Ir al contenido principal
Vendido y enviado por Sproh

Interruptor de nivel Rosemount 2140

Número de pieza2140FabricanteEmerson

Todavía no hay imágenes publicadas para este producto.

Opciones de compra

Desde583,19 US$

Disponibilidad
Consultar disponibilidad Original
Seleccionar opción

Configurable: elija las opciones para construir el número de pieza exacto.

Proveedor independiente

Sproh es un proveedor independiente y no es un distribuidor autorizado ni representante oficial de Rosemount o Emerson.

Resumen

Interruptor de nivel de horquilla vibrante con HART cableado, SIL 2 con HFT=0, con prueba de funcionamiento remota y detección de sedimento líquido en el perfil A.

Especificaciones principales

Exactitud
Not an analogue measurement - a repeatable point switch driven by a piezo-electric crystal oscillating the forks at their natural frequency, with the frequency change on immersion detected by the electronics
Señal de salida
mA output with HART communication, switchable between HART 5 and HART 7 so it drops into an existing wired loop without additional wiring. Media learn, frequency output and settable HART alerts
Diagnósticos
IEC 61508 certified to SIL 2 with HFT = 0, so one device serves a simplex safety loop. Remote proof testing keeps the actual proof-test interval aligned with the interval the safety case assumes. Liquid-to-sediment detection (profile A) distinguishes a vessel filled with settled solids from a genuine high liquid level - the failure that otherwise reports a permanent, correct and useless covered state
Rango de presión
Set by the process connection and fork material selected. Operating temperature for the mid-range option is -40 to 356 F (-40 to 180 C), with other options in the ordering table
Variantes
2140 standard and 2140:SIS. Two profile options: A includes sediment detection and the scaled variable; F omits both. Both profiles retain remote proof testing, local proof testing with the test button, media learn, frequency output and the smart diagnostic suite
Aplicación
High and low level alarms, pump control and limit detection, run-dry and pump protection on liquid vessels, and SIS applications that need a SIL 2 single device with remote proof testing
Ver todas las especificaciones