Overview
Retrofit kit that converts an existing Hagan 4x5 or 8x14 pneumatic power positioner to a PowerVUE with an integral digital valve controller.
Key features
- Converts an existing Hagan 4x5 or 8x14 pneumatic power positioner to a PowerVUE with a FieldVUE DVC5000/6000 controller
- Kit PVD 468R contains the mounting bracket, DVC unit, air line tubing and fittings, cam assembly, limit switch spacer and reversing relay
- Raises the control end from 1% to ±0.5% repeatability without replacing the actuator, frame or linkage
- Some drilling and tapping required; the cover is modified in the field or a precut back cover 4851B28G01 is ordered
- Setup and calibration are the installer's responsibility, and performance varies with the age of the existing actuator
- HART (DVC6000) or fieldbus (DVC5000/5000f) controller selection, plus an optional digital EPT with two limit contacts
Key specifications
- Accuracy
- Raises the control end from 1% of full stroke on the pneumatic positioner to ±0.5% on the DVC5000/6000, with the caveat in the bulletin that performance may vary with the age of the Hagan actuator and the quality of the installation
- Output signal
- Controller choice determines the interface: 00 none, 01 HART with a DVC6000, 02 fieldbus with a DVC5000 and basic control suite, 03 fieldbus DVC5000f without the suite, 04 another DVC style by note
- Diagnostics
- Kit contents: mounting bracket, DVC electronic unit, air line tubing and fittings, cam assembly, limit switch spacer, reversing relay and the retrofit instruction bulletin IB-102-204P; setup and calibration are the installer's responsibility
- Pressure range
- The kit reuses the existing actuator's air supply and consumption; the DVC controller vents continuously, so the PowerVUE 4x5 figure of 10 scfm steady state is the order of magnitude when the header is being sized
- Variants
- PVD 468R with frame code 01 for 4x5 or 02 for 8x14, the controller code above, and an electronic position transmitter code 00 none or 01 digital EPT with two limit contacts on HART versions using a Moore Industries HART alarm
- Application
- Converting an existing Hagan 4x5 or 8x14 pneumatic power positioner to a PowerVUE drive with a FieldVUE digital valve controller, reusing the installed actuator, frame and linkage
A retrofit kit that puts a digital controller on the Hagan drive already bolted to the damper
The PowerVUE Retrofit Kit (PVD 468R) is not a drive. It is the package that converts an existing Hagan pneumatic power positioner — the 4x5 or the 8x14 — into a PowerVUE by replacing the force-balance positioner with a Fisher FieldVUE DVC5000/6000 digital valve controller, reusing the actuator, the frame and the linkage that are already installed.
Why anyone does this
A pneumatic positioner that has been in service for twenty years develops the two problems that make it hunt: a dirty relay and a spring whose characteristic has drifted. The usual answers are a rebuild or a new drive. The retrofit is the third option — the piston is usually fine, so the money goes into the control end, and the drive comes out of the job with ±0.5 percent repeatability and a diagnostic interface instead of a 1 percent mechanical positioner that has to be re-calibrated by hand.
What is in the box
Figure A-1 of the installation bulletin lists the contents: the mounting bracket, the DVC electronic unit, air line tubing and fittings, the cam assembly, a limit switch spacer, the reversing relay, and the PowerVUE actuator instruction bulletin with the retrofit instructions. The tubing is supplied uncut and unformed, so it is bent to the installation rather than pre-formed for a bench layout.
What the kit asks of the installer
The bulletin is explicit on three points, and they decide whether the job is a day or a week. Some drilling and tapping is required, and the existing cover can either be modified in the field or replaced with a precut back cover (P/N 4851B28G01). Performance may vary from the published specification depending on the age of the Hagan actuator and the quality of the DVC installation — a retrofit inherits the piston, the bore and the linkage it is fitted to. And setup and calibration are the responsibility of the installer, not of the kit.
Ordering
The model number is built from the frame (01 for 4x5, 02 for 8x14), the controller (00 none, 01 HART with a DVC6000, 02 fieldbus with a DVC5000 and basic control suite, 03 fieldbus DVC5000f without the suite, 04 another DVC style by note) and the electronic position transmitter option (00 none, 01 digital EPT with two limit contacts, HART versions only, using a Moore Industries Site Programmable HART alarm). The DVC can be supplied by others, but then no accuracy or response guarantee applies and its warranty sits with the other supplier.
Note on the 6x10
The ordering matrix in this bulletin covers the 4x5 and the 8x14. The 6x10 is a PowerVUE model in its own right (PVD 610), so a 6x10 conversion is normally quoted as that drive rather than as this kit — check the frame on the existing nameplate before ordering.
Where it fits
Plants with a fleet of Hagan drives in boiler and fan service that want digital positioning and diagnostics without replacing actuators that are mechanically sound — and that accept the installation work and the calibration responsibility that come with a retrofit.
Manufacturer reference: PowerVUE Fan/Damper Actuator Torque Type 4 x 5 with Retrofit Kit Installation Instructions IB-102-204P Rev. 1.1, retrofit ordering information and Appendix A kit contents.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | Raises the control end from 1% of full stroke on the pneumatic positioner to ±0.5% on the DVC5000/6000, with the caveat in the bulletin that performance may vary with the age of the Hagan actuator and the quality of the installation |
| Output signal | Controller choice determines the interface: 00 none, 01 HART with a DVC6000, 02 fieldbus with a DVC5000 and basic control suite, 03 fieldbus DVC5000f without the suite, 04 another DVC style by note |
| Diagnostics | Kit contents: mounting bracket, DVC electronic unit, air line tubing and fittings, cam assembly, limit switch spacer, reversing relay and the retrofit instruction bulletin IB-102-204P; setup and calibration are the installer's responsibility |
| Pressure range | The kit reuses the existing actuator's air supply and consumption; the DVC controller vents continuously, so the PowerVUE 4x5 figure of 10 scfm steady state is the order of magnitude when the header is being sized |
| Variants | PVD 468R with frame code 01 for 4x5 or 02 for 8x14, the controller code above, and an electronic position transmitter code 00 none or 01 digital EPT with two limit contacts on HART versions using a Moore Industries HART alarm |
| Application | Converting an existing Hagan 4x5 or 8x14 pneumatic power positioner to a PowerVUE drive with a FieldVUE digital valve controller, reusing the installed actuator, frame and linkage |
| Mounting | Mounting bracket and cam assembly supplied; the bulletin states that some drilling and tapping is required, and the existing cover is either modified in the field or replaced with precut back cover P/N 4851B28G01 |
| Operating temperature (°C) | Governed by the host actuator and the DVC controller; the kit adds no separate temperature rating, so the installed drive keeps the rating of the frame it is fitted to |
Documents