Rosemount 2140 Level Switch
No product images are published for this product yet.
Purchase options
From$583.19
- Availability
- Call for availability Originalx
Configurable — choose options to build the exact part number.
Independent supplier
Sproh is an independent supplier and is not an authorized distributor or official representative of Rosemount or Emerson.
Overview
Wired HART vibrating fork liquid level switch, SIL 2 with HFT=0, with remote proof testing and liquid-to-sediment detection on profile A.
Key features
- Wired HART vibrating fork point level switch for liquids, switchable between HART 5 and HART 7, available as the standard 2140 and the 2140:SIS variant
- IEC 61508 certified to SIL 2 with HFT = 0, so a single device can serve a simplex safety loop
- Remote proof testing as well as local proof testing with a test button, so the routine SIL proof test can be run without access equipment or a shutdown
- Two ordering profiles that are not equivalent: profile A includes sediment detection and the scaled variable, profile F does not, while both keep remote and local proof testing
- Liquid-to-sediment detection is the exclusive capability that turns a false high-level alarm from an unexplained shutdown into a maintenance instruction
- Fast Drip fork design drains quickly after the level falls, which shortens the dry response delay that matters on pump protection
Key specifications
- Accuracy
- Not an analogue measurement - a repeatable point switch driven by a piezo-electric crystal oscillating the forks at their natural frequency, with the frequency change on immersion detected by the electronics
- Output signal
- mA output with HART communication, switchable between HART 5 and HART 7 so it drops into an existing wired loop without additional wiring. Media learn, frequency output and settable HART alerts
- Diagnostics
- IEC 61508 certified to SIL 2 with HFT = 0, so one device serves a simplex safety loop. Remote proof testing keeps the actual proof-test interval aligned with the interval the safety case assumes. Liquid-to-sediment detection (profile A) distinguishes a vessel filled with settled solids from a genuine high liquid level - the failure that otherwise reports a permanent, correct and useless covered state
- Pressure range
- Set by the process connection and fork material selected. Operating temperature for the mid-range option is -40 to 356 F (-40 to 180 C), with other options in the ordering table
- Variants
- 2140 standard and 2140:SIS. Two profile options: A includes sediment detection and the scaled variable; F omits both. Both profiles retain remote proof testing, local proof testing with the test button, media learn, frequency output and the smart diagnostic suite
- Application
- High and low level alarms, pump control and limit detection, run-dry and pump protection on liquid vessels, and SIS applications that need a SIL 2 single device with remote proof testing
A proof test you can run without climbing the tank
The Rosemount 2140 is a wired HART vibrating fork point level switch for liquids, available as the standard instrument and as the 2140:SIS variant. It is IEC 61508 certified to SIL 2 with HFT = 0, and its two distinguishing features are not about the fork at all: it can be proof tested remotely, and it can detect that the vessel has filled with sediment.
Why remote proof testing is the feature that matters
A SIL-rated point switch carries an obligation, not just a rating: the proof test has to be performed at the interval the safety lifecycle assumes. On a tank, the traditional proof test means a person physically at the instrument, disturbing the fork — lifting it, draining the vessel, or pouring something over it — and confirming that the output changed. That is slow, it needs access, it often needs the process shut down or bypassed, and it is the step that gets deferred when the plant is busy.
Every deferral pushes the actual proof-test interval past the assumed one, which silently changes the safety case. The 2140 offers remote proof testing as well as local proof testing using a test button on the instrument, so the routine test can be performed from the control room rather than from a ladder. Both methods are listed as available on both profile options, which is unusual and useful: the safety function does not have to be traded against testability.
Two profiles, and one of them drops a feature
Ordering involves a profile selection, and the two options are not equivalent:
| Feature | Profile A | Profile F |
|---|---|---|
| Remote proof testing | Yes | Yes |
| Local proof testing (test button) | Yes | Yes |
| Media learn | Yes | Yes |
| Frequency output | Yes | Yes |
| Sediment detection | Yes | No |
| Scaled variable | Yes | No |
| Smart diagnostic suite | Yes | Yes |
The proof-test capability is common to both, but sediment detection exists only on profile A. So a site that chose profile F for its loop requirements and then reads the product page expecting "liquid-to-sediment detection" has bought an instrument without it. That is the sort of detail that is invisible in a purchase order description and obvious in a failure investigation.
Sediment, which is how a liquid fork actually fails
A vibrating fork is damped by whatever is in contact with it. In clean liquid the change between wet and dry is large and unambiguous. The failure mode is sediment: the vessel fills with sludge, scale or settled solids up to the fork, and the instrument reports "covered" permanently — correctly, from its own point of view, and uselessly for the process. The measurement has not drifted; the instrument is telling the truth about a condition that the control system interprets as a liquid level.
The feature is described as exclusive liquid-to-sediment detection, and it is the one capability that turns a false "high level" alarm from an unexplained shutdown into a maintenance instruction. On a tank that accumulates solids — brine, slurry settlers, wastewater wet wells, crystallising chemicals — that distinction pays for itself once.
The fork, and the fast-drip variant
The measuring principle is the familiar tuning fork: a piezo-electric crystal oscillates the forks at their natural frequency, and immersion in a medium changes that frequency and amplitude, which the electronics detect. The "Fast Drip" fork design matters for liquids that coat or are viscous: a conventional fork holds a film of liquid between the tines after the level falls, so the "dry" signal arrives late. A fork shaped to drain quickly shortens that delay, which matters on pump protection where the delay is exactly what the pump is exposed to.
Integration, which is the wired HART angle
The instrument communicates over wired HART and can be switched between HART 5 and HART 7, so it drops into an existing wired loop without additional wiring — which matters on a brownfield tank farm where pulling new cable is the expensive part of any upgrade. Media learn allows the instrument to be taught the medium it is in, and the smart diagnostic suite plus settable HART alerts expose the device's own condition rather than only its switch state.
Where it fits
High and low level alarms, pump control and limit detection, run-dry and pump protection on liquid vessels, and SIS applications that need a SIL 2 single device with remote proof testing. Choose the profile deliberately: if sediment detection or the scaled variable is part of the justification, profile A is the requirement and the safety function has to be checked against it.
Manufacturer reference: Rosemount 2140 and 2140:SIS Level Detector Product Data Sheet for the tuning fork principle, profile selection features, SIL certification and ordering information.
Specifications
| Attribute | Value |
|---|---|
| Accuracy | Not an analogue measurement - a repeatable point switch driven by a piezo-electric crystal oscillating the forks at their natural frequency, with the frequency change on immersion detected by the electronics |
| Output signal | mA output with HART communication, switchable between HART 5 and HART 7 so it drops into an existing wired loop without additional wiring. Media learn, frequency output and settable HART alerts |
| Diagnostics | IEC 61508 certified to SIL 2 with HFT = 0, so one device serves a simplex safety loop. Remote proof testing keeps the actual proof-test interval aligned with the interval the safety case assumes. Liquid-to-sediment detection (profile A) distinguishes a vessel filled with settled solids from a genuine high liquid level - the failure that otherwise reports a permanent, correct and useless covered state |
| Pressure range | Set by the process connection and fork material selected. Operating temperature for the mid-range option is -40 to 356 F (-40 to 180 C), with other options in the ordering table |
| Variants | 2140 standard and 2140:SIS. Two profile options: A includes sediment detection and the scaled variable; F omits both. Both profiles retain remote proof testing, local proof testing with the test button, media learn, frequency output and the smart diagnostic suite |
| Application | High and low level alarms, pump control and limit detection, run-dry and pump protection on liquid vessels, and SIS applications that need a SIL 2 single device with remote proof testing |
| Mounting | Threaded process connection into the vessel or pipe with the fork at the switching level. Proof testing can be performed remotely or from the local test button, so routine testing does not require access equipment |
| Operating temperature (°C) | Mid-range option -40 to 356 F (-40 to 180 C). The fast drip fork design gives a quicker dry response for liquids that coat or drain slowly between the tines |
Documents
Accessories and related items
Accessories and related items for this product are not available to order on Sproh yet. If the manufacturer lists them, an engineer can source them for you.
Ask an engineer