Rosemount R306 Enhanced In-Line Manifold
No product images are published for this product yet.
Purchase options
From$121.06
- Availability
- Call for availability Originalx
Configurable — choose options to build the exact part number.
Independent supplier
Sproh is an independent supplier and is not an authorized distributor or official representative of Rosemount or Emerson.
Overview
In-line manifold for a gauge transmitter or pressure gauge: block-and-bleed or two-valve, with the Pressure-Lock stem and no intermediate flange.
Key features
- In-line manifold for the 3051S In-Line pressure transmitter or a Rosemount pressure gauge, assembled directly to the instrument
- Block-and-bleed or two-valve configuration: one isolation and one vent, because a gauge measurement has no second side to equalise
- A three-valve coplanar manifold on a gauge transmitter adds an equalising valve with nothing to connect, plus wetted surface and a stem that can leak
- Pressure-Lock valve with two-piece stem: needle-tip safety back seating, process-isolated stem threads, and a tip that does not score the seat
- No intermediate flange, nipple or union - the stack is one machined body, factory leak-tested and calibrated with the instrument
- Female NPT process connections, special cleaning options available, and the same valve design as the coplanar R305
Key specifications
- Accuracy
- Not a measurement device - the manifold carries the impulse path and protects the instrument's own accuracy claim by giving it a clean, isolatable connection
- Output signal
- Not applicable; the manifold is a passive valve body with no electrical function
- Diagnostics
- A gauge measurement has one pressure port, so an equalising valve has nothing to connect: that is why this body carries two valves and not three. Pressure-Lock valve with two-piece stem, needle-tip safety back seating and process-isolated threads, shared with the R305
- Pressure range
- Set by the manifold body class and the instrument it is bolted to; the assembly leaves the factory leak-tested and calibrated as a single pressure boundary rather than a box of fittings
- Variants
- Block-and-bleed or two-valve configuration. Female NPT process connections and special cleaning options. In-line style for gauge measurement; the coplanar three- or five-valve R305 is the DP equivalent
- Application
- Gauge pressure measurement where a 3051S In-Line transmitter or a Rosemount pressure gauge needs isolation and venting at the point of measurement: process lines, headers and skids
Two valves, because a gauge measurement has nothing to equalise
The Rosemount R306 is the in-line member of the enhanced manifold range: a body that mounts directly to a 3051S In-Line pressure transmitter or to a Rosemount pressure gauge. It comes as block-and-bleed or two-valve, in the same Pressure-Lock valve design as the coplanar R305.
The two-valve body is not a cost-reduced three-valve body
An in-line measurement has one pressure port. A coplanar DP manifold carries three valves because two isolation valves plus an equalising valve are what a differential measurement needs — the equalise valve lets both sides of the DP cell sit at the same pressure while it is zeroed. On a gauge measurement there is no second side, so an equalising valve has nothing to connect. The R306 carries one isolation valve and one vent or bleed, and that is the complete set of functions the measurement has.
This matters at specification time, not at installation. A three-valve coplanar manifold ordered onto a gauge transmitter arrives with a valve that cannot do anything, and on a live plant the extra body volume is a real cost: more wetted surface, more places for the process to collect, one more stem to leak. The right number of valves is set by the measurement, not by the range the manifold belongs to.
Block-and-bleed against two-valve
Both are offered, and the difference is where the vent sits. A block-and-bleed body puts isolation and bleed in one assembly, which is the compact arrangement for a gauge or a transmitter on a line where the vent only needs to release pressure before the instrument is removed. A two-valve body gives the vent its own valve and its own outlet, which is what a calibration or vent-to-a-safe-point installation needs. Choosing between them is a question about what the technician will do at that point, not about performance.
The same stem, and the same reason it exists
The Pressure-Lock valve is shared with the R305, and it carries the three properties that matter on any manifold regardless of valve count:
- Needle-tip safety back seating — with the valve fully back the tip seals against a back seat, so a packing failure cannot eject the stem under pressure.
- Process-isolated stem threads — the threads stay out of the wetted path, so they do not corrode or gall, which is what keeps the valve operable years after installation.
- Two-piece stem — the tip does not rotate against the seat, so the seat is not scored by grit on every stroke.
What "assembled directly" removes
The manifold bolts to the instrument with no intermediate flange and no exposed bolt configuration. On an in-line installation the alternative is a nipple and a valve and a union between the process and the transmitter, and each of those is a joint with its own leak path and its own torque. The R306 collapses that stack into one machined body, factory leak-tested and calibrated with the instrument it ships with, so what arrives is a tested pressure boundary rather than a box of fittings.
Where it fits
Gauge pressure measurement on a line where the transmitter or gauge needs isolation and venting at the point of measurement: process lines with a 3051S In-Line transmitter, pressure gauges on headers and skids, and any installation that currently uses a nipple-and-valve stack. It is the right choice precisely where a DP manifold would be wrong, and knowing which of the two applies is most of the selection.
Manufacturer reference: Rosemount Manifold Solutions product data sheet, R306 in-line section, Pressure-Lock valve technology and ordering information.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | Not a measurement device - the manifold carries the impulse path and protects the instrument's own accuracy claim by giving it a clean, isolatable connection |
| Output signal | Not applicable; the manifold is a passive valve body with no electrical function |
| Diagnostics | A gauge measurement has one pressure port, so an equalising valve has nothing to connect: that is why this body carries two valves and not three. Pressure-Lock valve with two-piece stem, needle-tip safety back seating and process-isolated threads, shared with the R305 |
| Pressure range | Set by the manifold body class and the instrument it is bolted to; the assembly leaves the factory leak-tested and calibrated as a single pressure boundary rather than a box of fittings |
| Variants | Block-and-bleed or two-valve configuration. Female NPT process connections and special cleaning options. In-line style for gauge measurement; the coplanar three- or five-valve R305 is the DP equivalent |
| Application | Gauge pressure measurement where a 3051S In-Line transmitter or a Rosemount pressure gauge needs isolation and venting at the point of measurement: process lines, headers and skids |
| Mounting | Assembles directly to the transmitter or gauge with no intermediate flange, nipple or union, so the stack from the process to the instrument is one machined body |
| Operating temperature (°C) | Governed by the body and packing material selected for the service, with the same material options as the coplanar range |
Documents
Accessories and related items
Accessories and related items for this product are not available to order on Sproh yet. If the manufacturer lists them, an engineer can source them for you.
Ask an engineer