Rosemount RBI pH Sensors
Purchase options
From$432.02
- Availability
- Call for availability Originalx
Configurable — choose options to build the exact part number.
Independent supplier
Sproh is an independent supplier and is not an authorized distributor or official representative of Rosemount or Emerson.
Overview
Kynar body pH/ORP sensor with multi-junction reference: 0-14 pH, 150 psig at 158 F, threaded in-line or retractable through a ball valve.
Key features
- Kynar body pH/ORP sensor with a multi-junction reference for streams carrying sulfides and other poisoning ions
- pH 0 to 14, or ORP -1500 to +1500 mV in the B10 platinum version
- Body 546: forward and rear facing 3/4 in. MNPT for in-line tees or submersion; body 547: retractable through a user-supplied ball valve
- 150 psig at 158 F (70 C), and 248 F (120 C) at 40 psig; retractable limits 65 psig insertion and 40 psig retraction
- Electrodes: A10 hemi-glass 0-14 or A11 flat glass 1-14, both with PT100 RTD; B10 ORP without temperature compensation
- EPDM, Viton or Kalrez O-rings; titanium on the 547 only; universal VP8 Variopol cable connector
Key specifications
- Accuracy
- pH range 0 to 14 on the A10 hemi-glass and A11 flat glass electrodes, and -1500 to +1500 mV on the B10 platinum ORP electrode; A10 and A11 carry a PT100 RTD for temperature compensation, B10 has none
- Output signal
- Analog measurement electrode potential to the transmitter, with PT100 RTD compensation on A10 and A11; universal VP8 Variopol connector allows quick cable release at the sensor
- Diagnostics
- Multi-junction reference design extends life in poisoning service; wetted materials are Kynar, titanium on the 547 only, porous PTFE, wood, glass and the selected O-ring elastomer
- Pressure range
- Maximum pressure 150 psig (1,035 kPa abs) at 158 F (70 C); the retractable body 547 is limited to 65 psig insertion pressure at 158 F and 40 psig retraction pressure at 248 F
- Variants
- Electrode A10 ruggedised hemi-glass 0-14 pH, A11 ruggedised flat glass 1-14 pH, B10 platinum ORP; tip D1 dual notched PTFE junction with tip protection or F1 flush PTFE junction without; O-rings EPDM, Viton or Kalrez
- Application
- pH/ORP measurement in streams with sulfides and other poisoning ions: pulp and paper stock and white water, chemical process, wastewater with high solids, and points needing removal without a shutdown
A pH sensor built to survive poisoning ions rather than to be cleaned every month
The Rosemount RBI is a pH/ORP sensor with a Kynar body and a multi-junction reference, made for the streams where a conventional sensor dies young: sulfides and other poisoning species that diffuse into the reference and drag its potential off until the reading no longer means anything. It comes in a threaded in-line/submersion body and a retractable version that inserts through a ball valve.
The reference is the specification that matters
Most pH failures in industrial service are reference failures, not glass failures. A single-junction reference leaks electrolyte and lets process ions migrate into the reference element; when those ions are sulfides the junction plugs and the potential drifts in a way no buffer calibration can fix. The RBI's multi-junction design puts intermediate junctions between the process and the reference, which slows that migration and extends the sensor's useful life in exactly the applications where the annual spend on sensors is a line item.
Two body types, two different installation jobs
Body 546 has forward and rear facing ¾ inch MNPT process connections, so it drops into a pipe tee for in-line measurement or screws onto a ¾ inch FNPT coupling extension for submersion in a tank. Body 547 is the retractable version: it slides through a ball valve so the sensor can be removed for cleaning or calibration without draining the line, and it needs a user-supplied 1 inch MNPT fitting or ball valve set — that fitting is not part of the sensor.
Pressure and temperature are coupled
The headline ratings read together, not separately: 150 psig at 158 °F (70 °C) and 248 °F (120 °C) at 40 psig. For the retractable 547 the limits tighten further — 65 psig insertion at 158 °F and 40 psig retraction at 248 °F — because the sensor has to be moved through the packing while pressurised. A line running hot and at pressure at the same time is the case where a standard sensor is installed and then found to be outside both corners of the envelope.
Electrode choices
Three measurement types: A10 ruggedised hemi-glass for 0-14 pH with a PT100 RTD for temperature compensation, A11 ruggedised flat glass for 1-14 pH with a PT100 (the flat glass is the one for streams carrying solids that would abrade or coat a bulb), and B10 platinum ORP covering ±1500 mV with no temperature compensation. Tip configurations are D1, a dual notched PTFE junction with tip protection, and F1, a flush PTFE junction without it — the D1 is the choice where the sensor is handled or where the process has grit.
Materials and connection
Wetted materials are Kynar, titanium on the retractable 547 only, porous PTFE, wood, glass and a choice of EPDM, Viton or Kalrez O-rings. The O-ring choice is a real decision, not a default: Viton for hydrocarbons, EPDM for many aqueous and steam services, Kalrez where both are aggressive. The universal VP8 Variopol connector lets the cable be released at the sensor rather than pulled back through conduit.
Where it fits
Pulp and paper stock and white water, chemical process streams with sulfide load, wastewater with high solids, and any point where the sensor has to be pulled for cleaning without a shutdown — the retractable body exists for those, and the flat glass electrode exists for the ones that would destroy a bulb.
Manufacturer reference: Rosemount RBI pH/ORP Sensors Product Data Sheet 00813-0100-3008 Rev AD, ordering information and specifications.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | pH range 0 to 14 on the A10 hemi-glass and A11 flat glass electrodes, and -1500 to +1500 mV on the B10 platinum ORP electrode; A10 and A11 carry a PT100 RTD for temperature compensation, B10 has none |
| Output signal | Analog measurement electrode potential to the transmitter, with PT100 RTD compensation on A10 and A11; universal VP8 Variopol connector allows quick cable release at the sensor |
| Diagnostics | Multi-junction reference design extends life in poisoning service; wetted materials are Kynar, titanium on the 547 only, porous PTFE, wood, glass and the selected O-ring elastomer |
| Pressure range | Maximum pressure 150 psig (1,035 kPa abs) at 158 F (70 C); the retractable body 547 is limited to 65 psig insertion pressure at 158 F and 40 psig retraction pressure at 248 F |
| Variants | Electrode A10 ruggedised hemi-glass 0-14 pH, A11 ruggedised flat glass 1-14 pH, B10 platinum ORP; tip D1 dual notched PTFE junction with tip protection or F1 flush PTFE junction without; O-rings EPDM, Viton or Kalrez |
| Application | pH/ORP measurement in streams with sulfides and other poisoning ions: pulp and paper stock and white water, chemical process, wastewater with high solids, and points needing removal without a shutdown |
| Mounting | Body 546 with forward and rear facing 3/4 in. MNPT for a pipe tee or a 3/4 in. FNPT coupling extension for submersion; body 547 retractable, requiring a user-supplied 1 in. MNPT fitting or ball valve set |
| Operating temperature (°C) | Maximum temperature 248 F (120 C) at 40 psig; the pressure and temperature ratings apply as a pair, so a hot and pressurised line must satisfy both corners |
Documents
Accessories and related items
Accessories and related items for this product are not available to order on Sproh yet. If the manufacturer lists them, an engineer can source them for you.
Ask an engineer