Skip to main content
Sold and shipped by Sproh

Rosemount PowerVUE 6x10 Power Positioner

Part numberPowerVUE 6x10ManufacturerEmerson

Purchase options

From$8,504.74

Availability
Call for availability Originalx
Select option

Configurable — choose options to build the exact part number.

Independent supplier

Sproh is an independent supplier and is not an authorized distributor or official representative of Rosemount or Emerson.

Overview

Hagan 6x10 floor mounted damper drive with an integral digital valve controller: 1,800 ft-lb stall torque, ±0.5% repeatability, HART or fieldbus.

Key features

  • Hagan 6x10 floor mounted actuator with an integral Fisher FieldVUE DVC6000 digital valve controller
  • Stall torque 1,800 ft-lb (2,441 N·m); friction load 450 ft-lb; weight load 600 ft-lb; 10 in. stroke and 80 degrees
  • Repeatability ±0.5% of full stroke, against 1% for the pneumatic positioner on the same actuator
  • 4-20 mA with HART or FOUNDATION fieldbus; ValveLink and AMS diagnostics; single replaceable master module
  • Base assembly includes air filter-regulator 4505C21G03, clevis 174469 and manual IB-102-204
  • Manual lock and mechanical air lock assembly options in brass or stainless; heater and limit switch options

Key specifications

Accuracy
Repeatability ±0.5% of full stroke or better, against 1% for the pneumatic positioner on the same actuator; the actuator's unloaded full stroke is 5 seconds for the 10 in. stroke and 80 degrees on the pneumatic version
Output signal
Stall torque 1,800 ft-lb (2,441 N·m); maximum friction load 450 ft-lb (610 N·m); maximum weight load 600 ft-lb (814 N·m) over a 10 in. stroke producing 80 degrees of rotation
Diagnostics
ValveLink and AMS diagnostics through the DVC6000 with stored as-found signatures; single replaceable master module; optional 4-20 mA position transmitter with two limit contacts on HART versions
Pressure range
Air supply 45 to 120 psig (310 to 827 kPa gauge) with 100 psig recommended for the actuator; the digital controller vents continuously, and the published PowerVUE 4x5 figure of 10 scfm steady state is the order of magnitude to size the header by, not the 1 scfm of the pneumatic 6x10
Variants
Assembly in brass or stainless with manual lock and mechanical air lock combinations and polymer or stainless tubing; DVC6000 as HART, fieldbus with or without basic control suite, or supplied by others
Application
Forced and induced draft fan dampers and large secondary air or flue gas recirculation dampers on utility and industrial boilers, where a 4x5 runs out of torque and closed loop positioning with diagnostics is wanted
See all specifications