inputs on the eight-port master, 8 on the four-port
- Class B actuators such as IO-Link valve manifolds need an isolated auxiliary supply these Class A ports do not provide
- Digital outputs: 4 on the four-port and 8 on the eight-port, 200 mA each and short-circuit protected
- Sensor supply is a 3.6 A TOTAL for the module from a 20 to 28 V DC SELV/PELV supply - sum the sensor currents before filling all eight ports
- PROFINET RT device with a two-port switch on X21/X22, so masters can be daisy chained or ringed without an external switch
Key specifications
- Accuracy
- Not a measurement device: the master carries digital process values unchanged. What it determines is whether the sensor's value reaches the controller with the right port configuration, which is why the IO-Link Assistant (FB-5401) matters before first start-up
- Output signal
- PROFINET RT (FB-5104, FB-5108) or EtherNet/IP (FB-5204, FB-5208) to the controller; IO-Link Class A on the sensor ports with a digital input on pin 2 of each
- Diagnostics
- All ports are Class A. A Class B actuator - an IO-Link valve manifold or motor starter - needs the isolated auxiliary supply on pins 2 and 5 that a Class A port does not provide, so sensors work here while some actuators will not. Digital outputs: 4 on the four-port and 8 on the eight-port at 200 mA each, short-circuit protected
- Pressure range
- Not applicable - a DIN-rail mounted communication module with no process connection and no wetted parts
- Variants
- FB-5104 four port and FB-5108 eight port for PROFINET; FB-5204 four port and FB-5208 eight port for EtherNet/IP. Digital inputs: 8 on the four-port and 16 on the eight-port, switching level 11 to 28 V high and 0 to 5 V low, short-circuit protected
- Application
- Connecting IO-Link instruments to a PROFINET or EtherNet/IP control system on machines and skids; also brings the discrete signals that ride on the same M12 cable into the controller
Four or eight ports, and the pin that does two jobs
The Rosemount IO-Link Masters connect IO-Link sensors to a control system over PROFINET or EtherNet/IP, in four-port and eight-port versions: FB-5104 and FB-5108 for PROFINET, FB-5204 and FB-5208 for EtherNet/IP. They are small, DIN-rail mounted, and they are the piece that turns a digital sensor into something a PLC can actually use.
Class A is the specification that decides whether your device works
All ports on these masters are IO-Link Class A. That is not a version number — it describes the pin assignment. A Class A port carries IO-Link communication on pin 4 and a digital input on pin 2. A Class B port adds an isolated auxiliary supply on pins 2 and 5 so that an actuator with its own power requirement — a valve manifold, a motor starter — can be driven from the same port without sharing the master's supply.
The consequence is a selection error that only appears at commissioning: sensors are Class A devices and work on these masters. Some actuators are Class B, and a Class B actuator on a Class A port has no isolated supply to run from. If the application includes IO-Link valves or actuators rather than instruments, check the class before ordering, because the port count and the protocol are the obvious questions and this is the one that decides it.
Pin 2, and why each port is two signals
Because of that Class A pinout, every IO-Link port also exposes a digital input on pin 2 — 16 inputs on the eight-port master and 8 on the four-port — with switching levels of 11 to 28 V for high and 0 to 5 V for low, short-circuit protected. In practice a single M12 cable can carry an IO-Link measurement and a discrete state at the same time, and that is how a flow switch, a level limit or an interlock gets into the control system without a second cable run to the field.
The masters also carry digital outputs: four on the FB-5104 and eight on the FB-5108, at 200 mA per output with short-circuit protection. That is enough for a lamp, a relay input or a small solenoid, so a port does not have to be given up to switch something trivial.
Power, and the total that matters
Supply is 20 to 28 V DC, SELV or PELV only, and the sensor supply carries a total maximum load of 3.6 A — the number that gets overlooked when eight sensors are specified onto one master. The budget is shared: sum the sensor currents before assuming an eight-port master will feed eight devices at their full draw, and note that the 3.6 A is a total for the module rather than a per-port allowance.
The two-port switch, which is the topology argument
The master is a PROFINET RT device (Class B conformance class) with a two-port switch on X21 and X22. That means it can be wired in a line — cable in, cable out, master to master — or in a ring for media redundancy, without an external switch in the cabinet. On a skid or a machine with several IO-Link masters, that removes a switch, its power supply and its cabinet space, and it makes the network layout follow the physical layout of the machine.
Where it fits
Any machine or skid with several IO-Link instruments where the control system speaks PROFINET or EtherNet/IP: hygienic measurement transmitters, level and flow sensors, and the digital inputs that come along with them. The configuration tool is the IO-Link Assistant (FB-5401), which reads device information and sets the port parameters — worth having on the engineering laptop before the first master arrives, since an IO-Link master with unconfigured ports looks like a network problem and is not one.
Manufacturer reference: Rosemount IO-Link Masters Product Data Sheet 00807-0200-7062 for ordering; reference manual 00809-0100-4114 for port classes, power budget and digital I/O tables.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | Not a measurement device: the master carries digital process values unchanged. What it determines is whether the sensor's value reaches the controller with the right port configuration, which is why the IO-Link Assistant (FB-5401) matters before first start-up |
| Output signal | PROFINET RT (FB-5104, FB-5108) or EtherNet/IP (FB-5204, FB-5208) to the controller; IO-Link Class A on the sensor ports with a digital input on pin 2 of each |
| Diagnostics | All ports are Class A. A Class B actuator - an IO-Link valve manifold or motor starter - needs the isolated auxiliary supply on pins 2 and 5 that a Class A port does not provide, so sensors work here while some actuators will not. Digital outputs: 4 on the four-port and 8 on the eight-port at 200 mA each, short-circuit protected |
| Pressure range | Not applicable - a DIN-rail mounted communication module with no process connection and no wetted parts |
| Variants | FB-5104 four port and FB-5108 eight port for PROFINET; FB-5204 four port and FB-5208 eight port for EtherNet/IP. Digital inputs: 8 on the four-port and 16 on the eight-port, switching level 11 to 28 V high and 0 to 5 V low, short-circuit protected |
| Application | Connecting IO-Link instruments to a PROFINET or EtherNet/IP control system on machines and skids; also brings the discrete signals that ride on the same M12 cable into the controller |
| Mounting | DIN rail in the cabinet. The two-port switch on X21 and X22 lets masters be wired in a line or a ring without an external switch, so the network topology can follow the machine |
| Operating temperature (°C) | Supply 20 to 28 V DC, SELV or PELV only, protection class III. Sensor supply total maximum load 3.6 A for the module - a shared budget, not a per-port allowance |
Documents
Accessories and related items
Accessories and related items for this product are not available to order on Sproh yet. If the manufacturer lists them, an engineer can source them for you.