Overview
Hagan 6x10 floor mounted damper drive with an integral digital valve controller: 1,800 ft-lb stall torque, ±0.5% repeatability, HART or fieldbus.
Key features
- Hagan 6x10 floor mounted actuator with an integral Fisher FieldVUE DVC6000 digital valve controller
- Stall torque 1,800 ft-lb (2,441 N·m); friction load 450 ft-lb; weight load 600 ft-lb; 10 in. stroke and 80 degrees
- Repeatability ±0.5% of full stroke, against 1% for the pneumatic positioner on the same actuator
- 4-20 mA with HART or FOUNDATION fieldbus; ValveLink and AMS diagnostics; single replaceable master module
- Base assembly includes air filter-regulator 4505C21G03, clevis 174469 and manual IB-102-204
- Manual lock and mechanical air lock assembly options in brass or stainless; heater and limit switch options
Key specifications
- Accuracy
- Repeatability ±0.5% of full stroke or better, against 1% for the pneumatic positioner on the same actuator; the actuator's unloaded full stroke is 5 seconds for the 10 in. stroke and 80 degrees on the pneumatic version
- Output signal
- Stall torque 1,800 ft-lb (2,441 N·m); maximum friction load 450 ft-lb (610 N·m); maximum weight load 600 ft-lb (814 N·m) over a 10 in. stroke producing 80 degrees of rotation
- Diagnostics
- ValveLink and AMS diagnostics through the DVC6000 with stored as-found signatures; single replaceable master module; optional 4-20 mA position transmitter with two limit contacts on HART versions
- Pressure range
- Air supply 45 to 120 psig (310 to 827 kPa gauge) with 100 psig recommended for the actuator; the digital controller vents continuously, and the published PowerVUE 4x5 figure of 10 scfm steady state is the order of magnitude to size the header by, not the 1 scfm of the pneumatic 6x10
- Variants
- Assembly in brass or stainless with manual lock and mechanical air lock combinations and polymer or stainless tubing; DVC6000 as HART, fieldbus with or without basic control suite, or supplied by others
- Application
- Forced and induced draft fan dampers and large secondary air or flue gas recirculation dampers on utility and industrial boilers, where a 4x5 runs out of torque and closed loop positioning with diagnostics is wanted
The mid-size Hagan frame with a digital controller on the front
The PowerVUE 6x10 torque type floor mounted drive is the middle of the three PowerVUE sizes: the 6 inch cylinder and 10 inch stroke of the Hagan 6x10 actuator, 1,800 ft-lb of stall torque, and an integral Fisher FieldVUE DVC6000 digital valve controller in place of the pneumatic positioner. It is the drive for large fan and damper service where a 4x5 is too small and an 8x14 is overkill.
What changes when the positioner becomes digital
The actuator is the familiar Hagan piston unit, rated at 1,800 ft-lb (2,441 N·m) stall torque, 450 ft-lb (610 N·m) maximum friction load and 600 ft-lb (814 N·m) maximum weight load, with a 10 inch stroke producing 80 degrees of rotation. What changes is the control end: the pneumatic force-balance positioner, rated at 1 percent repeatability, is replaced by a DVC6000 that reads actuator travel from an independent feedback transducer and holds ±0.5 percent of full stroke. The drive therefore performs better than the actuator's own pneumatic specification, which is the whole point of the product.
Air consumption is the trade
A digital controller vents continuously to hold position, so air demand is the specification that decides whether this drive fits a plant. The published PowerVUE figure for the 4x5 frame is 10 scfm steady state — the pneumatic 6x10 positioner uses 1 scfm — and Emerson does not publish a separate consumption figure for the 6x10 PowerVUE. Treat the 4x5 number as the order of magnitude when sizing the instrument air header, not the pneumatic figure.
Diagnostics and communication
The DVC6000 is available with HART or FOUNDATION fieldbus, with ValveLink and AMS diagnostics on top: an as-found signature is stored at commissioning and compared later, so friction and load changes show up before the damper sticks. A single master module carries the electronics and is replaceable without disconnecting wiring or tubing. Fieldbus versions can also run PID loop control in the drive itself.
What is included
The base assembly includes the air filter-regulator (4505C21G03), the clevis (174469) and instruction manual IB-102-204, so unlike the pneumatic drives in this family there is no separate filter to order. Assembly options cover manual lock and mechanical air lock combinations in brass or stainless with polymer or stainless tubing, and a stainless engraved tag is available as an accessory.
Options and area classification
Options are two SPDT mechanical limit switches, a digital electronic position transmitter with two limit contacts on HART versions, and a 115 V 150 W heater with thermostat for condensation (not for hazardous areas). The controller is offered explosion-proof, flameproof or intrinsically safe, with standard arrangements certified FM or CSA as intrinsically safe and Division II.
Physical
Typical actuator weight is 275 lb (125 kg) and shipping weight 125 kg, with 1/4 inch NPT female air connections and 16 gauge pigtail leads for the electrical interface. It is a floor mounted drive, and the frame needs the same foundation and linkage alignment as any Hagan unit of this size.
Where it fits
Utility and industrial boiler forced and induced draft fans, secondary air and flue gas recirculation dampers on units where a 4x5 runs out of torque, and steel mill or refinery dampers that need closed-loop positioning with diagnostics.
Manufacturer reference: PowerVUE Product Data Sheet PDS 102-222.A01, PVD 610 ordering section, and Rosemount Analytical Damper Drives Product Data Sheet, 6 x 10 torque type floor mounted specifications.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | Repeatability ±0.5% of full stroke or better, against 1% for the pneumatic positioner on the same actuator; the actuator's unloaded full stroke is 5 seconds for the 10 in. stroke and 80 degrees on the pneumatic version |
| Output signal | Stall torque 1,800 ft-lb (2,441 N·m); maximum friction load 450 ft-lb (610 N·m); maximum weight load 600 ft-lb (814 N·m) over a 10 in. stroke producing 80 degrees of rotation |
| Diagnostics | ValveLink and AMS diagnostics through the DVC6000 with stored as-found signatures; single replaceable master module; optional 4-20 mA position transmitter with two limit contacts on HART versions |
| Pressure range | Air supply 45 to 120 psig (310 to 827 kPa gauge) with 100 psig recommended for the actuator; the digital controller vents continuously, and the published PowerVUE 4x5 figure of 10 scfm steady state is the order of magnitude to size the header by, not the 1 scfm of the pneumatic 6x10 |
| Variants | Assembly in brass or stainless with manual lock and mechanical air lock combinations and polymer or stainless tubing; DVC6000 as HART, fieldbus with or without basic control suite, or supplied by others |
| Application | Forced and induced draft fan dampers and large secondary air or flue gas recirculation dampers on utility and industrial boilers, where a 4x5 runs out of torque and closed loop positioning with diagnostics is wanted |
| Mounting | 6 x 10 torque type floor mounted; 275 lb (125 kg) typical actuator weight; 1/4 in. NPT female air supply and signal connections; 16 gauge pigtail leads for electrical connections |
| Operating temperature (°C) | 0 to 140 F (-18 to 60 C) for the actuator, extended to 160 F (71 C) with increased maintenance; the heater option is rated 115 V 150 W with thermostat and is not for hazardous areas |
Documents