Rosemount PowerVUE 4x5 Power Positioner
Purchase options
From$5,090.85
- Availability
- Call for availability Originalx
Configurable — choose options to build the exact part number.
Independent supplier
Sproh is an independent supplier and is not an authorized distributor or official representative of Rosemount or Emerson.
Overview
Hagan 4x5 torque type floor mounted damper drive with an integral digital valve controller: 400 ft-lb stall torque, ±0.5% repeatability, HART or fieldbus.
Key features
- Hagan pneumatic piston drive with an integral Fisher FieldVUE DVC5000/6000 digital valve controller
- Repeatability ±0.5% of full stroke; no-load full stroke 3 seconds for 5 in. stroke and 80 degrees
- Stall torque 400 ft-lb (542 N·m) at 100 psig; Emerson recommends applying a 60% factor for control response
- 4-20 mA with HART or FOUNDATION fieldbus input; ValveLink and AMS diagnostics
- Base assembly includes air filter-regulator 4505C21G03, clevis 174469 and manual IB-102-204
- Power air consumption 10 scfm steady state; explosion-proof, flameproof or intrinsically safe versions
Key specifications
- Accuracy
- Repeatability ±0.5% of full stroke or better; no load full stroke time 3 seconds for the 5 in. stroke and 80 degrees of rotation
- Output signal
- Stall torque 400 ft-lb (542 N·m) at 100 psig; maximum friction load 50% of control torque and maximum weight load 140 ft-lb (189 N·m); Emerson recommends a 60% factor on stall torque for fast control response
- Diagnostics
- Integral FieldVUE DVC5000/6000 with ValveLink and AMS diagnostics; single master module replaceable without disconnecting wiring or tubing; optional 4-20 mA position transmitter on HART versions and two SPDT limit switches
- Pressure range
- Air supply 45 to 100 psig (310 to 689 kPa gauge) with 100 psig recommended; power air consumption 10 scfm steady state, an order of magnitude above the pneumatic drives in this family
- Variants
- Basic assembly in brass or stainless steel with standard, manual lock or mechanical air lock configuration; digital valve controller as HART, fieldbus with or without basic control suite, or supplied by others
- Application
- Fan and damper actuation in utilities, steel mills, refineries, pulp and paper and wastewater aeration blowers, where closed loop positioning and instrument diagnostics are required
A Hagan piston drive with a digital positioner where the pneumatic relay used to be
The PowerVUE 4x5 torque type floor mounted drive keeps the Hagan actuator — the double-acting piston, the 5 inch stroke and the 80 degree rotation — and replaces the mechanical force-balance positioner with a Fisher FieldVUE DVC5000/6000 digital valve controller. The result is a damper drive that reports its own position, trend it, and can be diagnosed without taking the linkage apart.
Why the mechanical positioner is the weak point it replaces
A traditional positioner balances an input diaphragm against a feedback spring through a pneumatic relay. As those parts get dirty the drive begins to stick and then hunt for setpoint, so the controlled variable sits above or below target and the linkage and damper take the wear. The PowerVUE converts the incoming 4-20 mA or fieldbus signal and reads actual actuator travel from an independent feedback transducer, so the drive moves to the setpoint the control system demands rather than to the position a spring says it should be at.
Repeatability and the torque rule
Repeatability is ±0.5 percent of full stroke, and no-load full stroke time is 3 seconds for the 5 inch stroke and 80 degrees. Stall torque is 400 ft-lb (542 N·m) at 100 psig, maximum friction load is 50 percent of control torque, and maximum weight load is 140 ft-lb. Emerson's own guidance on this family is worth repeating: apply a 60 percent factor to the published stall torque to keep control response fast, and the positioners are not recommended for reversing loads or heavy mass loads. A 400 ft-lb drive is therefore the right answer for a damper that needs about 240 ft-lb in service.
Air consumption is the honest number
Power air consumption is 10 scfm steady state — an order of magnitude above the pneumatic drives in this family, because the digital controller vents continuously to hold position. On a plant with a marginal instrument air header that is the specification that decides whether this product fits, not the torque rating.
Diagnostics
HART versions give setup and diagnostics through a Rosemount 375 communicator or ValveLink software, and AMS can collect the data. ValveLink advanced diagnostics store an as-found signature and compare it against a later one, so friction and load changes are visible before they become a stuck damper. The master module is a single replaceable part, swapped without disconnecting wiring or tubing.
What the base price includes
Unlike the pneumatic models in this family, the base assembly includes the air filter-regulator (4505C21G03), the clevis (174469) and the instruction manual IB-102-204. Options are a manual lock, a mechanical air lock that holds the drive on loss of plant air, two SPDT limit switches, a 4-20 mA electric position transmitter on HART versions, a minimum limit stop, and an anti-condensation heater (115 V, 150 W, not for hazardous areas). Digital communication is HART or FOUNDATION fieldbus, the latter also offering PID loop control in the drive.
Environment and area classification
Ambient temperature without the heater is 40 to 122 °F (4 to 50 °C), with 140 °F (60 °C) allowed under increased maintenance; with the heater the lower limit drops to -10 °F (-23 °C). The controller is available explosion-proof, flameproof or intrinsically safe, so the same drive covers ordinary and hazardous locations.
Where it fits
Utility and industrial boiler fan and damper service, steel mill and refinery dampers, pulp and paper, and aeration blowers in wastewater — anywhere the damper needs closed-loop positioning and the maintenance team wants the drive to say what is wrong with it.
Manufacturer reference: PowerVUE Product Data Sheet PDS 102-222.A01, 4 x 5 torque type floor mounted PVD 405 section.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | Repeatability ±0.5% of full stroke or better; no load full stroke time 3 seconds for the 5 in. stroke and 80 degrees of rotation |
| Output signal | Stall torque 400 ft-lb (542 N·m) at 100 psig; maximum friction load 50% of control torque and maximum weight load 140 ft-lb (189 N·m); Emerson recommends a 60% factor on stall torque for fast control response |
| Diagnostics | Integral FieldVUE DVC5000/6000 with ValveLink and AMS diagnostics; single master module replaceable without disconnecting wiring or tubing; optional 4-20 mA position transmitter on HART versions and two SPDT limit switches |
| Pressure range | Air supply 45 to 100 psig (310 to 689 kPa gauge) with 100 psig recommended; power air consumption 10 scfm steady state, an order of magnitude above the pneumatic drives in this family |
| Variants | Basic assembly in brass or stainless steel with standard, manual lock or mechanical air lock configuration; digital valve controller as HART, fieldbus with or without basic control suite, or supplied by others |
| Application | Fan and damper actuation in utilities, steel mills, refineries, pulp and paper and wastewater aeration blowers, where closed loop positioning and instrument diagnostics are required |
| Mounting | 4 x 5 torque type floor mounted; 1/4 in. NPT female air supply and signal connections; 80 lb (36 kg) typical weight, 95 lb shipping |
| Operating temperature (°C) | 40 to 122 F (4 to 50 C) without heater, 140 F (60 C) with increased maintenance; -10 to 122 F (-23 to 50 C) with the optional heater; operable to 100% relative humidity |
Documents
Accessories and related items
Accessories and related items for this product are not available to order on Sproh yet. If the manufacturer lists them, an engineer can source them for you.
Ask an engineer